Manual J by climate zone
BTU Per Square Foot Chart by Climate Zone
The figures in this chart are ACCA Manual J loads our engine computes on one stated house, DOE's 2021 code-built reference house, at a real ASHRAE weather station in each climate zone, with DOE's own sizing of the same house beside them.
BTU Per Square Foot by IECC Climate Zone
BTU per square foot of design load by IECC 2021 climate zone: ACCA Manual J (8th edition, abridged) computed by our engine on DOE's 2,376 sq ft two-storey reference house, built to the 2021 IECC for each zone, at the ASHRAE 2021 weather station nearest DOE's own model site. Heating is the 99% design load, cooling the 1% sensible plus latent load, each over the floor area.
Swipe the table sideways to see the rest of its columns. →
| Zone and station | Heating BTU/sq ft | Cooling BTU/sq ft |
|---|---|---|
| 1A (CZ1AWH)MIAMI NHC, Florida, 6 mi | 5.2 | 12.1 |
| 1A (CZ1AWHT)HONOLULU INTL, Hawaii, 0 mi | 1.5 | 11.6 |
| 1A (CZ1AWHTS)HONOLULU INTL, Hawaii, 0 mi | 1.5 | 12.5 |
| 2A (CZ2AWH)MACDILL AFB, Florida, 0 mi | 7.9 | 12.9 |
| 2B (CZ2B)DAVIS-MONTHAN AFB, Arizona, 0 mi | 10.1 | withheld |
| 3A (CZ3A)ATLANTA HARTSFIELD-JACKSON, Georgia, 1 mi | 11.1 | 10.6 |
| 3A (CZ3AWH)MONTGOMERY, Alabama, 1 mi | 10.7 | 10.7 |
| 3B (CZ3B)EL PASO, Texas, 8 mi | 10.3 | 10.9 |
| 3C (CZ3C)BROWN FIELD, California, 0 mi | 7.0 | 8.4 |
| 4A (CZ4A)NEW YORK KENNEDY, New York, 3 mi | 9.8 | 9.3 |
| 4B (CZ4B)ALBUQUERQUE INTL, New Mexico, 0 mi | 8.7 | 9.3 |
| 4C (CZ4C)SEATTLE TACOMA, Washington, 2 mi | 7.3 | 7.5 |
| 5A (CZ5A)BUFFALO NIAGARA, New York, 1 mi | 11.9 | 8.0 |
| 5B (CZ5B)BUCKLEY AFB, Colorado, 0 mi | 11.4 | 8.1 |
| 5C (CZ5C)BREMERTON, Washington, 56 mi | 8.0 | 7.5 |
| 6A (CZ6A)ROCHESTER INTL, Minnesota, 0 mi | 15.0 | 8.3 |
| 6B (CZ6B)GREAT FALLS, Montana, 1 mi | 15.0 | 8.1 |
| 7 (CZ7)DULUTH INTL, Minnesota, 132 mi | 15.8 | 7.5 |
| 8 (CZ8)FAIRBANKS, Alaska, 2 mi | 20.8 | 6.7 |
“Withheld” is Manual J's own limit at that station for the daily range class the run used, and no substitute figure is printed in its place: 2B (CZ2B): its 28.1 °F cooling design difference is outside Manual J's printed CLTD span for the medium daily range its DOE design day reads (23.9 °F); at the high range our engine computes 29,851 BTU per hour on the same house.
The House Behind Every Figure
DOE's single-family reference house (PNNL-37098, Table 1): 2,376 sq ft on two storeys, slab on grade, gas furnace and central air, priced by the abridged Manual J method (MJ8AE) as follows. The envelope changes by zone, as DOE's 2021 model files build it; the rest does not.
- Shape: A 39.8 by 29.8 ft rectangle per floor (the proportions of DOE's 39.8 by 29.8 ft reference house), two storeys, 8.5 ft ceilings: 139 ft of exposed wall, 2,368 sq ft gross wall.
- Windows and doors: 356.4 sq ft of window (15% of the floor area), a quarter on each of north, east, west and south; 42 sq ft of solid-core door.
- People: 3 bedrooms, so 4 occupants (Manual J counts bedrooms plus one).
- Ducts: In a vented attic, R-8 duct insulation, one return near the air handler, Manual J's default leakage.
- Inside: Appliances at Manual J's 2,400 Btuh block (kitchen, laundry, a TV and a computer); no fireplace; no mechanical ventilation, humidifier or hot-water piping; the equipment's capacity data not corrected for blower heat; every opaque panel vapor-retarded.
- Windows: DOE's low-e double windows, priced in Manual J Table 3A-1's “Triple Pane or Double Pane Low-e” column and Table 2A's triple-pane clear row, the nearest the abridged method prints.
- Weather: the ASHRAE 2021 station nearest DOE's model site, its 99% heating and 1% cooling dry bulbs (Manual J's percentiles), and the daily range class read from DOE's cooling design day for that site.
Each zone's envelope from DOE's 2021 model file (DOE Building Energy Codes Program residential prototype building models, 2021 IECC (single-family, slab-on-grade, gas furnace), read 2026-11-12), and the Manual J rows it prices as. The wall is the model's cavity R parameter (the name of its insulation layer carries another figure); a cavity R Manual J does not print prices at the printed row below it. The slab edge board runs to the depth shown; Manual J prints a vertical-only edge board at one depth, three feet below grade (Construction 22B); its other insulated slab rows (22C, 22D) add horizontal board under the slab, which the model's board does not have, so a shallower vertical board prices as no edge insulation and a deeper one at the 22B row.
Swipe the table sideways to see the rest of its columns. →
| Zone | Attic | Wall | Slab edge | ACH50 |
|---|---|---|---|---|
| CZ1AWH | R30 | R13 + R0 | none | 5 |
| CZ1AWHT | R30 | R13 + R0 | none | 5 |
| CZ1AWHTS | R15 | R13 + R0 | none | 5 |
| CZ2AWH | R49 | R13 + R0 | none | 5 |
| CZ2B | R49 | R13 + R0 | none | 5 |
| CZ3A | R49 | R20 + R0 | R10, 2 ft | 3 |
| CZ3AWH | R49 | R20 + R0 | R10, 2 ft | 3 |
| CZ3B | R49 | R20 + R0 | R10, 2 ft | 3 |
| CZ3C | R49 | R20 + R0 | R10, 2 ft | 3 |
| CZ4A | R60 | R20 + R5 | R10, 4 ft | 3 |
| CZ4B | R60 | R20 + R5 | R10, 4 ft | 3 |
| CZ4C | R60 | R20 + R5 | R10, 4 ft | 3 |
| CZ5A | R60 | R20 + R5 | R10, 4 ft | 3 |
| CZ5B | R60 | R20 + R5 | R10, 4 ft | 3 |
| CZ5C | R60 | R20 + R5 | R10, 4 ft | 3 |
| CZ6A | R60 | R20 + R5 | R10, 4 ft | 3 |
| CZ6B | R60 | R20 + R5 | R10, 4 ft | 3 |
| CZ7 | R60 | R20 + R5 | R10, 4 ft | 3 |
| CZ8 | R60 | R20 + R5 | R10, 4 ft | 3 |
Beside It: DOE's Own Sizing of the Same House
DOE's EnergyPlus run of each model file sizes its own equipment. These are equipment sizes, not loads: EnergyPlus sizes at the ASHRAE 0.4% cooling and 99.6% heating design days (Manual J uses 1% and 99%) and multiplies the load by 1.15 for cooling and 1.25 for heating. Our engine's load is beside it in the same units.
DOE's autosized cooling coil (tons) and furnace (BTU per hour) from each model's EnergyPlus output, beside our Manual J load on the same house.
Swipe the table sideways to see the rest of its columns. →
| Zone | DOE cooling, tons | Our cooling load, tons | DOE furnace, BTU/h | Our heating load, BTU/h |
|---|---|---|---|---|
| CZ1AWH | 2.5 | 2.39 | 12,816 | 12,248 |
| CZ1AWHT | 2.45 | 2.29 | 4,939 | 3,468 |
| CZ1AWHTS | 1.75 | 2.47 | 4,939 | 3,650 |
| CZ2AWH | 2.49 | 2.55 | 15,790 | 18,702 |
| CZ2B | 2.6 | withheld | 18,928 | 23,988 |
| CZ3A | 2 | 2.09 | 23,362 | 26,272 |
| CZ3AWH | 2.09 | 2.12 | 19,619 | 25,352 |
| CZ3B | 1.93 | 2.17 | 18,524 | 24,474 |
| CZ3C | 1.43 | 1.67 | 12,178 | 16,738 |
| CZ4A | 1.93 | 1.83 | 29,816 | 23,351 |
| CZ4B | 1.83 | 1.83 | 19,841 | 20,567 |
| CZ4C | 1.57 | 1.48 | 18,983 | 17,440 |
| CZ5A | 1.78 | 1.59 | 30,822 | 28,309 |
| CZ5B | 1.79 | 1.61 | 27,841 | 27,000 |
| CZ5C | 1.4 | 1.48 | 17,889 | 18,992 |
| CZ6A | 2.01 | 1.64 | 42,905 | 35,654 |
| CZ6B | 1.69 | 1.61 | 38,001 | 35,643 |
| CZ7 | 1.72 | 1.49 | 44,816 | 37,497 |
| CZ8 | 1.65 | 1.33 | 55,373 | 49,411 |
Where our cooling reads “withheld”, Manual J's printed tables do not reach that station at the daily range class the run used: CZ2B, its 28.1 °F cooling design difference is outside Manual J's printed CLTD span for the medium daily range its DOE design day reads (23.9 °F); at the high range our engine computes 29,851 BTU per hour on the same house.
Lab Figures for Other Houses
National labs and DOE's Building America program print loads and equipment sizes for their own stated houses. None is a load per square foot by climate zone, and each has its own house, weather and sizing rule, printed with it; they sit here as cross-checks on the scale of the figures above, not as our answer.
National Renewable Energy Laboratory: Procedures for Calculating Residential Dehumidification Loads (NREL/TP-5500-66515, June 2016)
Table 3. Simulated Air Conditioner Total Rated Capacity (tons), page 9 (zones from Table 1, page 6). “The air conditioner in each home was sized using ACCA Manual J and S procedures” The house: a three-bedroom, two-bathroom, 2,000 sq ft slab-on-grade house, 15% window-to-wall ratio, at three envelope levels (code, ENERGY STAR, Building America prototype). Weather: each city's 1% dry bulb, as the report's Table 1 prints it. Sizing: Manual S equipment selection. These figures are equipment capacities, not loads.
Swipe the table sideways to see the rest of its columns. →
| Place | Column | Figure |
|---|---|---|
| Miami, FL (zone 1) | Code | 2.6 tons |
| Miami, FL (zone 1) | ENERGY STAR | 1.6 tons |
| Miami, FL (zone 1) | BA Prototype | 1.2 tons |
| Houston, TX (zone 2A) | Code | 2.7 tons |
| Houston, TX (zone 2A) | ENERGY STAR | 1.7 tons |
| Houston, TX (zone 2A) | BA Prototype | 1.3 tons |
| Orlando, FL (zone 2A) | Code | 2.5 tons |
| Orlando, FL (zone 2A) | ENERGY STAR | 1.6 tons |
| Orlando, FL (zone 2A) | BA Prototype | 1.2 tons |
| Phoenix, AZ (zone 2B) | Code | 3.4 tons |
| Phoenix, AZ (zone 2B) | ENERGY STAR | 2.2 tons |
| Phoenix, AZ (zone 2B) | BA Prototype | 1.6 tons |
| Atlanta, GA (zone 3A) | Code | 2.3 tons |
| Atlanta, GA (zone 3A) | ENERGY STAR | 1.3 tons |
| Atlanta, GA (zone 3A) | BA Prototype | 1.2 tons |
| Dallas, TX (zone 3A) | Code | 2.9 tons |
| Dallas, TX (zone 3A) | ENERGY STAR | 1.5 tons |
| Dallas, TX (zone 3A) | BA Prototype | 1.4 tons |
| Las Vegas, NV (zone 3B) | Code | 3.2 tons |
| Las Vegas, NV (zone 3B) | ENERGY STAR | 1.7 tons |
| Las Vegas, NV (zone 3B) | BA Prototype | 1.6 tons |
| Nashville, TN (zone 4A) | Code | 2.5 tons |
| Nashville, TN (zone 4A) | ENERGY STAR | 1.4 tons |
| Nashville, TN (zone 4A) | BA Prototype | 1.3 tons |
| Albuquerque, NM (zone 4B) | Code | 2.1 tons |
| Albuquerque, NM (zone 4B) | ENERGY STAR | 1.3 tons |
| Albuquerque, NM (zone 4B) | BA Prototype | 1.2 tons |
| Indianapolis, IN (zone 5A) | Code | 2.2 tons |
| Indianapolis, IN (zone 5A) | ENERGY STAR | 1.3 tons |
| Indianapolis, IN (zone 5A) | BA Prototype | 1.2 tons |
U.S. Department of Energy, Building America (IBACOS): Strategy Guideline: Accurate Heating and Cooling Load Calculations (2011)
Table 2. Baseline Calculated Loads Using ACCA MJ8, page 6 (conditions: Table 1, page 5). “Table 2. Baseline Calculated Loads Using ACCA MJ8” The house: two 2,223 sq ft one-story houses to the 2009 IECC prescriptive path: Chicago (conditioned basement) and Orlando (slab-on-grade). Weather: Chicago 89 F dry bulb, 73 F wet bulb cooling, 2 F heating; Orlando 92 F dry bulb, 76 F wet bulb cooling, 42 F heating (Table 1). These figures are Manual J loads.
Swipe the table sideways to see the rest of its columns. →
| Place | Column | Figure |
|---|---|---|
| Chicago (zone 5) | Heating Load | 41,700 BTU/h |
| Chicago (zone 5) | Sensible Cooling | 17,400 BTU/h |
| Chicago (zone 5) | Latent Cooing | 3,200 BTU/h |
| Chicago (zone 5) | Total Cooling | 20,600 BTU/h |
| Orlando (zone 2) | Heating Load | 23,600 BTU/h |
| Orlando (zone 2) | Sensible Cooling | 16,600 BTU/h |
| Orlando (zone 2) | Latent Cooing | 4,000 BTU/h |
| Orlando (zone 2) | Total Cooling | 20,700 BTU/h |
U.S. Department of Energy, Building America (IBACOS): Strategy Guideline: HVAC Equipment Sizing (February 2012)
Table 1. ACCA Manual J Heating and Cooling Loads, page 6. “The Manual J loads from Burdick (2011) are listed in Table 1.” The house: two 2,223 sq ft one-story houses to the 2009 IECC prescriptive path: Chicago (conditioned basement) and Orlando (slab-on-grade). Weather: Chicago 89 F dry bulb, 73 F wet bulb cooling, 2 F heating; Orlando 92 F dry bulb, 76 F wet bulb cooling, 42 F heating (Table 1). These figures are Manual J loads.
Swipe the table sideways to see the rest of its columns. →
| Place | Column | Figure |
|---|---|---|
| Chicago (zone 5) | Heating Load | 41,660 BTU/h |
| Chicago (zone 5) | Sensible Cooling | 17,370 BTU/h |
| Chicago (zone 5) | Latent Cooling | 3,240 BTU/h |
| Chicago (zone 5) | Total Cooling | 20,610 BTU/h |
| Orlando (zone 2) | Heating Load | 23,640 BTU/h |
| Orlando (zone 2) | Sensible Cooling | 16,630 BTU/h |
| Orlando (zone 2) | Latent Cooling | 4,060 BTU/h |
| Orlando (zone 2) | Total Cooling | 20,690 BTU/h |
Oak Ridge National Laboratory: An Analysis of Representative Heating Load Lines for Residential HSPF Ratings (ORNL/TM-2015/281, July 2015)
Table A.1. Summary of locations and house types modeled in EnergyPlus and cooling capacity sizes autoselected, page A-7 (house: page 4). “Set points: cooling = 75°F; heating = 70°F” The house: two-story 30 by 40 ft houses, 2,400 sq ft conditioned (plus 1,200 sq ft where a conditioned basement is assumed), by DOE heating region, not IECC zone. Weather: EnergyPlus V8.1 autosizing at each location. These figures are equipment capacities, not loads.
Swipe the table sideways to see the rest of its columns. →
| Place | Column | Figure |
|---|---|---|
| Indianapolis, Indiana | Heated basement, IECC 2006 | 2.3 tons |
| Indianapolis, Indiana | Unheated basement, IECC 2006 | 2.2 tons |
| Indianapolis, Indiana | Slab, IECC 2006 | 2.1 tons |
| Indianapolis, Indiana | Crawl space, IECC 2006 | 2.3 tons |
| Indianapolis, Indiana | Heated basement, IECC 2009 | 2.2 tons |
| Indianapolis, Indiana | Heated basement, IECC 2012 | 1.9 tons |
| Philadelphia, Pennsylvania | Heated basement, IECC 2006 | 2.5 tons |
| Omaha, Nebraska | Heated basement, IECC 2006 | 2.5 tons |
| Peoria, Illinois | Heated basement, IECC 2006 | 2.4 tons |
| Atlanta, Georgia | Heated basement, IECC 2006 | 2.5 tons |
| Oklahoma City, Oklahoma | Heated basement, IECC 2006 | 2.8 tons |
| Minneapolis, Minnesota | Heated basement, IECC 2006 | 2.4 tons |
| Eagle County, Colorado | Heated basement, IECC 2006 | 2 tons |
| Tampa, Florida | Slab, IECC 2006 | 2.7 tons |
| Fort Worth, Texas | Slab, IECC 2006 | 2.9 tons |
| Portland, Oregon | Crawl space, IECC 2006 | 1.9 tons |
Why a Chart by Zone Needs a Stated House
A heating or cooling load is the house's envelope, glass, air leakage and ducts, meeting the design weather at its site. No code book or national lab document we have read prints one BTU per square foot figure by climate zone, because the figure changes with the house. So this chart fixes the house, DOE's own reference house built to the 2021 code in each zone, and lets only the weather and the zone's code envelope move. The 40 Manual J loads ACCA's blog reports ran from 624 to 3,325 sq ft per ton on real houses; size equipment from a load on yours.
Frequently Asked Questions
How many BTU per square foot to cool a house?
It depends on the house and the weather, which is why a single figure misleads. On DOE's 2,376 sq ft house built to the 2021 energy code, our Manual J engine computes 6.7 to 12.9 BTU per sq ft of cooling across the 18 zone runs where Manual J's tables reach the station (zone 4A at New York: 9.3; zone 3A at Atlanta: 10.6). DOE says the “commonly used estimate” of one ton per 400 to 500 sq ft “fails to take into account local climate and the efficiency of a house”.
How many BTU per square foot to heat a house?
On the same house our engine computes 1.5 to 20.8 BTU per sq ft of heating at Manual J's 99% design temperature, from HONOLULU INTL to FAIRBANKS (zone 4A at New York: 9.8). A house with less insulation or more air leakage needs more; the Manual J load calculator runs your own house at your ZIP.
How many BTU are in a ton of cooling?
One ton of refrigeration is 12,000 Btu per hour, 3,516.853 W (NIST's guide to the SI, SP 811, Appendix B.9). So 2 tons is 24,000 BTU per hour and 3 tons is 36,000.
How many BTU for a 2,000 square foot house?
On DOE's zone 4A house scaled to 2,000 sq ft, at NEW YORK KENNEDY: 20,957 BTU per hour of heating and 19,691 of cooling, about 1.64 tons, from our Manual J engine. At 1,000 sq ft in zone 3A (ATLANTA HARTSFIELD-JACKSON) the same house is 14,910 BTU per hour of heating and 15,088 of cooling. Your house and your ZIP move both; the Manual J load calculator runs them.
Is BTU per square foot accurate for sizing an air conditioner?
Not on its own. A post on ACCA's HVAC Blog reports 40 Manual J load calculations in hot and mixed climates that ranged from 624 to 3,325 sq ft per ton, and says: "No matter the number, you can’t use square feet per ton to size air conditioners." The figures in this chart are Manual J loads on one stated house, so they show how far a load moves with climate; equipment is sized from a load on the actual house.
Related Calculators & Charts
Manual J Load Calculator
The same Manual J engine on your own house at your ZIP: walls, attic, floor, glass, ducts and the site declarations.
BTU / Load Calculator
A house's heating and cooling loads by ACCA Manual J at your ZIP code's weather station, with the Manual S size.
Tonnage From Model Number
Decode the tonnage of an existing condenser or air handler from its model number.
Your house, your ZIP.
The Manual J load calculator runs the same engine on your own walls, attic, floor, glass and ducts at the ASHRAE station nearest your ZIP.
Keep going