NEC Wire Sizing

What Size Wire for an Electric Cooktop?

The breaker, copper and aluminum wire, and ground for the electric cooktop circuit this page shows, with the NEC basis and the nameplate caveats that actually decide it.

Quick answer: This page shows an electric cooktop on a 40A / 240V circuit with #8 copper (or #6 aluminum; #8 aluminum only on 75°C-marked terminations; aluminum on terminals identified for aluminum, NEC 2023, 110.14(A)) wire and a #10 copper ground. GE's quick specs for the JP3030DJ 30" electric cooktop list, at 240V, CONNECTED LOAD (MAX.) "7.4kW", CURRENT DRAW (MAX.) "30.8 Amps" and RECOMMENDED CIRCUIT BREAKER "40 Amps" It must be GFCI protected.

Electric Cooktop Circuit Spec

Branch circuit shown for an electric cooktop (nameplate rating, GFCI per NEC 210.8(D))

Swipe the table sideways to see the rest of its columns. →

Voltage240V
Breaker40A GFCI
Copper wire#8
Aluminum wire (75°C-marked terminations, SER or conduit)#8
Equipment ground (Cu)#10

Size to the nameplate and the maker's breaker: GE's quick specs for its 30-inch JP3030DJ list a 7.4 kW connected load, a 30.8 amps maximum current draw and a 40 Amps recommended circuit breaker at 240 volts, the circuit this page shows. On a 240V circuit, a 2-pole GFCI breaker is one way to provide GFCI protection. GFCI: NEC 2023 210.8(D) requires GFCI protection for the branch circuit or outlet supplying an electric cooktop (210.8(D)(10) "Counter-mounted cooking units") rated 150 volts or less to ground and 60 amperes or less, hardwired or plugged in, wherever it is installed; which edition applies is the one your jurisdiction has adopted. Wire sized at NEC Table 310.16 (copper lead at the 60°C column for NM-B); ground per NEC Table 250.122. The appliance nameplate lists the exact minimum circuit and maximum breaker; it governs over the circuit shown here.

Maker's instruction: GE JP3030DJ/TJ 30" Built-In Knob-Control Electric Cooktop, Quick Specs (Specification Revised 6/20), read 2026-11-13.

Aluminum branch conductors are 75°C-rated AA-8000 alloy (SER cable, or XHHW-2 / THWN-2 in conduit); there is no 60°C aluminum NM-B, so the aluminum row uses the 75°C column. Where the terminations are rated 60°C only, size aluminum from the 60°C column instead (#6 here). Aluminum: the terminals it lands on must be identified for aluminum conductors (NEC 2023, 110.14(A)).

Adding this as a new load? Check whether your panel can handle it (the NEC 220.87 service check), or compare it against the breaker size by load chart.


Size Your Exact Circuit

It opens on this page's 40 A circuit at the 60°C column. For a nameplate that differs from this page's circuit, enter your exact load and conditions. For a long run, the result links to the voltage drop calculator, which checks that wire over your run; this tool does not size for voltage drop.

Loading calculator...

The code sections this page cites are named in the source receipt.


Frequently Asked Questions

What size wire do I need for an electric cooktop?

This page shows an electric cooktop on a 40A / 240V circuit, which calls for #8 copper (or #6 aluminum; #8 aluminum only on 75°C-marked terminations; aluminum on terminals identified for aluminum, NEC 2023, 110.14(A)) conductors and a #10 copper equipment ground per NEC Table 250.122. GE's quick specs for the JP3030DJ 30" electric cooktop list, at 240V, CONNECTED LOAD (MAX.) "7.4kW", CURRENT DRAW (MAX.) "30.8 Amps" and RECOMMENDED CIRCUIT BREAKER "40 Amps" Size to the nameplate and the maker's breaker: GE's quick specs for its 30-inch JP3030DJ list a 7.4 kW connected load, a 30.8 amps maximum current draw and a 40 Amps recommended circuit breaker at 240 volts, the circuit this page shows. On a 240V circuit, a 2-pole GFCI breaker is one way to provide GFCI protection. GFCI: NEC 2023 210.8(D) requires GFCI protection for the branch circuit or outlet supplying an electric cooktop (210.8(D)(10) "Counter-mounted cooking units") rated 150 volts or less to ground and 60 amperes or less, hardwired or plugged in, wherever it is installed; which edition applies is the one your jurisdiction has adopted.

What size breaker for an electric cooktop?

A 40A double-pole (240V) breaker. The #8 copper conductors are matched to that 40A rating, and it must be a GFCI breaker (or GFCI protection ahead of the appliance). Do not oversize the breaker to a wire it does not protect: the breaker and the conductor go up together. Always confirm against the appliance nameplate, which lists the exact minimum circuit and maximum overcurrent device.

Does an electric cooktop need GFCI protection?

Yes. GFCI: NEC 2023 210.8(D) requires GFCI protection for the branch circuit or outlet supplying an electric cooktop (210.8(D)(10) "Counter-mounted cooking units") rated 150 volts or less to ground and 60 amperes or less, hardwired or plugged in, wherever it is installed; which edition applies is the one your jurisdiction has adopted. Use a GFCI breaker or a GFCI device ahead of it.

Can I use aluminum wire for an electric cooktop?

Yes. On the 75C column (the column this page reads for aluminum), a 40A circuit needs #8 aluminum, versus #8 copper. Aluminum: the terminals it lands on must be identified for aluminum conductors (NEC 2023, 110.14(A)). If you run aluminum, apply antioxidant to the terminations, torque to the listed spec, and remember aluminum drops slightly more voltage on long runs.

What size breaker for a stovetop?

Same answer: stovetop is another name for an electric cooktop. It uses a 40A / 240V circuit with #8 copper wire and a #10 copper ground. Size to the nameplate and the maker's breaker: GE's quick specs for its 30-inch JP3030DJ list a 7.4 kW connected load, a 30.8 amps maximum current draw and a 40 Amps recommended circuit breaker at 240 volts, the circuit this page shows. On a 240V circuit, a 2-pole GFCI breaker is one way to provide GFCI protection. GFCI: NEC 2023 210.8(D) requires GFCI protection for the branch circuit or outlet supplying an electric cooktop (210.8(D)(10) "Counter-mounted cooking units") rated 150 volts or less to ground and 60 amperes or less, hardwired or plugged in, wherever it is installed; which edition applies is the one your jurisdiction has adopted.


Wire Size for Other Appliances