NEC Wire Sizing
What Size Wire for an Electric Range?
The breaker, copper and aluminum wire, and ground for the electric range circuit this page shows, with the NEC basis and the nameplate caveats that actually decide it.
Electric Range Circuit Spec
Branch circuit shown for an electric range (NEC 220.55, 210.19(C), GFCI per NEC 210.8(D))
Swipe the table sideways to see the rest of its columns. →
| Voltage | 240V |
| Breaker | 50A GFCI |
| Copper wire | #6 |
| Copper (75°C conduit) | #8 |
| Aluminum wire (75°C-marked terminations, SER or conduit) | #6 |
| Equipment ground (Cu) | #10 |
The NEC minimum for a freestanding range (also called an electric stove) up to 12 kW is a 40A / #8 copper circuit: NEC 210.19(C) sets a 40A floor and Table 220.55 gives an 8 kW demand. This page shows the 50A / #6 copper circuit, which adds headroom and takes a NEMA 14-50. Ranges over 12 kW are sized up to the nameplate. On a 240V circuit, a 2-pole GFCI breaker is one way to provide GFCI protection. GFCI: NEC 2023 210.8(D) requires GFCI protection for the branch circuit or outlet supplying an electric range (210.8(D)(8) "Electric ranges") rated 150 volts or less to ground and 60 amperes or less, hardwired or plugged in, wherever it is installed; which edition applies is the one your jurisdiction has adopted. Wire sized at NEC Table 310.16 (copper lead at the 60°C column for NM-B); ground per NEC Table 250.122. The appliance nameplate lists the exact minimum circuit and maximum breaker; it governs over the circuit shown here.
Maker's instruction: GE JB645DKWW electric range, Quick Specs, read 2026-11-13.
Aluminum branch conductors are 75°C-rated AA-8000 alloy (SER cable, or XHHW-2 / THWN-2 in conduit); there is no 60°C aluminum NM-B, so the aluminum row uses the 75°C column. Where the terminations are rated 60°C only, size aluminum from the 60°C column instead (#4 here). Aluminum: the terminals it lands on must be identified for aluminum conductors (NEC 2023, 110.14(A)).
Adding this as a new load? Check whether your panel can handle it (the NEC 220.87 service check), or compare it against the breaker size by load chart.
Size Your Exact Circuit
It opens on this page's 50 A circuit at the 60°C column. For a nameplate that differs from this page's circuit, enter your exact load and conditions. For a long run, the result links to the voltage drop calculator, which checks that wire over your run; this tool does not size for voltage drop.
The code sections this page cites are named in the source receipt.
Frequently Asked Questions
What size wire do I need for an electric range?
This page shows an electric range on a 50A / 240V circuit, which calls for #6 copper (or #4 aluminum; #6 aluminum only on 75°C-marked terminations; aluminum on terminals identified for aluminum, NEC 2023, 110.14(A)) conductors and a #10 copper equipment ground per NEC Table 250.122. That is the 60C column, the NEC default for NM-B cable and terminations 100A and under; on 75C-rated terminals in conduit you may use #8 copper. GE's quick specs for the JB645DKWW freestanding range list "KW RATING 240V 12.1" and "BREAKER SIZE 240V 40 Amps", with the note "Check local codes for required breaker size." The NEC minimum for a freestanding range (also called an electric stove) up to 12 kW is a 40A / #8 copper circuit: NEC 210.19(C) sets a 40A floor and Table 220.55 gives an 8 kW demand. This page shows the 50A / #6 copper circuit, which adds headroom and takes a NEMA 14-50. Ranges over 12 kW are sized up to the nameplate. On a 240V circuit, a 2-pole GFCI breaker is one way to provide GFCI protection. GFCI: NEC 2023 210.8(D) requires GFCI protection for the branch circuit or outlet supplying an electric range (210.8(D)(8) "Electric ranges") rated 150 volts or less to ground and 60 amperes or less, hardwired or plugged in, wherever it is installed; which edition applies is the one your jurisdiction has adopted.
What size breaker for an electric range?
A 50A double-pole (240V) breaker. The #6 copper conductors are matched to that 50A rating, and it must be a GFCI breaker (or GFCI protection ahead of the appliance). Do not oversize the breaker to a wire it does not protect: the breaker and the conductor go up together. Always confirm against the appliance nameplate, which lists the exact minimum circuit and maximum overcurrent device.
Does an electric range need GFCI protection?
Yes. GFCI: NEC 2023 210.8(D) requires GFCI protection for the branch circuit or outlet supplying an electric range (210.8(D)(8) "Electric ranges") rated 150 volts or less to ground and 60 amperes or less, hardwired or plugged in, wherever it is installed; which edition applies is the one your jurisdiction has adopted. Use a GFCI breaker or a GFCI device ahead of it.
Can I use aluminum wire for an electric range?
Yes. On the 75C column (the column this page reads for aluminum), a 50A circuit needs #6 aluminum, versus #8 copper. Aluminum: the terminals it lands on must be identified for aluminum conductors (NEC 2023, 110.14(A)). If you run aluminum, apply antioxidant to the terminations, torque to the listed spec, and remember aluminum drops slightly more voltage on long runs.
What size breaker for a stove?
Same answer: stove is another name for an electric range. It uses a 50A / 240V circuit with #6 copper wire and a #10 copper ground. The NEC minimum for a freestanding range (also called an electric stove) up to 12 kW is a 40A / #8 copper circuit: NEC 210.19(C) sets a 40A floor and Table 220.55 gives an 8 kW demand. This page shows the 50A / #6 copper circuit, which adds headroom and takes a NEMA 14-50. Ranges over 12 kW are sized up to the nameplate. On a 240V circuit, a 2-pole GFCI breaker is one way to provide GFCI protection. GFCI: NEC 2023 210.8(D) requires GFCI protection for the branch circuit or outlet supplying an electric range (210.8(D)(8) "Electric ranges") rated 150 volts or less to ground and 60 amperes or less, hardwired or plugged in, wherever it is installed; which edition applies is the one your jurisdiction has adopted.
Wire Size for Other Appliances
Electric Dryer
#10 copper on a 30A / 240V circuit.
Electric Wall Oven
#8 copper on a 40A / 240V circuit.
Electric Cooktop
#8 copper on a 40A / 240V circuit.
Electric Water Heater
#10 copper on a 30A / 240V circuit.
Hot Tub
#6 copper on a 50A / 240V circuit.
Dishwasher
#12 copper on a 20A / 120V circuit.
Garbage Disposal
#14 copper on a 15A / 120V circuit.
Built-In Microwave
#12 copper on a 20A / 120V circuit.
Refrigerator
#12 copper on a 20A / 120V circuit.
Freezer
#12 copper on a 20A / 120V circuit.
Garage Door Opener
#12 copper on a 20A / 120V circuit.
Wire Size Calculator
Full NEC 310.16 sizing for any load, distance, and conditions.