Electrical Tool
Electrical Rough-In Checklist by Room
Enter the rooms. Each one gets its GFCI, AFCI and receptacle rules, and the dwelling its required circuits, each line with its NEC cite.
- Kitchen small-appliance 1: a 20 A branch circuit. Serves the kitchen's countertop, wall and floor receptacles and the refrigerator's, and may also serve the pantry, breakfast room and dining room; in addition to the required receptacles, a specific appliance's receptacle (a refrigerator's, say) may have its own circuit of 15 A or more (210.11(C)(1), 210.52(B)(1), 210.52(B)(1) Exception No. 2)
- Kitchen small-appliance 2: a 20 A branch circuit. Serves the kitchen's countertop, wall and floor receptacles and the refrigerator's, and may also serve the pantry, breakfast room and dining room; in addition to the required receptacles, a specific appliance's receptacle (a refrigerator's, say) may have its own circuit of 15 A or more (210.11(C)(1), 210.52(B)(1), 210.52(B)(1) Exception No. 2)
- Laundry: a 20 A branch circuit. The laundry receptacle outlets only (210.11(C)(2))
- Bathroom receptacles: a 20 A branch circuit. Bathroom receptacles only; where it supplies a single bathroom, outlets for other equipment in that bathroom may be on it within 210.23(B)(1) and (B)(2) (210.11(C)(3), 210.11(C)(3) Exception)
- Garage receptacles: a 20 A branch circuit. The garage receptacles and no other outlets, except that it may also supply outdoor receptacles, and where it supplies a single vehicle bay garage, outlets for other equipment within that garage may be on it within 210.23(B)(1) and (B)(2); added circuits of 15 A or more may serve its other receptacles (210.11(C)(4), 210.11(C)(4) Exception No. 1, 210.11(C)(4) Exception No. 2)
From NFPA 70, 2023 edition. A state, city or county can amend these rules; confirm with your inspector.
Kitchen
- Its receptacles: GFCI (210.8(A)(6))
- The branch circuit or outlet supplying a dishwasher, an electric range, a wall-mounted oven, a counter-mounted cooking unit and a microwave oven (150 V or less to ground, 60 A or less): GFCI (210.8(D)(7), 210.8(D)(8), 210.8(D)(9), 210.8(D)(10), 210.8(D)(12))
- Every 120 V, 10, 15 and 20 A branch circuit supplying outlets or devices here: AFCI, except the circuits 210.12(B)'s exceptions name (listed for the whole dwelling) (210.12(B)(1))
- No point along the floor line of any wall space more than 6 ft from a receptacle outlet (210.52(A)(1))
- A wall space is any space 2 ft or wider, measured around corners, unbroken by doorways, fireplaces, stationary appliances and fixed cabinets without countertops (210.52(A)(2)(1))
- A floor receptacle counts only within 18 in of the wall; countertop receptacles do not count toward these (210.52(A)(3), 210.52(A)(4))
- Its wall, floor and countertop receptacles and the refrigerator's are on the 20 A small-appliance circuits, which have no other outlets; in addition to the required receptacles, one for a specific appliance (a refrigerator, say) may have its own circuit of 15 A or more, and a clock receptacle or one powering a gas range's, oven's or cooktop's supplemental equipment and lighting may be on a small-appliance circuit (210.52(B)(1), 210.52(B)(2), 210.52(B)(1) Exception No. 2, 210.52(B)(2) Exception No. 1, 210.52(B)(2) Exception No. 2)
- Countertop receptacles on at least two small-appliance circuits, and no small-appliance circuit serves another kitchen (210.52(B)(3))
- Countertops and work surfaces 12 in or wider: no point along the wall line more than 24 in from a receptacle outlet (210.52(C)(1))
- Island or peninsula without a receptacle: provisions there for one later (210.52(C)(2))
- Countertop receptacles on or not more than 20 in above it, or in it or a work surface as listed assemblies (210.52(C)(3))
Dining room
- GFCI: not for the room itself; the dwelling's sink, bathtub and damp location rules below still apply (210.8(A))
- Every 120 V, 10, 15 and 20 A branch circuit supplying outlets or devices here: AFCI, except the circuits 210.12(B)'s exceptions name (listed for the whole dwelling) (210.12(B)(3))
- No point along the floor line of any wall space more than 6 ft from a receptacle outlet (210.52(A)(1))
- A wall space is any space 2 ft or wider, measured around corners, unbroken by doorways, fireplaces, stationary appliances and fixed cabinets without countertops (210.52(A)(2)(1))
- A floor receptacle counts only within 18 in of the wall; countertop receptacles do not count toward these (210.52(A)(3), 210.52(A)(4))
- Its wall, floor and countertop receptacles and the refrigerator's are on the 20 A small-appliance circuits, which have no other outlets; in addition to the required receptacles, one for a specific appliance (a refrigerator, say) may have its own circuit of 15 A or more, and a clock receptacle or one powering a gas range's, oven's or cooktop's supplemental equipment and lighting may be on a small-appliance circuit (210.52(B)(1), 210.52(B)(2), 210.52(B)(1) Exception No. 2, 210.52(B)(2) Exception No. 1, 210.52(B)(2) Exception No. 2)
- Where it has a countertop or work surface 12 in or wider, no point along the wall line more than 24 in from a receptacle outlet (210.52(C)(1))
- Where it has an island or peninsula countertop without a receptacle, provisions there for one later (210.52(C)(2))
- Where it has a countertop or work surface 12 in or wider, its receptacles on or not more than 20 in above it, or in it or a work surface as listed assemblies (210.52(C)(3))
Living room
- GFCI: not for the room itself; the dwelling's sink, bathtub and damp location rules below still apply (210.8(A))
- Every 120 V, 10, 15 and 20 A branch circuit supplying outlets or devices here: AFCI, except the circuits 210.12(B)'s exceptions name (listed for the whole dwelling) (210.12(B)(4))
- No point along the floor line of any wall space more than 6 ft from a receptacle outlet (210.52(A)(1))
- A wall space is any space 2 ft or wider, measured around corners, unbroken by doorways, fireplaces, stationary appliances and fixed cabinets without countertops (210.52(A)(2)(1))
- A floor receptacle counts only within 18 in of the wall; countertop receptacles do not count toward these (210.52(A)(3), 210.52(A)(4))
Bedroom 1
- GFCI: not for the room itself; the dwelling's sink, bathtub and damp location rules below still apply (210.8(A))
- Every 120 V, 10, 15 and 20 A branch circuit supplying outlets or devices here: AFCI, except the circuits 210.12(B)'s exceptions name (listed for the whole dwelling) (210.12(B)(8))
- No point along the floor line of any wall space more than 6 ft from a receptacle outlet (210.52(A)(1))
- A wall space is any space 2 ft or wider, measured around corners, unbroken by doorways, fireplaces, stationary appliances and fixed cabinets without countertops (210.52(A)(2)(1))
- A floor receptacle counts only within 18 in of the wall; countertop receptacles do not count toward these (210.52(A)(3), 210.52(A)(4))
Bedroom 2
- GFCI: not for the room itself; the dwelling's sink, bathtub and damp location rules below still apply (210.8(A))
- Every 120 V, 10, 15 and 20 A branch circuit supplying outlets or devices here: AFCI, except the circuits 210.12(B)'s exceptions name (listed for the whole dwelling) (210.12(B)(8))
- No point along the floor line of any wall space more than 6 ft from a receptacle outlet (210.52(A)(1))
- A wall space is any space 2 ft or wider, measured around corners, unbroken by doorways, fireplaces, stationary appliances and fixed cabinets without countertops (210.52(A)(2)(1))
- A floor receptacle counts only within 18 in of the wall; countertop receptacles do not count toward these (210.52(A)(3), 210.52(A)(4))
Bathroom
- Its receptacles: GFCI (210.8(A)(1))
- AFCI: not required for this room by 210.12(B), which does not name it (210.12(B))
- At least one receptacle outlet within 3 ft of the outside edge of each sink, not more than 12 in below its top (210.52(D))
Hallway
- GFCI: not for the room itself; the dwelling's sink, bathtub and damp location rules below still apply (210.8(A))
- Every 120 V, 10, 15 and 20 A branch circuit supplying outlets or devices here: AFCI, except the circuits 210.12(B)'s exceptions name (listed for the whole dwelling) (210.12(B)(12))
- At least one receptacle outlet: 14 ft along the centerline is 10 ft or more (210.52(H))
Closet
- GFCI: not for the room itself; the dwelling's sink, bathtub and damp location rules below still apply (210.8(A))
- Every 120 V, 10, 15 and 20 A branch circuit supplying outlets or devices here: AFCI, except the circuits 210.12(B)'s exceptions name (listed for the whole dwelling) (210.12(B)(11))
- None required here by 210.52 (210.52)
Laundry area
- Its receptacles: GFCI (210.8(A)(11))
- The branch circuit or outlet supplying a clothes dryer (150 V or less to ground, 60 A or less): GFCI (210.8(D)(11))
- Every 120 V, 10, 15 and 20 A branch circuit supplying outlets or devices here: AFCI, except the circuits 210.12(B)'s exceptions name (listed for the whole dwelling) (210.12(B)(13))
- At least one receptacle outlet where the laundry equipment goes (210.52(F))
Garage
- Its receptacles: GFCI (210.8(A)(2))
- Every outlet in it, not only receptacles (single-phase, 150 V or less to ground, 50 A or less), except lighting outlets: GFCI (210.8(F)(1), 210.8(F) Exception No. 1)
- The branch circuit or outlet supplying a sump pump, where one is installed (150 V or less to ground, 60 A or less): GFCI (210.8(D)(6))
- AFCI: not required for this room by 210.12(B), which does not name it (210.12(B))
- At least one receptacle outlet in each vehicle bay (2 bays: at least 2), in addition to any receptacle required for specific equipment, not more than 5½ ft above the floor; one supplying only a permanently installed premises security system does not count (210.52(G)(1))
Whole dwelling
- 210.8(A) reaches 125 V through 250 V receptacles on single-phase circuits of 150 V or less to ground (210.8(A))
- 210.8(A)'s exceptions: a receptacle that is not readily accessible, on a branch circuit dedicated to snow-melting, deicing, or pipeline and vessel heating equipment, installed as that exception says; a receptacle supplying only a permanently installed premises security system; a listed weight-supporting ceiling receptacle (WSCR) with its compatible fitting, supporting a ceiling luminaire or ceiling-suspended fan, unless a general-purpose convenience receptacle is integral to the luminaire or fan; a factory-installed receptacle that is not readily accessible, mounted inside a bathroom exhaust fan assembly, unless its installation instructions or listing require GFCI (210.8(A) Exception No. 1, 210.8(A) Exception No. 2, 210.8(A) Exception No. 3, 210.8(A) Exception No. 4)
- Outdoor receptacles: GFCI (210.8(A)(3))
- Every outdoor outlet, not only receptacles (single-phase, 150 V or less to ground, 50 A or less), except lighting outlets: GFCI. For an outdoor air conditioner or heat pump, run the outdoor HVAC GFCI check: its exception depends on the edition, the date and your state (210.8(F), 210.8(F) Exception No. 1)
- Anywhere in the dwelling: receptacles within 6 ft of the top inside edge of a sink's bowl, within 6 ft of the outside edge of a bathtub or shower stall, and in indoor damp and wet locations: GFCI (210.8(A)(8), 210.8(A)(10), 210.8(A)(12))
- The receptacle 210.63 requires near heating, air-conditioning and refrigeration equipment: GFCI (210.8(E))
- The branch circuit or outlet supplying an automotive vacuum machine, a drinking water cooler or bottle fill station, a high-pressure spray washing machine, a tire inflation machine, a vending machine, a sump pump, a dishwasher, an electric range, a wall-mounted oven, a counter-mounted cooking unit, a clothes dryer and a microwave oven, wherever in the dwelling one is installed (150 V or less to ground, 60 A or less): GFCI (210.8(D)(1), 210.8(D)(2), 210.8(D)(3), 210.8(D)(4), 210.8(D)(5), 210.8(D)(6), 210.8(D)(7), 210.8(D)(8), 210.8(D)(9), 210.8(D)(10), 210.8(D)(11), 210.8(D)(12))
- Outdoors: at least one receptacle outlet at the front and one at the back, readily accessible from grade and not more than 6½ ft above it (210.52(E)(1))
- Where branch-circuit wiring for a room 210.12(B) names is modified, replaced or extended: AFCI, except an extension of 6 ft or less with no added outlets or devices (210.12(E), 210.12(E) Exception)
- 210.12(B)'s exceptions in force: an individual branch circuit supplying a fire alarm system installed as that exception says, run in metal raceway, metal auxiliary gutter, steel-armored cable, or Type MC or Type AC cable, with metal boxes, conduit bodies and enclosures (210.12(B) Exception No. 1)
Show the math
- GIVENEdition: NEC 2023
- GIVENDwelling: One-family dwelling
- TABLEKitchen, GFCI: Its receptacles: GFCI (210.8(A)(6))NEC 2023 210.8(A)(6)
- TABLEKitchen, GFCI: The branch circuit or outlet supplying a dishwasher, an electric range, a wall-mounted oven, a counter-mounted cooking unit and a microwave oven (150 V or less to ground, 60 A or less): GFCI (210.8(D)(7), 210.8(D)(8), 210.8(D)(9), 210.8(D)(10), 210.8(D)(12))NEC 2023 210.8(D)(7), 210.8(D)(8), 210.8(D)(9), 210.8(D)(10), 210.8(D)(12)
- TABLEKitchen, AFCI: Every 120 V, 10, 15 and 20 A branch circuit supplying outlets or devices here: AFCI, except the circuits 210.12(B)'s exceptions name (listed for the whole dwelling) (210.12(B)(1))NEC 2023 210.12(B)(1)
- TABLEKitchen, Receptacles: No point along the floor line of any wall space more than 6 ft from a receptacle outlet (210.52(A)(1))NEC 2023 210.52(A)(1)
- TABLEKitchen, Receptacles: A wall space is any space 2 ft or wider, measured around corners, unbroken by doorways, fireplaces, stationary appliances and fixed cabinets without countertops (210.52(A)(2)(1))NEC 2023 210.52(A)(2)(1)
- TABLEKitchen, Receptacles: A floor receptacle counts only within 18 in of the wall; countertop receptacles do not count toward these (210.52(A)(3), 210.52(A)(4))NEC 2023 210.52(A)(3), 210.52(A)(4)
- TABLEKitchen, Receptacles: Its wall, floor and countertop receptacles and the refrigerator's are on the 20 A small-appliance circuits, which have no other outlets; in addition to the required receptacles, one for a specific appliance (a refrigerator, say) may have its own circuit of 15 A or more, and a clock receptacle or one powering a gas range's, oven's or cooktop's supplemental equipment and lighting may be on a small-appliance circuit (210.52(B)(1), 210.52(B)(2), 210.52(B)(1) Exception No. 2, 210.52(B)(2) Exception No. 1, 210.52(B)(2) Exception No. 2)NEC 2023 210.52(B)(1), 210.52(B)(2), 210.52(B)(1) Exception No. 2, 210.52(B)(2) Exception No. 1, 210.52(B)(2) Exception No. 2
- TABLEKitchen, Receptacles: Countertop receptacles on at least two small-appliance circuits, and no small-appliance circuit serves another kitchen (210.52(B)(3))NEC 2023 210.52(B)(3)
- TABLEKitchen, Receptacles: Countertops and work surfaces 12 in or wider: no point along the wall line more than 24 in from a receptacle outlet (210.52(C)(1))NEC 2023 210.52(C)(1)
- TABLEKitchen, Receptacles: Island or peninsula without a receptacle: provisions there for one later (210.52(C)(2))NEC 2023 210.52(C)(2)
- TABLEKitchen, Receptacles: Countertop receptacles on or not more than 20 in above it, or in it or a work surface as listed assemblies (210.52(C)(3))NEC 2023 210.52(C)(3)
- TABLEDining room, GFCI: GFCI: not for the room itself; the dwelling's sink, bathtub and damp location rules below still apply (210.8(A))NEC 2023 210.8(A)
- TABLEDining room, AFCI: Every 120 V, 10, 15 and 20 A branch circuit supplying outlets or devices here: AFCI, except the circuits 210.12(B)'s exceptions name (listed for the whole dwelling) (210.12(B)(3))NEC 2023 210.12(B)(3)
- TABLEDining room, Receptacles: No point along the floor line of any wall space more than 6 ft from a receptacle outlet (210.52(A)(1))NEC 2023 210.52(A)(1)
- TABLEDining room, Receptacles: A wall space is any space 2 ft or wider, measured around corners, unbroken by doorways, fireplaces, stationary appliances and fixed cabinets without countertops (210.52(A)(2)(1))NEC 2023 210.52(A)(2)(1)
- TABLEDining room, Receptacles: A floor receptacle counts only within 18 in of the wall; countertop receptacles do not count toward these (210.52(A)(3), 210.52(A)(4))NEC 2023 210.52(A)(3), 210.52(A)(4)
- TABLEDining room, Receptacles: Its wall, floor and countertop receptacles and the refrigerator's are on the 20 A small-appliance circuits, which have no other outlets; in addition to the required receptacles, one for a specific appliance (a refrigerator, say) may have its own circuit of 15 A or more, and a clock receptacle or one powering a gas range's, oven's or cooktop's supplemental equipment and lighting may be on a small-appliance circuit (210.52(B)(1), 210.52(B)(2), 210.52(B)(1) Exception No. 2, 210.52(B)(2) Exception No. 1, 210.52(B)(2) Exception No. 2)NEC 2023 210.52(B)(1), 210.52(B)(2), 210.52(B)(1) Exception No. 2, 210.52(B)(2) Exception No. 1, 210.52(B)(2) Exception No. 2
- TABLEDining room, Receptacles: Where it has a countertop or work surface 12 in or wider, no point along the wall line more than 24 in from a receptacle outlet (210.52(C)(1))NEC 2023 210.52(C)(1)
- TABLEDining room, Receptacles: Where it has an island or peninsula countertop without a receptacle, provisions there for one later (210.52(C)(2))NEC 2023 210.52(C)(2)
- TABLEDining room, Receptacles: Where it has a countertop or work surface 12 in or wider, its receptacles on or not more than 20 in above it, or in it or a work surface as listed assemblies (210.52(C)(3))NEC 2023 210.52(C)(3)
- TABLELiving room, GFCI: GFCI: not for the room itself; the dwelling's sink, bathtub and damp location rules below still apply (210.8(A))NEC 2023 210.8(A)
- TABLELiving room, AFCI: Every 120 V, 10, 15 and 20 A branch circuit supplying outlets or devices here: AFCI, except the circuits 210.12(B)'s exceptions name (listed for the whole dwelling) (210.12(B)(4))NEC 2023 210.12(B)(4)
- TABLELiving room, Receptacles: No point along the floor line of any wall space more than 6 ft from a receptacle outlet (210.52(A)(1))NEC 2023 210.52(A)(1)
- TABLELiving room, Receptacles: A wall space is any space 2 ft or wider, measured around corners, unbroken by doorways, fireplaces, stationary appliances and fixed cabinets without countertops (210.52(A)(2)(1))NEC 2023 210.52(A)(2)(1)
- TABLELiving room, Receptacles: A floor receptacle counts only within 18 in of the wall; countertop receptacles do not count toward these (210.52(A)(3), 210.52(A)(4))NEC 2023 210.52(A)(3), 210.52(A)(4)
- TABLEBedroom 1, GFCI: GFCI: not for the room itself; the dwelling's sink, bathtub and damp location rules below still apply (210.8(A))NEC 2023 210.8(A)
- TABLEBedroom 1, AFCI: Every 120 V, 10, 15 and 20 A branch circuit supplying outlets or devices here: AFCI, except the circuits 210.12(B)'s exceptions name (listed for the whole dwelling) (210.12(B)(8))NEC 2023 210.12(B)(8)
- TABLEBedroom 1, Receptacles: No point along the floor line of any wall space more than 6 ft from a receptacle outlet (210.52(A)(1))NEC 2023 210.52(A)(1)
- TABLEBedroom 1, Receptacles: A wall space is any space 2 ft or wider, measured around corners, unbroken by doorways, fireplaces, stationary appliances and fixed cabinets without countertops (210.52(A)(2)(1))NEC 2023 210.52(A)(2)(1)
- TABLEBedroom 1, Receptacles: A floor receptacle counts only within 18 in of the wall; countertop receptacles do not count toward these (210.52(A)(3), 210.52(A)(4))NEC 2023 210.52(A)(3), 210.52(A)(4)
- TABLEBedroom 2, GFCI: GFCI: not for the room itself; the dwelling's sink, bathtub and damp location rules below still apply (210.8(A))NEC 2023 210.8(A)
- TABLEBedroom 2, AFCI: Every 120 V, 10, 15 and 20 A branch circuit supplying outlets or devices here: AFCI, except the circuits 210.12(B)'s exceptions name (listed for the whole dwelling) (210.12(B)(8))NEC 2023 210.12(B)(8)
- TABLEBedroom 2, Receptacles: No point along the floor line of any wall space more than 6 ft from a receptacle outlet (210.52(A)(1))NEC 2023 210.52(A)(1)
- TABLEBedroom 2, Receptacles: A wall space is any space 2 ft or wider, measured around corners, unbroken by doorways, fireplaces, stationary appliances and fixed cabinets without countertops (210.52(A)(2)(1))NEC 2023 210.52(A)(2)(1)
- TABLEBedroom 2, Receptacles: A floor receptacle counts only within 18 in of the wall; countertop receptacles do not count toward these (210.52(A)(3), 210.52(A)(4))NEC 2023 210.52(A)(3), 210.52(A)(4)
- TABLEBathroom, GFCI: Its receptacles: GFCI (210.8(A)(1))NEC 2023 210.8(A)(1)
- TABLEBathroom, AFCI: AFCI: not required for this room by 210.12(B), which does not name it (210.12(B))NEC 2023 210.12(B)
- TABLEBathroom, Receptacles: At least one receptacle outlet within 3 ft of the outside edge of each sink, not more than 12 in below its top (210.52(D))NEC 2023 210.52(D)
- TABLEHallway, GFCI: GFCI: not for the room itself; the dwelling's sink, bathtub and damp location rules below still apply (210.8(A))NEC 2023 210.8(A)
- TABLEHallway, AFCI: Every 120 V, 10, 15 and 20 A branch circuit supplying outlets or devices here: AFCI, except the circuits 210.12(B)'s exceptions name (listed for the whole dwelling) (210.12(B)(12))NEC 2023 210.12(B)(12)
- TABLEHallway, Receptacles: At least one receptacle outlet: 14 ft along the centerline is 10 ft or more (210.52(H))NEC 2023 210.52(H)
- TABLECloset, GFCI: GFCI: not for the room itself; the dwelling's sink, bathtub and damp location rules below still apply (210.8(A))NEC 2023 210.8(A)
- TABLECloset, AFCI: Every 120 V, 10, 15 and 20 A branch circuit supplying outlets or devices here: AFCI, except the circuits 210.12(B)'s exceptions name (listed for the whole dwelling) (210.12(B)(11))NEC 2023 210.12(B)(11)
- TABLECloset, Receptacles: None required here by 210.52 (210.52)NEC 2023 210.52
- TABLELaundry area, GFCI: Its receptacles: GFCI (210.8(A)(11))NEC 2023 210.8(A)(11)
- TABLELaundry area, GFCI: The branch circuit or outlet supplying a clothes dryer (150 V or less to ground, 60 A or less): GFCI (210.8(D)(11))NEC 2023 210.8(D)(11)
- TABLELaundry area, AFCI: Every 120 V, 10, 15 and 20 A branch circuit supplying outlets or devices here: AFCI, except the circuits 210.12(B)'s exceptions name (listed for the whole dwelling) (210.12(B)(13))NEC 2023 210.12(B)(13)
- TABLELaundry area, Receptacles: At least one receptacle outlet where the laundry equipment goes (210.52(F))NEC 2023 210.52(F)
- TABLEGarage, GFCI: Its receptacles: GFCI (210.8(A)(2))NEC 2023 210.8(A)(2)
- TABLEGarage, GFCI: Every outlet in it, not only receptacles (single-phase, 150 V or less to ground, 50 A or less), except lighting outlets: GFCI (210.8(F)(1), 210.8(F) Exception No. 1)NEC 2023 210.8(F)(1), 210.8(F) Exception No. 1
- TABLEGarage, GFCI: The branch circuit or outlet supplying a sump pump, where one is installed (150 V or less to ground, 60 A or less): GFCI (210.8(D)(6))NEC 2023 210.8(D)(6)
- TABLEGarage, AFCI: AFCI: not required for this room by 210.12(B), which does not name it (210.12(B))NEC 2023 210.12(B)
- TABLEGarage, Receptacles: At least one receptacle outlet in each vehicle bay (2 bays: at least 2), in addition to any receptacle required for specific equipment, not more than 5½ ft above the floor; one supplying only a permanently installed premises security system does not count (210.52(G)(1))NEC 2023 210.52(G)(1)
- TABLEWhole dwelling, GFCI: 210.8(A) reaches 125 V through 250 V receptacles on single-phase circuits of 150 V or less to ground (210.8(A))NEC 2023 210.8(A)
- TABLEWhole dwelling, GFCI: 210.8(A)'s exceptions: a receptacle that is not readily accessible, on a branch circuit dedicated to snow-melting, deicing, or pipeline and vessel heating equipment, installed as that exception says; a receptacle supplying only a permanently installed premises security system; a listed weight-supporting ceiling receptacle (WSCR) with its compatible fitting, supporting a ceiling luminaire or ceiling-suspended fan, unless a general-purpose convenience receptacle is integral to the luminaire or fan; a factory-installed receptacle that is not readily accessible, mounted inside a bathroom exhaust fan assembly, unless its installation instructions or listing require GFCI (210.8(A) Exception No. 1, 210.8(A) Exception No. 2, 210.8(A) Exception No. 3, 210.8(A) Exception No. 4)NEC 2023 210.8(A) Exception No. 1, 210.8(A) Exception No. 2, 210.8(A) Exception No. 3, 210.8(A) Exception No. 4
- TABLEWhole dwelling, GFCI: Outdoor receptacles: GFCI (210.8(A)(3))NEC 2023 210.8(A)(3)
- TABLEWhole dwelling, GFCI: Every outdoor outlet, not only receptacles (single-phase, 150 V or less to ground, 50 A or less), except lighting outlets: GFCI. For an outdoor air conditioner or heat pump, run the outdoor HVAC GFCI check: its exception depends on the edition, the date and your state (210.8(F), 210.8(F) Exception No. 1)NEC 2023 210.8(F), 210.8(F) Exception No. 1
- TABLEWhole dwelling, GFCI: Anywhere in the dwelling: receptacles within 6 ft of the top inside edge of a sink's bowl, within 6 ft of the outside edge of a bathtub or shower stall, and in indoor damp and wet locations: GFCI (210.8(A)(8), 210.8(A)(10), 210.8(A)(12))NEC 2023 210.8(A)(8), 210.8(A)(10), 210.8(A)(12)
- TABLEWhole dwelling, GFCI: The receptacle 210.63 requires near heating, air-conditioning and refrigeration equipment: GFCI (210.8(E))NEC 2023 210.8(E)
- TABLEWhole dwelling, GFCI: The branch circuit or outlet supplying an automotive vacuum machine, a drinking water cooler or bottle fill station, a high-pressure spray washing machine, a tire inflation machine, a vending machine, a sump pump, a dishwasher, an electric range, a wall-mounted oven, a counter-mounted cooking unit, a clothes dryer and a microwave oven, wherever in the dwelling one is installed (150 V or less to ground, 60 A or less): GFCI (210.8(D)(1), 210.8(D)(2), 210.8(D)(3), 210.8(D)(4), 210.8(D)(5), 210.8(D)(6), 210.8(D)(7), 210.8(D)(8), 210.8(D)(9), 210.8(D)(10), 210.8(D)(11), 210.8(D)(12))NEC 2023 210.8(D)(1), 210.8(D)(2), 210.8(D)(3), 210.8(D)(4), 210.8(D)(5), 210.8(D)(6), 210.8(D)(7), 210.8(D)(8), 210.8(D)(9), 210.8(D)(10), 210.8(D)(11), 210.8(D)(12)
- TABLEWhole dwelling, Receptacles: Outdoors: at least one receptacle outlet at the front and one at the back, readily accessible from grade and not more than 6½ ft above it (210.52(E)(1))NEC 2023 210.52(E)(1)
- TABLEWhole dwelling, AFCI: Where branch-circuit wiring for a room 210.12(B) names is modified, replaced or extended: AFCI, except an extension of 6 ft or less with no added outlets or devices (210.12(E), 210.12(E) Exception)NEC 2023 210.12(E), 210.12(E) Exception
- TABLEWhole dwelling, AFCI: 210.12(B)'s exceptions in force: an individual branch circuit supplying a fire alarm system installed as that exception says, run in metal raceway, metal auxiliary gutter, steel-armored cable, or Type MC or Type AC cable, with metal boxes, conduit bodies and enclosures (210.12(B) Exception No. 1)NEC 2023 210.12(B) Exception No. 1
- TABLEWhole dwelling, Circuit: Kitchen small-appliance 1: a 20 A branch circuit. Serves the kitchen's countertop, wall and floor receptacles and the refrigerator's, and may also serve the pantry, breakfast room and dining room; in addition to the required receptacles, a specific appliance's receptacle (a refrigerator's, say) may have its own circuit of 15 A or more (210.11(C)(1), 210.52(B)(1), 210.52(B)(1) Exception No. 2)NEC 2023 210.11(C)(1), 210.52(B)(1), 210.52(B)(1) Exception No. 2
- TABLEWhole dwelling, Circuit: Kitchen small-appliance 2: a 20 A branch circuit. Serves the kitchen's countertop, wall and floor receptacles and the refrigerator's, and may also serve the pantry, breakfast room and dining room; in addition to the required receptacles, a specific appliance's receptacle (a refrigerator's, say) may have its own circuit of 15 A or more (210.11(C)(1), 210.52(B)(1), 210.52(B)(1) Exception No. 2)NEC 2023 210.11(C)(1), 210.52(B)(1), 210.52(B)(1) Exception No. 2
- TABLEWhole dwelling, Circuit: Laundry: a 20 A branch circuit. The laundry receptacle outlets only (210.11(C)(2))NEC 2023 210.11(C)(2)
- TABLEWhole dwelling, Circuit: Bathroom receptacles: a 20 A branch circuit. Bathroom receptacles only; where it supplies a single bathroom, outlets for other equipment in that bathroom may be on it within 210.23(B)(1) and (B)(2) (210.11(C)(3), 210.11(C)(3) Exception)NEC 2023 210.11(C)(3), 210.11(C)(3) Exception
- TABLEWhole dwelling, Circuit: Garage receptacles: a 20 A branch circuit. The garage receptacles and no other outlets, except that it may also supply outdoor receptacles, and where it supplies a single vehicle bay garage, outlets for other equipment within that garage may be on it within 210.23(B)(1) and (B)(2); added circuits of 15 A or more may serve its other receptacles (210.11(C)(4), 210.11(C)(4) Exception No. 1, 210.11(C)(4) Exception No. 2)NEC 2023 210.11(C)(4), 210.11(C)(4) Exception No. 1, 210.11(C)(4) Exception No. 2
- RESULTRequired circuits: Kitchen small-appliance 1, Kitchen small-appliance 2, Laundry, Bathroom receptacles, Garage receptaclesNEC 2023 210.11(C)
Where this number comes fromIntry Verified
- Calculated from
- NEC 2023 210.8, 210.11(C), 210.12 and 210.52 (NFPA 70, 2023 edition), without any state's amendment. Each room's GFCI, AFCI and receptacle lines and the dwelling's required circuits, from the NEC 2020, 2023 or 2026 rows of 210.8, 210.11(C), 210.12 and 210.52 for the edition you choose; a state's amendments are named, never applied. See the full receipt ↓
- Run with
- Edition2023
- Statenot chosen
- DwellingOne-family dwelling
- Rooms10
- Checked
- Every figure an Intry calculator computes comes from a locked source module, not hand-typed. 35,006 automated checks, one suite for the whole site rather than a per-tool count, re-derive the numbers before each deploy from the tables this site holds, read from the cited NEC section. This is our own deterministic gate, not a third-party audit.
- Final say
- Your AHJ and local amendments have final say. Confirm before rough-in.
Intry Verified · Build AF0D4B6 · 2026-11-11
Copy for job notes gives the checklist with a box beside each line. Save it to a job and the panel schedule can add its required circuits as rows; the job's PDF packet prints the checklist.
Cited against NFPA 70, the 2020, 2023 and 2026 editions, 210.8, 210.11(C), 210.12 and 210.52 (and 422.5 in 2020). A state, city or county can amend these rules; your inspector has the final word.
How to use the rough-in checklist
- Pick the code. Choose your state to set the NEC edition its record names, or choose 2020, 2023 or 2026 yourself, and pick the kind of dwelling.
- Enter the rooms. Add each room: a hallway with its length along the centerline, a foyer with its floor area, a garage with its bays, and any room in a basement marked In a basement.
- Read each room. Each room lists its GFCI, AFCI and receptacle lines, each with its section; the whole dwelling adds the required circuits and the outdoor rules.
- Take it to the job. Copy for job notes gives the checklist with a box beside each line; Save files it under a job, and the panel schedule can add its required circuits.
A distance, not a count
210.52(A) sets how far any point on a wall may be from a receptacle outlet, not how many a room gets. Doorways, fireplaces and fixed cabinets break a wall into separate wall spaces, so the checklist gives the distances and leaves the count to the layout. The counts it does give are the code's own: one per garage vehicle bay, one in a hallway of 10 ft or more, and one in each wall space 3 ft or wider in a foyer over 60 sq ft.
Worked examples
Example 1: a one-family house, NEC 2023
10 rooms, 5 required circuits (NEC 2023).
Show the math
- GIVENEdition: NEC 2023
- GIVENDwelling: One-family dwelling
- TABLEKitchen, GFCI: Its receptacles: GFCI (210.8(A)(6))NEC 2023 210.8(A)(6)
- TABLEKitchen, GFCI: The branch circuit or outlet supplying a dishwasher, an electric range, a wall-mounted oven, a counter-mounted cooking unit and a microwave oven (150 V or less to ground, 60 A or less): GFCI (210.8(D)(7), 210.8(D)(8), 210.8(D)(9), 210.8(D)(10), 210.8(D)(12))NEC 2023 210.8(D)(7), 210.8(D)(8), 210.8(D)(9), 210.8(D)(10), 210.8(D)(12)
- TABLEKitchen, AFCI: Every 120 V, 10, 15 and 20 A branch circuit supplying outlets or devices here: AFCI, except the circuits 210.12(B)'s exceptions name (listed for the whole dwelling) (210.12(B)(1))NEC 2023 210.12(B)(1)
- TABLEKitchen, Receptacles: No point along the floor line of any wall space more than 6 ft from a receptacle outlet (210.52(A)(1))NEC 2023 210.52(A)(1)
- TABLEKitchen, Receptacles: A wall space is any space 2 ft or wider, measured around corners, unbroken by doorways, fireplaces, stationary appliances and fixed cabinets without countertops (210.52(A)(2)(1))NEC 2023 210.52(A)(2)(1)
- TABLEKitchen, Receptacles: A floor receptacle counts only within 18 in of the wall; countertop receptacles do not count toward these (210.52(A)(3), 210.52(A)(4))NEC 2023 210.52(A)(3), 210.52(A)(4)
- TABLEKitchen, Receptacles: Its wall, floor and countertop receptacles and the refrigerator's are on the 20 A small-appliance circuits, which have no other outlets; in addition to the required receptacles, one for a specific appliance (a refrigerator, say) may have its own circuit of 15 A or more, and a clock receptacle or one powering a gas range's, oven's or cooktop's supplemental equipment and lighting may be on a small-appliance circuit (210.52(B)(1), 210.52(B)(2), 210.52(B)(1) Exception No. 2, 210.52(B)(2) Exception No. 1, 210.52(B)(2) Exception No. 2)NEC 2023 210.52(B)(1), 210.52(B)(2), 210.52(B)(1) Exception No. 2, 210.52(B)(2) Exception No. 1, 210.52(B)(2) Exception No. 2
- TABLEKitchen, Receptacles: Countertop receptacles on at least two small-appliance circuits, and no small-appliance circuit serves another kitchen (210.52(B)(3))NEC 2023 210.52(B)(3)
- TABLEKitchen, Receptacles: Countertops and work surfaces 12 in or wider: no point along the wall line more than 24 in from a receptacle outlet (210.52(C)(1))NEC 2023 210.52(C)(1)
- TABLEKitchen, Receptacles: Island or peninsula without a receptacle: provisions there for one later (210.52(C)(2))NEC 2023 210.52(C)(2)
- TABLEKitchen, Receptacles: Countertop receptacles on or not more than 20 in above it, or in it or a work surface as listed assemblies (210.52(C)(3))NEC 2023 210.52(C)(3)
- TABLEDining room, GFCI: GFCI: not for the room itself; the dwelling's sink, bathtub and damp location rules below still apply (210.8(A))NEC 2023 210.8(A)
- TABLEDining room, AFCI: Every 120 V, 10, 15 and 20 A branch circuit supplying outlets or devices here: AFCI, except the circuits 210.12(B)'s exceptions name (listed for the whole dwelling) (210.12(B)(3))NEC 2023 210.12(B)(3)
- TABLEDining room, Receptacles: No point along the floor line of any wall space more than 6 ft from a receptacle outlet (210.52(A)(1))NEC 2023 210.52(A)(1)
- TABLEDining room, Receptacles: A wall space is any space 2 ft or wider, measured around corners, unbroken by doorways, fireplaces, stationary appliances and fixed cabinets without countertops (210.52(A)(2)(1))NEC 2023 210.52(A)(2)(1)
- TABLEDining room, Receptacles: A floor receptacle counts only within 18 in of the wall; countertop receptacles do not count toward these (210.52(A)(3), 210.52(A)(4))NEC 2023 210.52(A)(3), 210.52(A)(4)
- TABLEDining room, Receptacles: Its wall, floor and countertop receptacles and the refrigerator's are on the 20 A small-appliance circuits, which have no other outlets; in addition to the required receptacles, one for a specific appliance (a refrigerator, say) may have its own circuit of 15 A or more, and a clock receptacle or one powering a gas range's, oven's or cooktop's supplemental equipment and lighting may be on a small-appliance circuit (210.52(B)(1), 210.52(B)(2), 210.52(B)(1) Exception No. 2, 210.52(B)(2) Exception No. 1, 210.52(B)(2) Exception No. 2)NEC 2023 210.52(B)(1), 210.52(B)(2), 210.52(B)(1) Exception No. 2, 210.52(B)(2) Exception No. 1, 210.52(B)(2) Exception No. 2
- TABLEDining room, Receptacles: Where it has a countertop or work surface 12 in or wider, no point along the wall line more than 24 in from a receptacle outlet (210.52(C)(1))NEC 2023 210.52(C)(1)
- TABLEDining room, Receptacles: Where it has an island or peninsula countertop without a receptacle, provisions there for one later (210.52(C)(2))NEC 2023 210.52(C)(2)
- TABLEDining room, Receptacles: Where it has a countertop or work surface 12 in or wider, its receptacles on or not more than 20 in above it, or in it or a work surface as listed assemblies (210.52(C)(3))NEC 2023 210.52(C)(3)
- TABLELiving room, GFCI: GFCI: not for the room itself; the dwelling's sink, bathtub and damp location rules below still apply (210.8(A))NEC 2023 210.8(A)
- TABLELiving room, AFCI: Every 120 V, 10, 15 and 20 A branch circuit supplying outlets or devices here: AFCI, except the circuits 210.12(B)'s exceptions name (listed for the whole dwelling) (210.12(B)(4))NEC 2023 210.12(B)(4)
- TABLELiving room, Receptacles: No point along the floor line of any wall space more than 6 ft from a receptacle outlet (210.52(A)(1))NEC 2023 210.52(A)(1)
- TABLELiving room, Receptacles: A wall space is any space 2 ft or wider, measured around corners, unbroken by doorways, fireplaces, stationary appliances and fixed cabinets without countertops (210.52(A)(2)(1))NEC 2023 210.52(A)(2)(1)
- TABLELiving room, Receptacles: A floor receptacle counts only within 18 in of the wall; countertop receptacles do not count toward these (210.52(A)(3), 210.52(A)(4))NEC 2023 210.52(A)(3), 210.52(A)(4)
- TABLEBedroom 1, GFCI: GFCI: not for the room itself; the dwelling's sink, bathtub and damp location rules below still apply (210.8(A))NEC 2023 210.8(A)
- TABLEBedroom 1, AFCI: Every 120 V, 10, 15 and 20 A branch circuit supplying outlets or devices here: AFCI, except the circuits 210.12(B)'s exceptions name (listed for the whole dwelling) (210.12(B)(8))NEC 2023 210.12(B)(8)
- TABLEBedroom 1, Receptacles: No point along the floor line of any wall space more than 6 ft from a receptacle outlet (210.52(A)(1))NEC 2023 210.52(A)(1)
- TABLEBedroom 1, Receptacles: A wall space is any space 2 ft or wider, measured around corners, unbroken by doorways, fireplaces, stationary appliances and fixed cabinets without countertops (210.52(A)(2)(1))NEC 2023 210.52(A)(2)(1)
- TABLEBedroom 1, Receptacles: A floor receptacle counts only within 18 in of the wall; countertop receptacles do not count toward these (210.52(A)(3), 210.52(A)(4))NEC 2023 210.52(A)(3), 210.52(A)(4)
- TABLEBedroom 2, GFCI: GFCI: not for the room itself; the dwelling's sink, bathtub and damp location rules below still apply (210.8(A))NEC 2023 210.8(A)
- TABLEBedroom 2, AFCI: Every 120 V, 10, 15 and 20 A branch circuit supplying outlets or devices here: AFCI, except the circuits 210.12(B)'s exceptions name (listed for the whole dwelling) (210.12(B)(8))NEC 2023 210.12(B)(8)
- TABLEBedroom 2, Receptacles: No point along the floor line of any wall space more than 6 ft from a receptacle outlet (210.52(A)(1))NEC 2023 210.52(A)(1)
- TABLEBedroom 2, Receptacles: A wall space is any space 2 ft or wider, measured around corners, unbroken by doorways, fireplaces, stationary appliances and fixed cabinets without countertops (210.52(A)(2)(1))NEC 2023 210.52(A)(2)(1)
- TABLEBedroom 2, Receptacles: A floor receptacle counts only within 18 in of the wall; countertop receptacles do not count toward these (210.52(A)(3), 210.52(A)(4))NEC 2023 210.52(A)(3), 210.52(A)(4)
- TABLEBathroom, GFCI: Its receptacles: GFCI (210.8(A)(1))NEC 2023 210.8(A)(1)
- TABLEBathroom, AFCI: AFCI: not required for this room by 210.12(B), which does not name it (210.12(B))NEC 2023 210.12(B)
- TABLEBathroom, Receptacles: At least one receptacle outlet within 3 ft of the outside edge of each sink, not more than 12 in below its top (210.52(D))NEC 2023 210.52(D)
- TABLEHallway, GFCI: GFCI: not for the room itself; the dwelling's sink, bathtub and damp location rules below still apply (210.8(A))NEC 2023 210.8(A)
- TABLEHallway, AFCI: Every 120 V, 10, 15 and 20 A branch circuit supplying outlets or devices here: AFCI, except the circuits 210.12(B)'s exceptions name (listed for the whole dwelling) (210.12(B)(12))NEC 2023 210.12(B)(12)
- TABLEHallway, Receptacles: At least one receptacle outlet: 14 ft along the centerline is 10 ft or more (210.52(H))NEC 2023 210.52(H)
- TABLECloset, GFCI: GFCI: not for the room itself; the dwelling's sink, bathtub and damp location rules below still apply (210.8(A))NEC 2023 210.8(A)
- TABLECloset, AFCI: Every 120 V, 10, 15 and 20 A branch circuit supplying outlets or devices here: AFCI, except the circuits 210.12(B)'s exceptions name (listed for the whole dwelling) (210.12(B)(11))NEC 2023 210.12(B)(11)
- TABLECloset, Receptacles: None required here by 210.52 (210.52)NEC 2023 210.52
- TABLELaundry area, GFCI: Its receptacles: GFCI (210.8(A)(11))NEC 2023 210.8(A)(11)
- TABLELaundry area, GFCI: The branch circuit or outlet supplying a clothes dryer (150 V or less to ground, 60 A or less): GFCI (210.8(D)(11))NEC 2023 210.8(D)(11)
- TABLELaundry area, AFCI: Every 120 V, 10, 15 and 20 A branch circuit supplying outlets or devices here: AFCI, except the circuits 210.12(B)'s exceptions name (listed for the whole dwelling) (210.12(B)(13))NEC 2023 210.12(B)(13)
- TABLELaundry area, Receptacles: At least one receptacle outlet where the laundry equipment goes (210.52(F))NEC 2023 210.52(F)
- TABLEGarage, GFCI: Its receptacles: GFCI (210.8(A)(2))NEC 2023 210.8(A)(2)
- TABLEGarage, GFCI: Every outlet in it, not only receptacles (single-phase, 150 V or less to ground, 50 A or less), except lighting outlets: GFCI (210.8(F)(1), 210.8(F) Exception No. 1)NEC 2023 210.8(F)(1), 210.8(F) Exception No. 1
- TABLEGarage, GFCI: The branch circuit or outlet supplying a sump pump, where one is installed (150 V or less to ground, 60 A or less): GFCI (210.8(D)(6))NEC 2023 210.8(D)(6)
- TABLEGarage, AFCI: AFCI: not required for this room by 210.12(B), which does not name it (210.12(B))NEC 2023 210.12(B)
- TABLEGarage, Receptacles: At least one receptacle outlet in each vehicle bay (2 bays: at least 2), in addition to any receptacle required for specific equipment, not more than 5½ ft above the floor; one supplying only a permanently installed premises security system does not count (210.52(G)(1))NEC 2023 210.52(G)(1)
- TABLEWhole dwelling, GFCI: 210.8(A) reaches 125 V through 250 V receptacles on single-phase circuits of 150 V or less to ground (210.8(A))NEC 2023 210.8(A)
- TABLEWhole dwelling, GFCI: 210.8(A)'s exceptions: a receptacle that is not readily accessible, on a branch circuit dedicated to snow-melting, deicing, or pipeline and vessel heating equipment, installed as that exception says; a receptacle supplying only a permanently installed premises security system; a listed weight-supporting ceiling receptacle (WSCR) with its compatible fitting, supporting a ceiling luminaire or ceiling-suspended fan, unless a general-purpose convenience receptacle is integral to the luminaire or fan; a factory-installed receptacle that is not readily accessible, mounted inside a bathroom exhaust fan assembly, unless its installation instructions or listing require GFCI (210.8(A) Exception No. 1, 210.8(A) Exception No. 2, 210.8(A) Exception No. 3, 210.8(A) Exception No. 4)NEC 2023 210.8(A) Exception No. 1, 210.8(A) Exception No. 2, 210.8(A) Exception No. 3, 210.8(A) Exception No. 4
- TABLEWhole dwelling, GFCI: Outdoor receptacles: GFCI (210.8(A)(3))NEC 2023 210.8(A)(3)
- TABLEWhole dwelling, GFCI: Every outdoor outlet, not only receptacles (single-phase, 150 V or less to ground, 50 A or less), except lighting outlets: GFCI. For an outdoor air conditioner or heat pump, run the outdoor HVAC GFCI check: its exception depends on the edition, the date and your state (210.8(F), 210.8(F) Exception No. 1)NEC 2023 210.8(F), 210.8(F) Exception No. 1
- TABLEWhole dwelling, GFCI: Anywhere in the dwelling: receptacles within 6 ft of the top inside edge of a sink's bowl, within 6 ft of the outside edge of a bathtub or shower stall, and in indoor damp and wet locations: GFCI (210.8(A)(8), 210.8(A)(10), 210.8(A)(12))NEC 2023 210.8(A)(8), 210.8(A)(10), 210.8(A)(12)
- TABLEWhole dwelling, GFCI: The receptacle 210.63 requires near heating, air-conditioning and refrigeration equipment: GFCI (210.8(E))NEC 2023 210.8(E)
- TABLEWhole dwelling, GFCI: The branch circuit or outlet supplying an automotive vacuum machine, a drinking water cooler or bottle fill station, a high-pressure spray washing machine, a tire inflation machine, a vending machine, a sump pump, a dishwasher, an electric range, a wall-mounted oven, a counter-mounted cooking unit, a clothes dryer and a microwave oven, wherever in the dwelling one is installed (150 V or less to ground, 60 A or less): GFCI (210.8(D)(1), 210.8(D)(2), 210.8(D)(3), 210.8(D)(4), 210.8(D)(5), 210.8(D)(6), 210.8(D)(7), 210.8(D)(8), 210.8(D)(9), 210.8(D)(10), 210.8(D)(11), 210.8(D)(12))NEC 2023 210.8(D)(1), 210.8(D)(2), 210.8(D)(3), 210.8(D)(4), 210.8(D)(5), 210.8(D)(6), 210.8(D)(7), 210.8(D)(8), 210.8(D)(9), 210.8(D)(10), 210.8(D)(11), 210.8(D)(12)
- TABLEWhole dwelling, Receptacles: Outdoors: at least one receptacle outlet at the front and one at the back, readily accessible from grade and not more than 6½ ft above it (210.52(E)(1))NEC 2023 210.52(E)(1)
- TABLEWhole dwelling, AFCI: Where branch-circuit wiring for a room 210.12(B) names is modified, replaced or extended: AFCI, except an extension of 6 ft or less with no added outlets or devices (210.12(E), 210.12(E) Exception)NEC 2023 210.12(E), 210.12(E) Exception
- TABLEWhole dwelling, AFCI: 210.12(B)'s exceptions in force: an individual branch circuit supplying a fire alarm system installed as that exception says, run in metal raceway, metal auxiliary gutter, steel-armored cable, or Type MC or Type AC cable, with metal boxes, conduit bodies and enclosures (210.12(B) Exception No. 1)NEC 2023 210.12(B) Exception No. 1
- TABLEWhole dwelling, Circuit: Kitchen small-appliance 1: a 20 A branch circuit. Serves the kitchen's countertop, wall and floor receptacles and the refrigerator's, and may also serve the pantry, breakfast room and dining room; in addition to the required receptacles, a specific appliance's receptacle (a refrigerator's, say) may have its own circuit of 15 A or more (210.11(C)(1), 210.52(B)(1), 210.52(B)(1) Exception No. 2)NEC 2023 210.11(C)(1), 210.52(B)(1), 210.52(B)(1) Exception No. 2
- TABLEWhole dwelling, Circuit: Kitchen small-appliance 2: a 20 A branch circuit. Serves the kitchen's countertop, wall and floor receptacles and the refrigerator's, and may also serve the pantry, breakfast room and dining room; in addition to the required receptacles, a specific appliance's receptacle (a refrigerator's, say) may have its own circuit of 15 A or more (210.11(C)(1), 210.52(B)(1), 210.52(B)(1) Exception No. 2)NEC 2023 210.11(C)(1), 210.52(B)(1), 210.52(B)(1) Exception No. 2
- TABLEWhole dwelling, Circuit: Laundry: a 20 A branch circuit. The laundry receptacle outlets only (210.11(C)(2))NEC 2023 210.11(C)(2)
- TABLEWhole dwelling, Circuit: Bathroom receptacles: a 20 A branch circuit. Bathroom receptacles only; where it supplies a single bathroom, outlets for other equipment in that bathroom may be on it within 210.23(B)(1) and (B)(2) (210.11(C)(3), 210.11(C)(3) Exception)NEC 2023 210.11(C)(3), 210.11(C)(3) Exception
- TABLEWhole dwelling, Circuit: Garage receptacles: a 20 A branch circuit. The garage receptacles and no other outlets, except that it may also supply outdoor receptacles, and where it supplies a single vehicle bay garage, outlets for other equipment within that garage may be on it within 210.23(B)(1) and (B)(2); added circuits of 15 A or more may serve its other receptacles (210.11(C)(4), 210.11(C)(4) Exception No. 1, 210.11(C)(4) Exception No. 2)NEC 2023 210.11(C)(4), 210.11(C)(4) Exception No. 1, 210.11(C)(4) Exception No. 2
- RESULTRequired circuits: Kitchen small-appliance 1, Kitchen small-appliance 2, Laundry, Bathroom receptacles, Garage receptaclesNEC 2023 210.11(C)
Example 2: the same house, NEC 2020
10 rooms, 5 required circuits (NEC 2020). Its kitchen GFCI line reaches only the receptacles that serve the countertop.
Show the math
- GIVENEdition: NEC 2020
- GIVENDwelling: One-family dwelling
- TABLEKitchen, GFCI: Receptacles serving the countertop surfaces: GFCI (210.8(A)(6))NEC 2020 210.8(A)(6)
- TABLEKitchen, GFCI: Any other receptacle within 6 ft of the top inside edge of the sink's bowl: GFCI (210.8(A)(7))NEC 2020 210.8(A)(7)
- TABLEKitchen, GFCI: The outlet supplying a dishwasher (150 V or less to ground, 60 A or less): GFCI at the breaker or a device or outlet in its circuit, unless the plug, the cord within 12 in of the plug or the appliance itself provides it (210.8(D), 422.5(A)(7), 422.5(B))NEC 2020 210.8(D), 422.5(A)(7), 422.5(B)
- TABLEKitchen, AFCI: Every 120 V, 15 and 20 A branch circuit supplying outlets or devices here: AFCI, except the circuits 210.12(A)'s exceptions name (listed for the whole dwelling) (210.12(A))NEC 2020 210.12(A)
- TABLEKitchen, Receptacles: No point along the floor line of any wall space more than 6 ft from a receptacle outlet (210.52(A)(1))NEC 2020 210.52(A)(1)
- TABLEKitchen, Receptacles: A wall space is any space 2 ft or wider, measured around corners, unbroken by doorways, fireplaces and fixed cabinets without countertops (210.52(A)(2)(1))NEC 2020 210.52(A)(2)(1)
- TABLEKitchen, Receptacles: A floor receptacle counts only within 18 in of the wall; countertop receptacles do not count toward these (210.52(A)(3), 210.52(A)(4))NEC 2020 210.52(A)(3), 210.52(A)(4)
- TABLEKitchen, Receptacles: Its wall, floor and countertop receptacles and the refrigerator's are on the 20 A small-appliance circuits, which have no other outlets; in addition to the required receptacles, one for a specific appliance (a refrigerator, say) may have its own circuit of 15 A or more, and a clock receptacle or one powering a gas range's, oven's or cooktop's supplemental equipment and lighting may be on a small-appliance circuit (210.52(B)(1), 210.52(B)(2), 210.52(B)(1) Exception No. 2, 210.52(B)(2) Exception No. 1, 210.52(B)(2) Exception No. 2)NEC 2020 210.52(B)(1), 210.52(B)(2), 210.52(B)(1) Exception No. 2, 210.52(B)(2) Exception No. 1, 210.52(B)(2) Exception No. 2
- TABLEKitchen, Receptacles: Countertop receptacles on at least two small-appliance circuits, and no small-appliance circuit serves another kitchen (210.52(B)(3))NEC 2020 210.52(B)(3)
- TABLEKitchen, Receptacles: Countertops and work surfaces 12 in or wider: no point along the wall line more than 24 in from a receptacle outlet (210.52(C)(1))NEC 2020 210.52(C)(1)
- TABLEKitchen, Receptacles: Island and peninsula: one receptacle outlet for the first 9 sq ft or fraction, one more for every additional 18 sq ft or fraction, and one within 2 ft of a peninsula's outer end (210.52(C)(2))NEC 2020 210.52(C)(2)
- TABLEKitchen, Receptacles: A peninsula is measured from the connected perpendicular wall (210.52(C)(2))NEC 2020 210.52(C)(2)
- TABLEKitchen, Receptacles: Countertop receptacles on or not more than 20 in above it, in it as listed assemblies, or not more than 12 in below it (not where it overhangs its base by more than 6 in) (210.52(C)(3))NEC 2020 210.52(C)(3)
- TABLEDining room, GFCI: GFCI: not for the room itself; the dwelling's sink, bathtub and damp location rules below still apply (210.8(A))NEC 2020 210.8(A)
- TABLEDining room, AFCI: Every 120 V, 15 and 20 A branch circuit supplying outlets or devices here: AFCI, except the circuits 210.12(A)'s exceptions name (listed for the whole dwelling) (210.12(A))NEC 2020 210.12(A)
- TABLEDining room, Receptacles: No point along the floor line of any wall space more than 6 ft from a receptacle outlet (210.52(A)(1))NEC 2020 210.52(A)(1)
- TABLEDining room, Receptacles: A wall space is any space 2 ft or wider, measured around corners, unbroken by doorways, fireplaces and fixed cabinets without countertops (210.52(A)(2)(1))NEC 2020 210.52(A)(2)(1)
- TABLEDining room, Receptacles: A floor receptacle counts only within 18 in of the wall; countertop receptacles do not count toward these (210.52(A)(3), 210.52(A)(4))NEC 2020 210.52(A)(3), 210.52(A)(4)
- TABLEDining room, Receptacles: Its wall, floor and countertop receptacles and the refrigerator's are on the 20 A small-appliance circuits, which have no other outlets; in addition to the required receptacles, one for a specific appliance (a refrigerator, say) may have its own circuit of 15 A or more, and a clock receptacle or one powering a gas range's, oven's or cooktop's supplemental equipment and lighting may be on a small-appliance circuit (210.52(B)(1), 210.52(B)(2), 210.52(B)(1) Exception No. 2, 210.52(B)(2) Exception No. 1, 210.52(B)(2) Exception No. 2)NEC 2020 210.52(B)(1), 210.52(B)(2), 210.52(B)(1) Exception No. 2, 210.52(B)(2) Exception No. 1, 210.52(B)(2) Exception No. 2
- TABLEDining room, Receptacles: Where it has a countertop or work surface 12 in or wider, no point along the wall line more than 24 in from a receptacle outlet (210.52(C)(1))NEC 2020 210.52(C)(1)
- TABLEDining room, Receptacles: Where it has an island or peninsula countertop, one receptacle outlet for the first 9 sq ft or fraction, one more for every additional 18 sq ft or fraction, and one within 2 ft of a peninsula's outer end (210.52(C)(2))NEC 2020 210.52(C)(2)
- TABLEDining room, Receptacles: Where it has a peninsula, measure it from the connected perpendicular wall (210.52(C)(2))NEC 2020 210.52(C)(2)
- TABLEDining room, Receptacles: Where it has a countertop or work surface 12 in or wider, its receptacles on or not more than 20 in above it, in it as listed assemblies, or not more than 12 in below it (not where it overhangs its base by more than 6 in) (210.52(C)(3))NEC 2020 210.52(C)(3)
- TABLELiving room, GFCI: GFCI: not for the room itself; the dwelling's sink, bathtub and damp location rules below still apply (210.8(A))NEC 2020 210.8(A)
- TABLELiving room, AFCI: Every 120 V, 15 and 20 A branch circuit supplying outlets or devices here: AFCI, except the circuits 210.12(A)'s exceptions name (listed for the whole dwelling) (210.12(A))NEC 2020 210.12(A)
- TABLELiving room, Receptacles: No point along the floor line of any wall space more than 6 ft from a receptacle outlet (210.52(A)(1))NEC 2020 210.52(A)(1)
- TABLELiving room, Receptacles: A wall space is any space 2 ft or wider, measured around corners, unbroken by doorways, fireplaces and fixed cabinets without countertops (210.52(A)(2)(1))NEC 2020 210.52(A)(2)(1)
- TABLELiving room, Receptacles: A floor receptacle counts only within 18 in of the wall; countertop receptacles do not count toward these (210.52(A)(3), 210.52(A)(4))NEC 2020 210.52(A)(3), 210.52(A)(4)
- TABLEBedroom 1, GFCI: GFCI: not for the room itself; the dwelling's sink, bathtub and damp location rules below still apply (210.8(A))NEC 2020 210.8(A)
- TABLEBedroom 1, AFCI: Every 120 V, 15 and 20 A branch circuit supplying outlets or devices here: AFCI, except the circuits 210.12(A)'s exceptions name (listed for the whole dwelling) (210.12(A))NEC 2020 210.12(A)
- TABLEBedroom 1, Receptacles: No point along the floor line of any wall space more than 6 ft from a receptacle outlet (210.52(A)(1))NEC 2020 210.52(A)(1)
- TABLEBedroom 1, Receptacles: A wall space is any space 2 ft or wider, measured around corners, unbroken by doorways, fireplaces and fixed cabinets without countertops (210.52(A)(2)(1))NEC 2020 210.52(A)(2)(1)
- TABLEBedroom 1, Receptacles: A floor receptacle counts only within 18 in of the wall; countertop receptacles do not count toward these (210.52(A)(3), 210.52(A)(4))NEC 2020 210.52(A)(3), 210.52(A)(4)
- TABLEBedroom 2, GFCI: GFCI: not for the room itself; the dwelling's sink, bathtub and damp location rules below still apply (210.8(A))NEC 2020 210.8(A)
- TABLEBedroom 2, AFCI: Every 120 V, 15 and 20 A branch circuit supplying outlets or devices here: AFCI, except the circuits 210.12(A)'s exceptions name (listed for the whole dwelling) (210.12(A))NEC 2020 210.12(A)
- TABLEBedroom 2, Receptacles: No point along the floor line of any wall space more than 6 ft from a receptacle outlet (210.52(A)(1))NEC 2020 210.52(A)(1)
- TABLEBedroom 2, Receptacles: A wall space is any space 2 ft or wider, measured around corners, unbroken by doorways, fireplaces and fixed cabinets without countertops (210.52(A)(2)(1))NEC 2020 210.52(A)(2)(1)
- TABLEBedroom 2, Receptacles: A floor receptacle counts only within 18 in of the wall; countertop receptacles do not count toward these (210.52(A)(3), 210.52(A)(4))NEC 2020 210.52(A)(3), 210.52(A)(4)
- TABLEBathroom, GFCI: Its receptacles: GFCI (210.8(A)(1))NEC 2020 210.8(A)(1)
- TABLEBathroom, AFCI: AFCI: not required for this room by 210.12(A), which does not name it (210.12(A))NEC 2020 210.12(A)
- TABLEBathroom, Receptacles: At least one receptacle outlet within 3 ft of the outside edge of each basin, not more than 12 in below its top (210.52(D))NEC 2020 210.52(D)
- TABLEHallway, GFCI: GFCI: not for the room itself; the dwelling's sink, bathtub and damp location rules below still apply (210.8(A))NEC 2020 210.8(A)
- TABLEHallway, AFCI: Every 120 V, 15 and 20 A branch circuit supplying outlets or devices here: AFCI, except the circuits 210.12(A)'s exceptions name (listed for the whole dwelling) (210.12(A))NEC 2020 210.12(A)
- TABLEHallway, Receptacles: At least one receptacle outlet: 14 ft along the centerline is 10 ft or more (210.52(H))NEC 2020 210.52(H)
- TABLECloset, GFCI: GFCI: not for the room itself; the dwelling's sink, bathtub and damp location rules below still apply (210.8(A))NEC 2020 210.8(A)
- TABLECloset, AFCI: Every 120 V, 15 and 20 A branch circuit supplying outlets or devices here: AFCI, except the circuits 210.12(A)'s exceptions name (listed for the whole dwelling) (210.12(A))NEC 2020 210.12(A)
- TABLECloset, Receptacles: None required here by 210.52 (210.52)NEC 2020 210.52
- TABLELaundry area, GFCI: Its receptacles: GFCI (210.8(A)(10))NEC 2020 210.8(A)(10)
- TABLELaundry area, AFCI: Every 120 V, 15 and 20 A branch circuit supplying outlets or devices here: AFCI, except the circuits 210.12(A)'s exceptions name (listed for the whole dwelling) (210.12(A))NEC 2020 210.12(A)
- TABLELaundry area, Receptacles: At least one receptacle outlet where the laundry equipment goes (210.52(F))NEC 2020 210.52(F)
- TABLEGarage, GFCI: Its receptacles: GFCI (210.8(A)(2))NEC 2020 210.8(A)(2)
- TABLEGarage, GFCI: The outlet supplying a sump pump, where one is installed (150 V or less to ground, 60 A or less): GFCI at the breaker or a device or outlet in its circuit, unless the plug, the cord within 12 in of the plug or the appliance itself provides it (210.8(D), 422.5(A)(6), 422.5(B))NEC 2020 210.8(D), 422.5(A)(6), 422.5(B)
- TABLEGarage, AFCI: AFCI: not required for this room by 210.12(A), which does not name it (210.12(A))NEC 2020 210.12(A)
- TABLEGarage, Receptacles: At least one receptacle outlet in each vehicle bay (2 bays: at least 2), in addition to any receptacle required for specific equipment, not more than 5½ ft above the floor (210.52(G)(1))NEC 2020 210.52(G)(1)
- TABLEWhole dwelling, GFCI: 210.8(A) reaches 125 V through 250 V receptacles on single-phase circuits of 150 V or less to ground (210.8(A))NEC 2020 210.8(A)
- TABLEWhole dwelling, GFCI: 210.8(A)'s exceptions: outdoors, a receptacle that is not readily accessible, on a branch circuit dedicated to snow-melting, deicing, or pipeline and vessel heating equipment, installed as that exception says; in a basement, a receptacle supplying only a permanently installed fire alarm or burglar alarm system; in the locations that exception names, a listed locking support and mounting receptacle serving a ceiling luminaire or ceiling fan, unless a general-purpose convenience receptacle is integral to the luminaire or fan (210.8(A) Exception to (3), 210.8(A) Exception to (5), 210.8(A) Exception to (1) through (3), (5) through (8), and (10))NEC 2020 210.8(A) Exception to (3), 210.8(A) Exception to (5), 210.8(A) Exception to (1) through (3), (5) through (8), and (10)
- TABLEWhole dwelling, GFCI: Outdoor receptacles: GFCI (210.8(A)(3))NEC 2020 210.8(A)(3)
- TABLEWhole dwelling, GFCI: Every outdoor outlet, not only receptacles (single-phase, 150 V or less to ground, 50 A or less), except lighting outlets: GFCI. For an outdoor air conditioner or heat pump, run the outdoor HVAC GFCI check: its exception depends on the edition, the date and your state (210.8(F), 210.8(F) Exception)NEC 2020 210.8(F), 210.8(F) Exception
- TABLEWhole dwelling, GFCI: Anywhere in the dwelling: receptacles within 6 ft of the top inside edge of a sink's bowl, within 6 ft of the outside edge of a bathtub or shower stall, and in indoor damp and wet locations: GFCI (210.8(A)(7), 210.8(A)(9), 210.8(A)(11))NEC 2020 210.8(A)(7), 210.8(A)(9), 210.8(A)(11)
- TABLEWhole dwelling, GFCI: The receptacle 210.63 requires near heating, air-conditioning and refrigeration equipment: GFCI (210.8(E))NEC 2020 210.8(E)
- TABLEWhole dwelling, GFCI: The outlet supplying an automotive vacuum machine, a drinking water cooler or bottle fill station, a cord-and-plug-connected high-pressure spray washing machine, a tire inflation machine, a sump pump and a dishwasher, wherever in the dwelling one is installed (150 V or less to ground, 60 A or less): GFCI at the breaker or a device or outlet in its circuit, unless the plug, the cord within 12 in of the plug or the appliance itself provides it (210.8(D), 422.5(A)(1), 422.5(A)(2), 422.5(A)(3), 422.5(A)(4), 422.5(A)(6), 422.5(A)(7), 422.5(B))NEC 2020 210.8(D), 422.5(A)(1), 422.5(A)(2), 422.5(A)(3), 422.5(A)(4), 422.5(A)(6), 422.5(A)(7), 422.5(B)
- TABLEWhole dwelling, GFCI: The branch circuit supplying a vending machine, wherever in the dwelling one is installed (150 V or less to ground, 60 A or less): GFCI at the breaker or a device or outlet in its circuit, unless the plug or the cord within 12 in of the plug provides it; GFCI within the machine itself does not count (210.8(D), 422.5(A)(5), 422.5(B))NEC 2020 210.8(D), 422.5(A)(5), 422.5(B)
- TABLEWhole dwelling, Receptacles: Outdoors: at least one receptacle outlet at the front and one at the back, readily accessible from grade and not more than 6½ ft above it (210.52(E)(1))NEC 2020 210.52(E)(1)
- TABLEWhole dwelling, AFCI: Where branch-circuit wiring for a room 210.12(A) names is modified, replaced or extended: AFCI, except an extension of 6 ft or less with no added outlets or devices (210.12(D), 210.12(D) Exception)NEC 2020 210.12(D), 210.12(D) Exception
- TABLEWhole dwelling, AFCI: 210.12(A)'s exceptions in force: an individual branch circuit supplying a fire alarm system installed as that exception says, run in metal raceway, metal auxiliary gutter, steel-armored cable, or Type MC or Type AC cable, with metal boxes, conduit bodies and enclosures (210.12(A) Exception)NEC 2020 210.12(A) Exception
- TABLEWhole dwelling, Circuit: Kitchen small-appliance 1: a 20 A branch circuit. Serves the kitchen's countertop, wall and floor receptacles and the refrigerator's, and may also serve the pantry, breakfast room and dining room; in addition to the required receptacles, a specific appliance's receptacle (a refrigerator's, say) may have its own circuit of 15 A or more (210.11(C)(1), 210.52(B)(1), 210.52(B)(1) Exception No. 2)NEC 2020 210.11(C)(1), 210.52(B)(1), 210.52(B)(1) Exception No. 2
- TABLEWhole dwelling, Circuit: Kitchen small-appliance 2: a 20 A branch circuit. Serves the kitchen's countertop, wall and floor receptacles and the refrigerator's, and may also serve the pantry, breakfast room and dining room; in addition to the required receptacles, a specific appliance's receptacle (a refrigerator's, say) may have its own circuit of 15 A or more (210.11(C)(1), 210.52(B)(1), 210.52(B)(1) Exception No. 2)NEC 2020 210.11(C)(1), 210.52(B)(1), 210.52(B)(1) Exception No. 2
- TABLEWhole dwelling, Circuit: Laundry: a 20 A branch circuit. The laundry receptacle outlets only (210.11(C)(2))NEC 2020 210.11(C)(2)
- TABLEWhole dwelling, Circuit: Bathroom receptacles: a 20 A branch circuit. Bathroom receptacles only; where it supplies a single bathroom, outlets for other equipment in that bathroom may be on it within 210.23(A)(1) and (A)(2) (210.11(C)(3), 210.11(C)(3) Exception)NEC 2020 210.11(C)(3), 210.11(C)(3) Exception
- TABLEWhole dwelling, Circuit: Garage receptacles: a 20 A branch circuit. The garage receptacles and no other outlets, except that it may also supply readily accessible outdoor receptacles (210.11(C)(4), 210.11(C)(4) Exception)NEC 2020 210.11(C)(4), 210.11(C)(4) Exception
- RESULTRequired circuits: Kitchen small-appliance 1, Kitchen small-appliance 2, Laundry, Bathroom receptacles, Garage receptaclesNEC 2020 210.11(C)
Example 3: an upper-floor apartment, NEC 2026
6 rooms, 3 required circuits (NEC 2026).
Show the math
- GIVENEdition: NEC 2026
- GIVENDwelling: Multifamily dwelling, any other unit
- TABLEKitchen, GFCI: Its receptacles: GFCI (210.8(A)(7))NEC 2026 210.8(A)(7)
- TABLEKitchen, GFCI: The branch circuit or outlet supplying a dishwasher, an electric range, a wall-mounted oven, a counter-mounted cooking unit and a microwave oven (150 V or less to ground, 60 A or less): GFCI (210.8(D)(7), 210.8(D)(8), 210.8(D)(9), 210.8(D)(10), 210.8(D)(12))NEC 2026 210.8(D)(7), 210.8(D)(8), 210.8(D)(9), 210.8(D)(10), 210.8(D)(12)
- TABLEKitchen, AFCI: Every 120 V, 10, 15 and 20 A branch circuit supplying outlets or devices here: AFCI, except the circuits 210.12(B)'s exceptions name (listed for the whole dwelling) (210.12(B)(1))NEC 2026 210.12(B)(1)
- TABLEKitchen, Receptacles: No point along the floor line of any wall space more than 6 ft from a receptacle outlet (210.52(A)(1))NEC 2026 210.52(A)(1)
- TABLEKitchen, Receptacles: A wall space is any space 2 ft or wider, measured around corners, unbroken by doorways, fireplaces, stationary appliances and fixed cabinets (210.52(A)(2)(1))NEC 2026 210.52(A)(2)(1)
- TABLEKitchen, Receptacles: A floor receptacle counts only within 18 in of the wall; countertop receptacles do not count toward these (210.52(A)(3), 210.52(A)(4))NEC 2026 210.52(A)(3), 210.52(A)(4)
- TABLEKitchen, Receptacles: Below the countertop of a fixed room divider (a bar-type counter), none within 24 in of the countertop (210.52(A)(5))NEC 2026 210.52(A)(5)
- TABLEKitchen, Receptacles: Its wall, floor and countertop receptacles and the refrigerator's are on the 20 A small-appliance circuits, which have no other outlets; in addition to the required receptacles, one for a specific appliance (a refrigerator, say) may have its own circuit of 15 A or more, and a clock receptacle or one powering a gas range's, oven's or cooktop's supplemental equipment and lighting may be on a small-appliance circuit (210.52(B)(1), 210.52(B)(2), 210.52(B)(1) Exception No. 2, 210.52(B)(2) Exception No. 1, 210.52(B)(2) Exception No. 2)NEC 2026 210.52(B)(1), 210.52(B)(2), 210.52(B)(1) Exception No. 2, 210.52(B)(2) Exception No. 1, 210.52(B)(2) Exception No. 2
- TABLEKitchen, Receptacles: Countertop receptacles on at least two small-appliance circuits, and no small-appliance circuit serves another kitchen (210.52(B)(3))NEC 2026 210.52(B)(3)
- TABLEKitchen, Receptacles: Countertops and work surfaces 12 in or wider: no point along the wall line more than 24 in from a receptacle outlet (210.52(C)(1))NEC 2026 210.52(C)(1)
- TABLEKitchen, Receptacles: Island or peninsula without a receptacle: electrical provisions there for one later (210.52(C)(2))NEC 2026 210.52(C)(2)
- TABLEKitchen, Receptacles: Countertop receptacles on or not more than 20 in above it, or in it or a work surface as listed assemblies (210.52(C)(3))NEC 2026 210.52(C)(3)
- TABLEKitchen, Receptacles: Below a countertop or work surface, where accessible outside cabinet or wall surfaces: none on the walls beside the base cabinets within 24 in, and none beneath it within 24 in of it, except a receptacle installed in a drawer (210.52(C)(4), 210.52(C)(4) Exception)NEC 2026 210.52(C)(4), 210.52(C)(4) Exception
- TABLELiving room, GFCI: GFCI: not for the room itself; the dwelling's sink, bathtub and damp location rules below still apply (210.8(A))NEC 2026 210.8(A)
- TABLELiving room, AFCI: Every 120 V, 10, 15 and 20 A branch circuit supplying outlets or devices here: AFCI, except the circuits 210.12(B)'s exceptions name (listed for the whole dwelling) (210.12(B)(4))NEC 2026 210.12(B)(4)
- TABLELiving room, Receptacles: No point along the floor line of any wall space more than 6 ft from a receptacle outlet (210.52(A)(1))NEC 2026 210.52(A)(1)
- TABLELiving room, Receptacles: A wall space is any space 2 ft or wider, measured around corners, unbroken by doorways, fireplaces, stationary appliances and fixed cabinets (210.52(A)(2)(1))NEC 2026 210.52(A)(2)(1)
- TABLELiving room, Receptacles: A floor receptacle counts only within 18 in of the wall; countertop receptacles do not count toward these (210.52(A)(3), 210.52(A)(4))NEC 2026 210.52(A)(3), 210.52(A)(4)
- TABLELiving room, Receptacles: Below the countertop of a fixed room divider (a bar-type counter), none within 24 in of the countertop (210.52(A)(5))NEC 2026 210.52(A)(5)
- TABLEBedroom, GFCI: GFCI: not for the room itself; the dwelling's sink, bathtub and damp location rules below still apply (210.8(A))NEC 2026 210.8(A)
- TABLEBedroom, AFCI: Every 120 V, 10, 15 and 20 A branch circuit supplying outlets or devices here: AFCI, except the circuits 210.12(B)'s exceptions name (listed for the whole dwelling) (210.12(B)(8))NEC 2026 210.12(B)(8)
- TABLEBedroom, Receptacles: No point along the floor line of any wall space more than 6 ft from a receptacle outlet (210.52(A)(1))NEC 2026 210.52(A)(1)
- TABLEBedroom, Receptacles: A wall space is any space 2 ft or wider, measured around corners, unbroken by doorways, fireplaces, stationary appliances and fixed cabinets (210.52(A)(2)(1))NEC 2026 210.52(A)(2)(1)
- TABLEBedroom, Receptacles: A floor receptacle counts only within 18 in of the wall; countertop receptacles do not count toward these (210.52(A)(3), 210.52(A)(4))NEC 2026 210.52(A)(3), 210.52(A)(4)
- TABLEBedroom, Receptacles: Below the countertop of a fixed room divider (a bar-type counter), none within 24 in of the countertop (210.52(A)(5))NEC 2026 210.52(A)(5)
- TABLEBathroom, GFCI: Its receptacles: GFCI (210.8(A)(1))NEC 2026 210.8(A)(1)
- TABLEBathroom, AFCI: AFCI: not required for this room by 210.12(B), which does not name it (210.12(B))NEC 2026 210.12(B)
- TABLEBathroom, Receptacles: At least one receptacle outlet within 3 ft of the outside edge of each sink, not more than 12 in below its top (210.52(D)(1) and (D)(2))NEC 2026 210.52(D)(1) and (D)(2)
- TABLEHallway, GFCI: GFCI: not for the room itself; the dwelling's sink, bathtub and damp location rules below still apply (210.8(A))NEC 2026 210.8(A)
- TABLEHallway, AFCI: Every 120 V, 10, 15 and 20 A branch circuit supplying outlets or devices here: AFCI, except the circuits 210.12(B)'s exceptions name (listed for the whole dwelling) (210.12(B)(12))NEC 2026 210.12(B)(12)
- TABLEHallway, Receptacles: None required by 210.52(H): 8 ft along the centerline is under 10 ft (210.52(H))NEC 2026 210.52(H)
- TABLEBalcony, deck or porch, GFCI: Its receptacles: GFCI (210.8(A)(4))NEC 2026 210.8(A)(4)
- TABLEBalcony, deck or porch, GFCI: Every outdoor outlet, not only receptacles (single-phase, 150 V or less to ground, 60 A or less), except lighting outlets: GFCI (210.8(F), 210.8(F) Exception No. 1)NEC 2026 210.8(F), 210.8(F) Exception No. 1
- TABLEBalcony, deck or porch, AFCI: AFCI: not required for this room by 210.12(B), which does not name it (210.12(B))NEC 2026 210.12(B)
- TABLEBalcony, deck or porch, Receptacles: At least one receptacle outlet reached from it, not more than 6½ ft above its walking surface (210.52(E)(3))NEC 2026 210.52(E)(3)
- TABLEWhole dwelling, GFCI: 210.8(A) reaches 125 V through 250 V receptacles on single-phase circuits of 150 V or less to ground (210.8(A))NEC 2026 210.8(A)
- TABLEWhole dwelling, GFCI: 210.8(A)'s exceptions: a receptacle that is not readily accessible, on a branch circuit dedicated to snow-melting, deicing, or pipeline and vessel heating equipment, installed as that exception says; a receptacle supplying only a permanently installed premises security system; a listed weight-supporting ceiling receptacle (WSCR) with its compatible fitting, supporting a ceiling luminaire or ceiling-suspended fan, unless a general-purpose convenience receptacle is integral to the luminaire or fan; a factory-installed receptacle that is not readily accessible, mounted inside an exhaust fan assembly, unless its installation instructions or listing require GFCI (210.8(A) Exception No. 1, 210.8(A) Exception No. 2, 210.8(A) Exception No. 3, 210.8(A) Exception No. 4)NEC 2026 210.8(A) Exception No. 1, 210.8(A) Exception No. 2, 210.8(A) Exception No. 3, 210.8(A) Exception No. 4
- TABLEWhole dwelling, GFCI: Outdoor receptacles: GFCI (210.8(A)(4))NEC 2026 210.8(A)(4)
- TABLEWhole dwelling, GFCI: Every outdoor outlet, not only receptacles (single-phase, 150 V or less to ground, 60 A or less), except lighting outlets: GFCI. For an outdoor air conditioner or heat pump, run the outdoor HVAC GFCI check: its exception depends on the edition, the date and your state (210.8(F), 210.8(F) Exception No. 1)NEC 2026 210.8(F), 210.8(F) Exception No. 1
- TABLEWhole dwelling, GFCI: Anywhere in the dwelling: receptacles within 6 ft of the top inside edge of a sink's bowl, within 6 ft of the outside edge of a bathtub or shower stall, and in indoor damp and wet locations: GFCI (210.8(A)(9), 210.8(A)(11), 210.8(A)(13) and (A)(14))NEC 2026 210.8(A)(9), 210.8(A)(11), 210.8(A)(13) and (A)(14)
- TABLEWhole dwelling, GFCI: The receptacle 210.63 requires near heating, air-conditioning and refrigeration equipment: GFCI (210.8(E))NEC 2026 210.8(E)
- TABLEWhole dwelling, GFCI: The branch circuit or outlet supplying an automotive vacuum machine, a drinking water cooler or bottle fill station, a high-pressure spray washing machine, a tire inflation machine, a vending machine, a sump pump, a dishwasher, an electric range, a wall-mounted oven, a counter-mounted cooking unit, a clothes dryer and a microwave oven, wherever in the dwelling one is installed (150 V or less to ground, 60 A or less): GFCI (210.8(D)(1), 210.8(D)(2), 210.8(D)(3), 210.8(D)(4), 210.8(D)(5), 210.8(D)(6), 210.8(D)(7), 210.8(D)(8), 210.8(D)(9), 210.8(D)(10), 210.8(D)(11), 210.8(D)(12))NEC 2026 210.8(D)(1), 210.8(D)(2), 210.8(D)(3), 210.8(D)(4), 210.8(D)(5), 210.8(D)(6), 210.8(D)(7), 210.8(D)(8), 210.8(D)(9), 210.8(D)(10), 210.8(D)(11), 210.8(D)(12)
- TABLEWhole dwelling, Receptacles: Outdoors: none required by 210.52(E)(1) or (E)(2) for a unit that is not at grade with its own entrance; a balcony, deck or porch keeps its own rule (210.52(E)(1), 210.52(E)(2))NEC 2026 210.52(E)(1), 210.52(E)(2)
- TABLEWhole dwelling, AFCI: Where branch-circuit wiring for a room 210.12(B) names is modified, replaced or extended: AFCI, except an extension of 6 ft or less with no added outlets or devices (210.12(E), 210.12(E) Exception)NEC 2026 210.12(E), 210.12(E) Exception
- TABLEWhole dwelling, AFCI: 210.12(B)'s exceptions in force: an individual branch circuit supplying a fire alarm system installed as that exception says, run in metal raceway, metal auxiliary gutter, steel-armored cable, or Type MC or Type AC cable, with metal boxes, conduit bodies and enclosures; the individual branch circuit supplying an outlet for arc welding equipment (210.12(B) Exception No. 1, 210.12(B) Exception No. 2)NEC 2026 210.12(B) Exception No. 1, 210.12(B) Exception No. 2
- TABLEWhole dwelling, Circuit: Kitchen small-appliance 1: a 20 A branch circuit. Serves the kitchen's countertop, wall and floor receptacles and the refrigerator's, and may also serve the pantry, breakfast room and dining room; in addition to the required receptacles, a specific appliance's receptacle (a refrigerator's, say) may have its own circuit of 15 A or more (210.11(C)(1), 210.52(B)(1), 210.52(B)(1) Exception No. 2)NEC 2026 210.11(C)(1), 210.52(B)(1), 210.52(B)(1) Exception No. 2
- TABLEWhole dwelling, Circuit: Kitchen small-appliance 2: a 20 A branch circuit. Serves the kitchen's countertop, wall and floor receptacles and the refrigerator's, and may also serve the pantry, breakfast room and dining room; in addition to the required receptacles, a specific appliance's receptacle (a refrigerator's, say) may have its own circuit of 15 A or more (210.11(C)(1), 210.52(B)(1), 210.52(B)(1) Exception No. 2)NEC 2026 210.11(C)(1), 210.52(B)(1), 210.52(B)(1) Exception No. 2
- TABLEWhole dwelling, Circuit: Bathroom receptacles: a 20 A branch circuit. Bathroom receptacles only; where it supplies a single bathroom, outlets for other equipment in that bathroom may be on it within 210.23(B)(1) and 210.23(B)(2) (210.11(C)(3), 210.11(C)(3) Exception)NEC 2026 210.11(C)(3), 210.11(C)(3) Exception
- RESULTRequired circuits: Kitchen small-appliance 1, Kitchen small-appliance 2, Bathroom receptaclesNEC 2026 210.11(C)
Frequently Asked Questions
Which rooms need GFCI protection in a house?
Under NEC 2023 210.8(A), every 125-volt through 250-volt receptacle on a single-phase circuit of 150 volts or less to ground in bathrooms, garages, outdoors, crawl spaces at or below grade, basements, kitchens, areas with a sink and permanent provisions for food or drink preparation or cooking, boathouses, laundry areas and indoor damp and wet locations, and any receptacle within 6 ft of a sink's bowl or of a bathtub or shower stall. 210.8(D) adds, wherever in the dwelling it is installed, the branch circuit or outlet supplying an appliance it lists that is rated 150 volts or less to ground and 60 amperes or less: automotive vacuum machines, drinking water coolers and bottle fill stations, high-pressure spray washing machines, tire inflation machines, vending machines, sump pumps, dishwashers, electric ranges, wall-mounted ovens, counter-mounted cooking units, clothes dryers and microwave ovens. 210.8(A) prints exceptions, among them a receptacle supplying only a permanently installed premises security system; the checklist lists each room's lines with its cite and the exceptions for the whole dwelling.
Which rooms need AFCI protection?
NEC 2023 210.12(B) covers the 120-volt, 10, 15 and 20 A branch circuits supplying outlets or devices in kitchens, family rooms, dining rooms, living rooms, parlors, libraries, dens, bedrooms, sunrooms, recreation rooms, closets, hallways, laundry areas and similar areas. Bathrooms, garages, basements and outdoors are not on the list. An individual branch circuit supplying a fire alarm system, installed in the wiring methods 210.12's exception names, is excepted. The 2020 edition, 210.12(A), names the same rooms for 15 and 20 A circuits.
How many circuits does a kitchen need?
At least two 20-ampere small-appliance circuits for its countertop receptacles, and no small-appliance circuit may serve more than one kitchen (210.11(C)(1) and 210.52(B)(3)). They also serve the kitchen's wall and floor receptacles, the refrigerator's, and those of the dining room, pantry and breakfast room, and they have no other outlets, except a clock receptacle or one powering a gas range's, oven's or cooktop's supplemental equipment and lighting (210.52(B)(2)). In addition to the required receptacles, one for a specific appliance, such as the refrigerator, may have its own circuit of 15 amperes or more (210.52(B)(1) Exception No. 2). The checklist also says which appliance circuits need GFCI.
How far apart do receptacles have to be?
In a living room, bedroom, kitchen and the other rooms 210.52(A) names, no point along the floor line of any wall space may be more than 6 ft from a receptacle outlet, and a wall space is any space 2 ft or wider. On a countertop 12 in or wider, no point along the wall line may be more than 24 in from one (210.52(C)(1)). The checklist states these distances; it does not turn a wall's length into a count, because doorways and fixed cabinets decide where each wall space starts and ends.
What did the 2023 NEC change for kitchens?
The 2020 edition's kitchen GFCI item reaches only the receptacles that serve the countertop surfaces (210.8(A)(6)); the 2023 and 2026 items reach every kitchen receptacle. The 2020 appliance rule (210.8(D) and 422.5(A)) lists dishwashers and sump pumps among its seven appliances; the 2023 and 2026 210.8(D) also lists electric ranges, wall-mounted ovens, counter-mounted cooking units, clothes dryers and microwave ovens. Pick the edition at the top of the checklist to see each.
Does it apply my state's amendments?
No. Pick your state and the checklist shows its record from the NEC adoption page and, where the state's adopting documents amend 210.8, 210.11, 210.12 or 210.52, names those sections and says the lines are the NEC text without the amendment. Some states change where GFCI and AFCI apply (Idaho by room, Iowa for the whole one- or two-family dwelling), so read the amendment or ask your inspector. City and county amendments are not read here.
Does it put the circuits on the panel schedule?
Yes. Save the checklist to a job, open the panel schedule, and Add from your saved jobs adds each required circuit as a 20 A row and shows any state check the checklist carries as it adds them. The rows leave the wire and the load for you to enter, because the checklist sizes no conductor and states no load.
Related Calculators
Electrical Panel Schedule
Add this checklist's required circuits as rows, then fill in each one's wire and load.
Outdoor HVAC GFCI Requirement
Whether an outdoor air conditioner or heat pump needs GFCI under 210.8(F), by state and date.
Box Fill Calculator
The cubic inches each box needs for its conductors and devices.
NEC Adoption by State
Which NEC edition each state enforces, read from its own documents.