NEC Wire Sizing

What Size Wire for an Electric Range?

The breaker, copper and aluminum wire, and ground for a typical electric range circuit, with the NEC basis and the nameplate caveats that actually decide it.

Quick answer: An electric range typically needs a 50A / 240V circuit with #6 copper (or #6 aluminum) wire and a #10 copper ground. On 75°C terminals in conduit, #8 copper is permitted.

Electric Range Circuit Spec

Typical branch circuit for an electric range (NEC 220.55, 210.19(C))
Voltage240V
Breaker50A
Copper wire#6
Copper (75°C conduit)#8
Aluminum wire (75°C, SER or conduit)#6
Equipment ground (Cu)#10

The NEC minimum for a freestanding range (also called an electric stove) up to 12 kW is a 40A / #8 copper circuit: NEC 210.19(C) sets a 40A floor and Table 220.55 gives an 8 kW demand. In practice it is most commonly installed on the 50A / #6 copper circuit shown here, which adds headroom and takes a NEMA 14-50. Ranges over 12 kW are sized up to the nameplate. Under the 2023 NEC (210.8(A)), a dwelling range receptacle also requires GFCI protection (a 2-pole GFCI breaker); this is a 2023 expansion still being adopted and is contested for 240V appliances, so verify your local edition. Wire sized at NEC Table 310.16 (copper lead at the 60°C column for NM-B); ground per NEC Table 250.122. The appliance nameplate lists the exact minimum circuit and maximum breaker; it always governs over a typical value.

Aluminum branch conductors are 75°C-rated AA-8000 alloy (SER cable, or XHHW-2 / THWN-2 in conduit); there is no 60°C aluminum NM-B, so the aluminum row uses the 75°C column. Where the terminations are rated 60°C only, size aluminum from the 60°C column instead (#4 here).

Adding this as a new load? Check whether your panel can handle it (the NEC 220.87 service check), or compare it against the breaker size by load chart.


Long Run? Size It Exactly

For a long run where voltage drop matters, or a nameplate that differs from the typical value, enter your exact load, distance, and conditions.

Loading calculator...

Frequently Asked Questions

What size wire do I need for an electric range?

An electric range typically uses a 50A / 240V circuit, which calls for #6 copper (or #6 aluminum) conductors and a #10 copper equipment ground per NEC Table 250.122. That is the 60C column, the NEC default for NM-B cable and terminations 100A and under; on 75C-rated terminals in conduit you may use #8 copper. The NEC minimum for a freestanding range (also called an electric stove) up to 12 kW is a 40A / #8 copper circuit: NEC 210.19(C) sets a 40A floor and Table 220.55 gives an 8 kW demand. In practice it is most commonly installed on the 50A / #6 copper circuit shown here, which adds headroom and takes a NEMA 14-50. Ranges over 12 kW are sized up to the nameplate. Under the 2023 NEC (210.8(A)), a dwelling range receptacle also requires GFCI protection (a 2-pole GFCI breaker); this is a 2023 expansion still being adopted and is contested for 240V appliances, so verify your local edition.

What size breaker for an electric range?

A 50A double-pole (240V) breaker. The #6 copper conductors are matched to that 50A rating. Do not oversize the breaker to a wire it does not protect: the breaker and the conductor go up together. Always confirm against the appliance nameplate, which lists the exact minimum circuit and maximum overcurrent device.

Can I use aluminum wire for an electric range?

Yes. On the 75C column (the usual basis for aluminum), a 50A circuit needs #6 aluminum, versus #8 copper. Aluminum is common on larger circuits and services to save cost; apply antioxidant to the terminations, torque to the listed spec, and remember aluminum drops slightly more voltage on long runs.

What size breaker for a stove?

Same answer: stove is another name for an electric range. It uses a 50A / 240V circuit with #6 copper wire and a #10 copper ground. The NEC minimum for a freestanding range (also called an electric stove) up to 12 kW is a 40A / #8 copper circuit: NEC 210.19(C) sets a 40A floor and Table 220.55 gives an 8 kW demand. In practice it is most commonly installed on the 50A / #6 copper circuit shown here, which adds headroom and takes a NEMA 14-50. Ranges over 12 kW are sized up to the nameplate. Under the 2023 NEC (210.8(A)), a dwelling range receptacle also requires GFCI protection (a 2-pole GFCI breaker); this is a 2023 expansion still being adopted and is contested for 240V appliances, so verify your local edition.


Wire Size for Other Appliances