NEC 422.13 · 310.16 · 250.122
What Size Breaker for an Electric Water Heater?
The breaker, copper wire, and ground for an electric water heater by element wattage, sized at 125% per NEC 422.13. Number first, then the code behind it.
Electric Water Heater Breaker & Wire by Wattage
Residential 240V electric storage water heater: breaker and copper wire by element wattage (sized at 125% per NEC 422.13).
Swipe the table sideways to see the rest of its columns. →
| Element / nameplate | Running amps | Design (125%) | Min breaker | Copper wire, 75°C terminations | Copper wire, 60°C or NM-B | Ground (Cu) |
|---|---|---|---|---|---|---|
| 3,000Wpoint-of-use / small tank | 12.5A | 15.63A | 20A | #12 AWG | #12 AWG | #12 AWG |
| 3,800Wcompact 30-gal | 15.83A | 19.79A | 20A | #12 AWG | #12 AWG | #12 AWG |
| 4,500Wstandard 40-50 gal | 18.75A | 23.44A | 25A | #10 AWG | #10 AWG | #10 AWG |
| 5,500Whigh-recovery / 80-gal | 22.92A | 28.65A | 30A | #10 AWG | #10 AWG | #10 AWG |
Running amps = watts ÷ volts. NEC 422.13 requires the breaker and conductors for a fixed storage water heater 120 gallons or under to be rated at not less than 125% of that (the design amps). The breaker shown is the code minimum, the smallest standard overcurrent device that covers the design load; if the nameplate prints a specific maximum breaker (NEC 422.11(E)), that governs. The first copper column is the 75°C column of NEC 310.16, which holds only where the breaker and the heater's terminals are both listed and identified for 75°C conductors (NEC 110.14(C)(1)(a)(3)); the second is the 60°C column, which governs on unmarked terminations and for NM-B cable (NEC 334.80). Ground per NEC Table 250.122.
The 4500W row shows a 25A code-minimum breaker; where the nameplate's maximum allows a 30A breaker, the 10 AWG copper conductor is rated for both, so the wire does not change. On a 208V supply the same element draws more current (a 4500W element is 21.63A at 208V), so confirm the voltage before you size the circuit.
The 4500W Water Heater, Worked
- Running current: 4500W ÷ 240V = 18.75A.
- 125% (NEC 422.13): the breaker and wire for a fixed storage water heater 120 gallons or under are rated at not less than 125% of the load: 18.75A × 1.25 = 23.44A design.
- Breaker: the smallest standard overcurrent device covering 23.44A is a 25A breaker (the code minimum); a 30A breaker on 10 AWG copper also covers it.
- Conductor (NEC 310.16, 60°C): 10 AWG copper is rated 30A, which covers the 23.44A design load on either breaker.
- Ground (NEC Table 250.122): a 10 AWG copper equipment grounding conductor.
Size Your Own Water Heater Circuit
Read the wattage off the rating plate, divide by the supply voltage for the running current, and enter that as the load. NEC 422.13 sizes a fixed storage water heater 120 gallons or under at 125%, so leave the continuous option on and the calculator applies that 125%.
Sharing a circuit, or a 120V unit?
A 4500W 240V resistive tank cannot share a general-purpose 15 or 20A circuit: its 18.75A is more than the 50% NEC 210.23(B)(2) allows for equipment fastened in place there, and the manufacturer's instructions say what circuit it takes. If the goal is to avoid a new circuit, the newer 120V plug-in heat pump water heater class is the one to look at: some models are listed by their manufacturer to share a general-purpose 15 or 20A circuit (NEC 110.3(B)), within NEC 210.23(B)(2)'s cap. The heat pump water heater circuit tool answers the shared-circuit question and sizes the 240V hybrid class. Adding a water heater to a panel that may be near capacity? Check whether the panel can handle it first.
The code sections this page cites are named in the source receipt.
Frequently Asked Questions
Is the Intry Water Heater Circuit Calculator accurate and NEC compliant?
Every figure an Intry calculator computes comes from a locked source module, not hand-typed. 35,938 automated checks, one suite for the whole site rather than a per-tool count, re-derive the numbers before each deploy from the tables this site holds, read from the cited NEC section. This is our own deterministic gate, not a third-party audit. The per-tool receipt is public at https://www.intrysys.com/verified.
What size breaker do I need for an electric water heater?
A standard 40 to 50 gallon, 4500W residential electric water heater at 240V draws 18.75A. NEC 422.13 requires the breaker and conductors for a fixed storage water heater of 120 gallons or less to be rated at not less than 125 percent of its rating, 23.44A. The code minimum overcurrent device is a 25A breaker; a 30A double-pole breaker is also used where the nameplate's maximum allows it, and both use 10 AWG copper. A 5500W unit needs a 30A breaker; a 3000 to 3800W unit fits a 20A breaker on 12 AWG. The nameplate maximum breaker always governs.
What wire size for a 4500W water heater?
10 AWG copper. The 4500W element draws 18.75A, sized at 125 percent to 23.44A (NEC 422.13). 10 AWG copper is rated 30A at the 60C column (NEC 310.16), which covers the 23.44A design load on either the 25A code-minimum or a 30A breaker. Use a 10 AWG copper equipment ground (NEC Table 250.122). On 208V the same 4500W element draws more, 21.63A, so confirm the supply voltage.
Does an electric water heater need its own circuit?
A 4500W 240V storage water heater cannot share a general-purpose 15 or 20A branch circuit: its 18.75A is more than the 50% cap NEC 210.23(B)(2) sets for equipment fastened in place on those circuits. The exception is the newer 120V plug-in heat pump water heater class, some of which are listed by their manufacturer to share a 15 or 20A circuit (NEC 110.3(B)), within NEC 210.23(B)(2)'s cap. If sharing a circuit is the goal, that is the class to look at, not a resistive tank.
Why is a water heater sized at 125 percent?
Because NEC 422.13 requires the branch-circuit overcurrent device and conductors for a fixed storage water heater of 120 gallons or less to have an ampere rating of not less than 125 percent of the heater's rating. That is why an 18.75A heater is put on a circuit sized for 23.44A rather than 18.75A. It is the same reason an EV charger and other continuous loads get the 125 percent treatment.
Related Calculators
Can My Panel Handle a Tankless Water Heater?
The electric tankless is a far larger load, 45.9 to 112.5A on that page's units. The NEC 220.87 fit threshold by unit size and service.
Heat Pump Water Heater Circuit
The 240V hybrid circuit, or the 120V plug-in class that can share a general-purpose circuit under NEC 210.23(B)(2).
Wire Size for Appliances
The breaker, copper and aluminum wire, and ground for every common household appliance circuit.
Can My Panel Handle It?
Adding any big load: the NEC 220.87 and 220.83 checks, plus the no-service-upgrade workarounds.