Electrical · Feeders

Tap Conductor Calculator

The conductor for a feeder tap under NEC 240.21(B): which rule your run falls under, the ampacity floors it sets and which one governs, sized from Table 310.16. It sizes the conductor; it does not approve the install.

Field brief
25 ft rulea 25 ft tap off a 400 A feeder needs at least 133.3 A, which is 1/0 AWG copper at 75°C. One-third of the feeder device, NEC 240.21(B)(2)(1).1/0 AWG
10 ft rulenot one-tenth by default. The floor is the calculated load and the rating of the device the tap lands in. One-tenth applies only where the tap leaves the enclosure, 240.21(B)(1)(4).load or device
No rounding240.21(B) states 240.4(B) is not permitted for tap conductors, so a tap is sized to an ampacity and never rounded up to the next standard breaker rating.240.4(B) off

10 ft rule, 240.21(B)(1)

The breaker or fuse protecting the feeder you are tapping, not the tap.

The panelboard, disconnect, or breaker at the end of the tap. 240.21(B)(1)(1)b.

NEC 110.14(C): use the lowest-rated termination in the circuit. Most gear is 75°C.

Minimum tap conductor
3 AWG Cu
Taps Not over 3 m (10 ft) Long, NEC 240.21(B)(1)
Rule that appliesNEC 240.21(B)(1)
Required ampacity100 A
Conductor ampacity at 75°C100 A
The floors this rule sets, and which one governs
Combined calculated load on the circuits supplied by the tap (NEC 240.21(B)(1)(1)a)60 A
Rating of the equipment or overcurrent device at the tap termination (NEC 240.21(B)(1)(1)b)governs100 A
Show the math

Required ampacity = the LARGEST floor 240.21(B)(1) sets

240.21(B)(1)(1)a: 60 A

240.21(B)(1)(1)b: 100 A (governs)

One-tenth floor does NOT apply: it is limited to field installations where the tap leaves the enclosure or vault (240.21(B)(1)(4)).

Table 310.16 copper 75°C: smallest size at or above 100 A is 3 AWG (100 A)

No next-standard-size rounding is applied. NEC 240.21(B) states that 240.4(B) is not permitted for tap conductors, so the tap is sized to an ampacity, never to a breaker rating.

Conditions this calculator cannot check for you
  • The tap conductors do not extend beyond the switchboard, switchgear, panelboard, disconnecting means, or control devices they supply. (NEC 240.21(B)(1)(2))
  • Except at the point of connection to the feeder, the tap conductors are enclosed in a raceway running from the tap to the enclosure of the equipment they supply. (NEC 240.21(B)(1)(3))
  • This circuit is rated 100 A or less (100 A), so 110.14(C)(1)(a) allows a column above 60C ONLY where the equipment is listed and identified for it. If the gear is not marked, size from the 60C column instead: the answer above can come out one trade size small. (NEC 110.14(C)(1)(a))
  • Ambient temperature and conductor bundling have been checked. This result reads Table 310.16 at its base conditions (30C ambient, not more than three current-carrying conductors) and applies no correction or adjustment factor. (NEC 310.15)
Where this number comes fromIntry Verified
Calculated from
NEC 2023 240.21(B)(1) through (B)(5) and Table 310.16. Computed by the tap-conductor engine from NEC 2023 240.21(B) and Table 310.16: the required ampacity is the largest floor the applicable rule sets, and the conductor is the smallest size that meets it. See the full receipt ↓
Run with
  • Feeder OCPD400 A
  • Tap length8 ft
  • RuleNEC 240.21(B)(1)
  • Required100 A
Checked
Every figure an Intry calculator computes comes from a locked source module, not hand-typed. 31163 automated checks, one suite for the whole site rather than a per-tool count, re-derive the numbers before each deploy from the tables this site transcribed from the cited NEC 240.21(B) tap rule and Table 310.16. This is our own deterministic gate, not a third-party audit.
Final say
Your AHJ has final say. This sizes the conductor; the conditions each tap rule places on the installation still have to be met on the job.
What Intry Verified means

Intry Verified · NEC 2023 · Build 2731D30 · 2026-10-15

This sizes the conductor. It does not approve the tap. A feeder tap is legal only when every condition of its rule is met, and several of them are physical facts about your install that no calculator can see: how the conductors are protected, whether they leave the enclosure, whether the run is continuous, who services the equipment. Work the checklist above against the job, and confirm the result with your AHJ. This tool covers feeder taps under 240.21(B). Transformer secondary conductors are a different rule, 240.21(C), and take their ratios from the device protecting the transformer primary instead of the feeder.
100 A required, 75°C terminations3 AWG Cu

Feeder Tap Ratio Floors by Feeder OCPD

NEC 240.21(B) ratio floors only, with the conductor from NEC Table 310.16 at 75°C. These are the code ratios, not the final answer: the governing size is the largest of the ratio floor, the calculated load, and the rating of the device the tap terminates in.
Feeder OCPD25 ft: one-thirdCuAl10 ft leaving the can: one-tenthCu
100 A33.3 A10 AWG8 AWG10 A14 AWG
200 A66.7 A4 AWG3 AWG20 A14 AWG
400 A133.3 A1/0 AWG2/0 AWG40 A8 AWG
600 A200 A3/0 AWG250 kcmil60 A6 AWG
800 A266.7 A300 kcmil400 kcmil80 A4 AWG
1200 A400 A600 kcmil900 kcmil120 A1 AWG

Read the one-tenth column carefully. It is the smallest number in the table and it is the one people reach for first, but it is also the most conditional: it applies only to a field installation where the tap conductors leave the enclosure or vault in which the tap is made. Even then it is an additional floor, not a replacement for the load and the terminating device. A 10 ft tap off a 400 A feeder landing in a panelboard is sized to that panelboard, not to the 40 A the one-tenth column shows.


The Five Feeder Tap Rules of NEC 240.21(B)

NEC 2023 Article 240, Part II, 240.21(B)(1) through (B)(5).
RuleMax lengthAmpacity floor
240.21(B)(1)10 ftCalculated load, and the rating of the equipment or device at the termination. One-tenth of the feeder is added only where the tap leaves the enclosure.
240.21(B)(2)25 ftOne-third of the feeder overcurrent device rating.
240.21(B)(3)25 ft primary plus secondaryPrimary: one-third of the feeder device. Secondary: the primary-to-secondary voltage ratio times that one-third.
240.21(B)(4)100 ft total, 25 ft horizontalOne-third of the feeder device, and never smaller than 6 AWG copper or 4 AWG aluminum. High bay buildings over 35 ft at the walls only.
240.21(B)(5)Unlimited, outsideThe load, with the terminating device limiting it to the tap ampacity. Disconnect at a readily accessible location nearest the point of entrance.

How the tap size is computed

Every tap rule sets one or more minimum ampacities. The conductor has to satisfy all of them at once, so the governing value is the largest:

Required ampacity = max(calculated load, terminating device rating, ratio floor)

The ratio floor is one-third of the feeder overcurrent device under 240.21(B)(2), (B)(3) and (B)(4), and one-tenth under 240.21(B)(1)(4) where the tap leaves the enclosure. For a transformer tap the secondary carries its own floor of (primary volts / secondary volts) times one-third of the feeder device, per 240.21(B)(3)(2). The conductor is then the smallest size in NEC Table 310.16 whose ampacity in the governing termination column reaches that number. No next-standard-size rounding is applied, because 240.21(B) states that 240.4(B) is not permitted for tap conductors.


Feeder Tap Conductor FAQs

How small can a tap conductor be off a 400 amp feeder?

Under the 25 foot tap rule, a tap off a 400 amp feeder must have an ampacity of at least 133.3 amps, which is 1/0 AWG copper or 2/0 AWG aluminum in the 75 degree C column of NEC Table 310.16. That is one-third of the feeder overcurrent device rating, per NEC 240.21(B)(2)(1). Under the 10 foot rule the answer can be smaller or larger, because that rule sizes the tap to the calculated load and to the rating of the device the tap lands in, and only adds a one-tenth-of-the-feeder floor when the tap leaves the enclosure.

What is the difference between the 10 foot and 25 foot tap rule?

The 25 foot rule (NEC 240.21(B)(2)) sets one ratio: the tap conductor must carry at least one-third of the feeder overcurrent device rating. The 10 foot rule (NEC 240.21(B)(1)) sets no such ratio in the general case. Instead it requires the tap to be at least as large as the combined calculated load and at least as large as the rating of the equipment or overcurrent device it terminates in. A one-tenth-of-the-feeder floor is added only for field installations where the tap conductors leave the enclosure or vault in which the tap is made. Sizing a 10 foot tap at one-tenth of the feeder and nothing else is a common and dangerous shortcut: one-tenth of a 400 amp feeder is 40 amps, but a tap landing in a panelboard rated well above that has to be good for the panelboard rating.

Do I need a breaker at a feeder tap?

Not at the tap point itself. That is the whole purpose of NEC 240.21(B): it permits conductors to be tapped to a feeder without overcurrent protection at the tap, provided the tap meets one of the five rules. Where the protection sits instead depends on the rule. The 25 foot rule, the high bay rule and the outside rule each require the tap to terminate in a single circuit breaker or a single set of fuses that limits the load to the ampacity of the tap conductors, so the protection sits at the end of the tap. The transformer rule places that requirement on the secondary conductors. The 10 foot rule states it differently: it does not name a single device, it requires the tap conductors to be at least as large as the rating of the equipment or overcurrent device they terminate in, and it requires that they not extend beyond the equipment they supply. If the tap does not fit any of the five rules, then you must install overcurrent protection where the conductors receive their supply.

Can a tap conductor be rounded up to the next standard breaker size?

No. NEC 240.21(B) states directly that 240.4(B) is not permitted for tap conductors. The next-standard-size rule that lets you protect a conductor at the next breaker up does not apply here. A tap is sized to an ampacity from Table 310.16, and the conductor you choose must actually meet or exceed the required ampacity rather than land near it and get rounded.

How do you size a tap that feeds a transformer?

Use NEC 240.21(B)(3). The primary conductors must carry at least one-third of the rating of the overcurrent device protecting the feeder. The secondary conductors must carry at least the primary-to-secondary voltage ratio multiplied by that same one-third. On a 480 to 208 volt transformer tapped off a 400 amp feeder, the primary floor is 133.3 amps and the secondary floor is 480 divided by 208, times 133.3, which is 307.7 amps. Dropping the voltage ratio is the single most dangerous error in this rule, because it undersizes the secondary by more than half. Those are code minimums: if the transformer actually carries more than that, the conductors have to carry the real load, and this calculator applies whichever is larger. The combined primary plus secondary length cannot exceed 25 feet, excluding any portion of the primary that is protected at its ampacity.

How long can a feeder tap be?

Ten feet under 240.21(B)(1), 25 feet under 240.21(B)(2), and 25 feet of combined primary plus secondary under the transformer rule 240.21(B)(3). Longer taps are permitted in only two situations. In a high bay manufacturing building over 35 feet high at the walls, 240.21(B)(4) allows up to 100 feet total, but no more than 25 feet of that horizontally, and the conductors must be at least 6 AWG copper or 4 AWG aluminum. Outside a building, 240.21(B)(5) allows unlimited length provided the disconnect is at a readily accessible location nearest the point of entrance. Anything else needs overcurrent protection at the supply.

Is a transformer secondary conductor the same as a feeder tap?

No, and confusing them changes the answer. A feeder tap supplying a transformer falls under 240.21(B)(3), and its ratios are taken against the overcurrent device protecting the feeder. Transformer secondary conductors fall under 240.21(C), and those ratios are taken against the overcurrent device protecting the transformer primary. Same-looking arithmetic, different reference device, different result. This calculator implements the feeder tap rules of 240.21(B) only.


Next in the feeder job

A tap sits in the middle of a distribution run. Size the load, then the feeder, then the tap, then what the tap feeds: