Electrical · Feeders
Tap Conductor Calculator
The conductor for a feeder tap under NEC 240.21(B): which rule your run falls under, the ampacity floors it sets and which one governs, sized from Table 310.16. It sizes the conductor; it does not approve the install.
10 ft rule, 240.21(B)(1)
The breaker or fuse protecting the feeder you are tapping, not the tap.
The panelboard, disconnect, or breaker at the end of the tap. 240.21(B)(1)(1)b.
NEC 110.14(C): use the lowest-rated termination in the circuit. Most gear is 75°C.
Show the math
Required ampacity = the LARGEST floor 240.21(B)(1) sets
240.21(B)(1)(1)a: 60 A
240.21(B)(1)(1)b: 100 A (governs)
One-tenth floor does NOT apply: it is limited to field installations where the tap leaves the enclosure or vault (240.21(B)(1)(4)).
Table 310.16 copper 75°C: smallest size at or above 100 A is 3 AWG (100 A)
No next-standard-size rounding is applied. NEC 240.21(B) states that 240.4(B) is not permitted for tap conductors, so the tap is sized to an ampacity, never to a breaker rating.
- The tap conductors do not extend beyond the switchboard, switchgear, panelboard, disconnecting means, or control devices they supply. (NEC 240.21(B)(1)(2))
- Except at the point of connection to the feeder, the tap conductors are enclosed in a raceway running from the tap to the enclosure of the equipment they supply. (NEC 240.21(B)(1)(3))
- This circuit is rated 100 A or less (100 A), so 110.14(C)(1)(a) allows a column above 60C ONLY where the equipment is listed and identified for it. If the gear is not marked, size from the 60C column instead: the answer above can come out one trade size small. (NEC 110.14(C)(1)(a))
- Ambient temperature and conductor bundling have been checked. This result reads Table 310.16 at its base conditions (30C ambient, not more than three current-carrying conductors) and applies no correction or adjustment factor. (NEC 310.15)
Where this number comes fromIntry Verified
- Calculated from
- NEC 2023 240.21(B)(1) through (B)(5) and Table 310.16. Computed by the tap-conductor engine from NEC 2023 240.21(B) and Table 310.16: the required ampacity is the largest floor the applicable rule sets, and the conductor is the smallest size that meets it. See the full receipt ↓
- Run with
- Feeder OCPD400 A
- Tap length8 ft
- RuleNEC 240.21(B)(1)
- Required100 A
- Checked
- Every figure an Intry calculator computes comes from a locked source module, not hand-typed. 31163 automated checks, one suite for the whole site rather than a per-tool count, re-derive the numbers before each deploy from the tables this site transcribed from the cited NEC 240.21(B) tap rule and Table 310.16. This is our own deterministic gate, not a third-party audit.
- Final say
- Your AHJ has final say. This sizes the conductor; the conditions each tap rule places on the installation still have to be met on the job.
Intry Verified · NEC 2023 · Build 2731D30 · 2026-10-15
Feeder Tap Ratio Floors by Feeder OCPD
| Feeder OCPD | 25 ft: one-third | Cu | Al | 10 ft leaving the can: one-tenth | Cu |
|---|---|---|---|---|---|
| 100 A | 33.3 A | 10 AWG | 8 AWG | 10 A | 14 AWG |
| 200 A | 66.7 A | 4 AWG | 3 AWG | 20 A | 14 AWG |
| 400 A | 133.3 A | 1/0 AWG | 2/0 AWG | 40 A | 8 AWG |
| 600 A | 200 A | 3/0 AWG | 250 kcmil | 60 A | 6 AWG |
| 800 A | 266.7 A | 300 kcmil | 400 kcmil | 80 A | 4 AWG |
| 1200 A | 400 A | 600 kcmil | 900 kcmil | 120 A | 1 AWG |
Read the one-tenth column carefully. It is the smallest number in the table and it is the one people reach for first, but it is also the most conditional: it applies only to a field installation where the tap conductors leave the enclosure or vault in which the tap is made. Even then it is an additional floor, not a replacement for the load and the terminating device. A 10 ft tap off a 400 A feeder landing in a panelboard is sized to that panelboard, not to the 40 A the one-tenth column shows.
The Five Feeder Tap Rules of NEC 240.21(B)
| Rule | Max length | Ampacity floor |
|---|---|---|
| 240.21(B)(1) | 10 ft | Calculated load, and the rating of the equipment or device at the termination. One-tenth of the feeder is added only where the tap leaves the enclosure. |
| 240.21(B)(2) | 25 ft | One-third of the feeder overcurrent device rating. |
| 240.21(B)(3) | 25 ft primary plus secondary | Primary: one-third of the feeder device. Secondary: the primary-to-secondary voltage ratio times that one-third. |
| 240.21(B)(4) | 100 ft total, 25 ft horizontal | One-third of the feeder device, and never smaller than 6 AWG copper or 4 AWG aluminum. High bay buildings over 35 ft at the walls only. |
| 240.21(B)(5) | Unlimited, outside | The load, with the terminating device limiting it to the tap ampacity. Disconnect at a readily accessible location nearest the point of entrance. |
How the tap size is computed
Every tap rule sets one or more minimum ampacities. The conductor has to satisfy all of them at once, so the governing value is the largest:
Required ampacity = max(calculated load, terminating device rating, ratio floor)
The ratio floor is one-third of the feeder overcurrent device under 240.21(B)(2), (B)(3) and (B)(4), and one-tenth under 240.21(B)(1)(4) where the tap leaves the enclosure. For a transformer tap the secondary carries its own floor of (primary volts / secondary volts) times one-third of the feeder device, per 240.21(B)(3)(2). The conductor is then the smallest size in NEC Table 310.16 whose ampacity in the governing termination column reaches that number. No next-standard-size rounding is applied, because 240.21(B) states that 240.4(B) is not permitted for tap conductors.
Feeder Tap Conductor FAQs
How small can a tap conductor be off a 400 amp feeder?
Under the 25 foot tap rule, a tap off a 400 amp feeder must have an ampacity of at least 133.3 amps, which is 1/0 AWG copper or 2/0 AWG aluminum in the 75 degree C column of NEC Table 310.16. That is one-third of the feeder overcurrent device rating, per NEC 240.21(B)(2)(1). Under the 10 foot rule the answer can be smaller or larger, because that rule sizes the tap to the calculated load and to the rating of the device the tap lands in, and only adds a one-tenth-of-the-feeder floor when the tap leaves the enclosure.
What is the difference between the 10 foot and 25 foot tap rule?
The 25 foot rule (NEC 240.21(B)(2)) sets one ratio: the tap conductor must carry at least one-third of the feeder overcurrent device rating. The 10 foot rule (NEC 240.21(B)(1)) sets no such ratio in the general case. Instead it requires the tap to be at least as large as the combined calculated load and at least as large as the rating of the equipment or overcurrent device it terminates in. A one-tenth-of-the-feeder floor is added only for field installations where the tap conductors leave the enclosure or vault in which the tap is made. Sizing a 10 foot tap at one-tenth of the feeder and nothing else is a common and dangerous shortcut: one-tenth of a 400 amp feeder is 40 amps, but a tap landing in a panelboard rated well above that has to be good for the panelboard rating.
Do I need a breaker at a feeder tap?
Not at the tap point itself. That is the whole purpose of NEC 240.21(B): it permits conductors to be tapped to a feeder without overcurrent protection at the tap, provided the tap meets one of the five rules. Where the protection sits instead depends on the rule. The 25 foot rule, the high bay rule and the outside rule each require the tap to terminate in a single circuit breaker or a single set of fuses that limits the load to the ampacity of the tap conductors, so the protection sits at the end of the tap. The transformer rule places that requirement on the secondary conductors. The 10 foot rule states it differently: it does not name a single device, it requires the tap conductors to be at least as large as the rating of the equipment or overcurrent device they terminate in, and it requires that they not extend beyond the equipment they supply. If the tap does not fit any of the five rules, then you must install overcurrent protection where the conductors receive their supply.
Can a tap conductor be rounded up to the next standard breaker size?
No. NEC 240.21(B) states directly that 240.4(B) is not permitted for tap conductors. The next-standard-size rule that lets you protect a conductor at the next breaker up does not apply here. A tap is sized to an ampacity from Table 310.16, and the conductor you choose must actually meet or exceed the required ampacity rather than land near it and get rounded.
How do you size a tap that feeds a transformer?
Use NEC 240.21(B)(3). The primary conductors must carry at least one-third of the rating of the overcurrent device protecting the feeder. The secondary conductors must carry at least the primary-to-secondary voltage ratio multiplied by that same one-third. On a 480 to 208 volt transformer tapped off a 400 amp feeder, the primary floor is 133.3 amps and the secondary floor is 480 divided by 208, times 133.3, which is 307.7 amps. Dropping the voltage ratio is the single most dangerous error in this rule, because it undersizes the secondary by more than half. Those are code minimums: if the transformer actually carries more than that, the conductors have to carry the real load, and this calculator applies whichever is larger. The combined primary plus secondary length cannot exceed 25 feet, excluding any portion of the primary that is protected at its ampacity.
How long can a feeder tap be?
Ten feet under 240.21(B)(1), 25 feet under 240.21(B)(2), and 25 feet of combined primary plus secondary under the transformer rule 240.21(B)(3). Longer taps are permitted in only two situations. In a high bay manufacturing building over 35 feet high at the walls, 240.21(B)(4) allows up to 100 feet total, but no more than 25 feet of that horizontally, and the conductors must be at least 6 AWG copper or 4 AWG aluminum. Outside a building, 240.21(B)(5) allows unlimited length provided the disconnect is at a readily accessible location nearest the point of entrance. Anything else needs overcurrent protection at the supply.
Is a transformer secondary conductor the same as a feeder tap?
No, and confusing them changes the answer. A feeder tap supplying a transformer falls under 240.21(B)(3), and its ratios are taken against the overcurrent device protecting the feeder. Transformer secondary conductors fall under 240.21(C), and those ratios are taken against the overcurrent device protecting the transformer primary. Same-looking arithmetic, different reference device, different result. This calculator implements the feeder tap rules of 240.21(B) only.
Next in the feeder job
A tap sits in the middle of a distribution run. Size the load, then the feeder, then the tap, then what the tap feeds:
Sub Panel Feeder
Size the feeder and its overcurrent device before you tap it.
Wire Ampacity Chart
Check what an existing conductor carries in your conditions, from the same NEC Table 310.16 data.
Wire Size Calculator
Size a branch or feeder conductor where the tap rules do not apply.
Standard Breaker Sizes
The NEC 240.6(A) ladder for the device at the end of the tap.