NEC Wire Sizing

What Size Wire for an Electric Cooktop?

The breaker, copper and aluminum wire, and ground for a typical electric cooktop circuit, with the NEC basis and the nameplate caveats that actually decide it.

Quick answer: An electric cooktop typically needs a 40A / 240V circuit with #8 copper (or #8 aluminum) wire and a #10 copper ground.

Electric Cooktop Circuit Spec

Typical branch circuit for an electric cooktop (nameplate rating)
Voltage240V
Breaker40A
Copper wire#8
Aluminum wire (75°C, SER or conduit)#8
Equipment ground (Cu)#10

Cooktops range from 30A to 50A depending on the number and size of elements. A standard four-burner cooktop is commonly on a 40A circuit; size to the nameplate. Under the 2023 NEC (210.8(A)), a dwelling cooktop receptacle requires GFCI protection; this 2023 expansion is still being adopted, so verify your local edition. Wire sized at NEC Table 310.16 (copper lead at the 60°C column for NM-B); ground per NEC Table 250.122. The appliance nameplate lists the exact minimum circuit and maximum breaker; it always governs over a typical value.

Aluminum branch conductors are 75°C-rated AA-8000 alloy (SER cable, or XHHW-2 / THWN-2 in conduit); there is no 60°C aluminum NM-B, so the aluminum row uses the 75°C column. Where the terminations are rated 60°C only, size aluminum from the 60°C column instead (#6 here).

Adding this as a new load? Check whether your panel can handle it (the NEC 220.87 service check), or compare it against the breaker size by load chart.


Long Run? Size It Exactly

For a long run where voltage drop matters, or a nameplate that differs from the typical value, enter your exact load, distance, and conditions.

Loading calculator...

Frequently Asked Questions

What size wire do I need for an electric cooktop?

An electric cooktop typically uses a 40A / 240V circuit, which calls for #8 copper (or #8 aluminum) conductors and a #10 copper equipment ground per NEC Table 250.122. Cooktops range from 30A to 50A depending on the number and size of elements. A standard four-burner cooktop is commonly on a 40A circuit; size to the nameplate. Under the 2023 NEC (210.8(A)), a dwelling cooktop receptacle requires GFCI protection; this 2023 expansion is still being adopted, so verify your local edition.

What size breaker for an electric cooktop?

A 40A double-pole (240V) breaker. The #8 copper conductors are matched to that 40A rating. Do not oversize the breaker to a wire it does not protect: the breaker and the conductor go up together. Always confirm against the appliance nameplate, which lists the exact minimum circuit and maximum overcurrent device.

Can I use aluminum wire for an electric cooktop?

Yes. On the 75C column (the usual basis for aluminum), a 40A circuit needs #8 aluminum, versus #8 copper. Aluminum is common on larger circuits and services to save cost; apply antioxidant to the terminations, torque to the listed spec, and remember aluminum drops slightly more voltage on long runs.

What size breaker for a stovetop?

Same answer: stovetop is another name for an electric cooktop. It uses a 40A / 240V circuit with #8 copper wire and a #10 copper ground. Cooktops range from 30A to 50A depending on the number and size of elements. A standard four-burner cooktop is commonly on a 40A circuit; size to the nameplate. Under the 2023 NEC (210.8(A)), a dwelling cooktop receptacle requires GFCI protection; this 2023 expansion is still being adopted, so verify your local edition.


Wire Size for Other Appliances