NEC 250.122

Ground Wire Size Calculator

The breaker gives you the ground wire from Table 250.122. Then NEC 250.122(B) makes it bigger when the conductors in the pipe are larger than the circuit actually needs, for any reason other than the 310.15(B) or (C) corrections. This works out both, and tells you which one you are looking at.

NEC Table 250.122 is keyed on the DEVICE. Not on the load, and not on the conductor beside it.

The size in the pipe, whoever put it there and whatever their reason. If it is larger than this circuit needs, 250.122(B) is live and this is the field that fires it.

Leave it unticked for a single appliance, a feeder or a sub-panel. It decides whether NEC 240.4(B) lets the device sit on the next standard size above the conductor’s ampacity, which sets the smallest conductor this device may protect.

The conditions that set the minimum (ambient, conductor count, terminations)

These four set the MINIMUM conductor this circuit requires, which is what the increase is measured from. That is also how the code’s own exclusion is honoured: 250.122(B) does not count an increase required by 310.15(B) or 310.15(C), and a conductor upsized purely for heat or conduit fill lands on this minimum, so no increase is left to scale.

How the minimum is chosen. NEC 310.15(B)(1) permits two ways to correct for ambient: the banded Table 310.15(B)(1)(1), and the equation computed at your actual temperature. The minimum this tool prints is the smaller conductor either method allows, because the code permits both, and it says which method set it. So a conductor you sized off the other method can read as an increase: 250.122(B) then scales the ground for it, which can only make the ground larger, never smaller than the code requires.

20 A device, #12 AWG copper in the pipe
TABLE 250.122 MINIMUM STANDS
#12 AWG
copper equipment grounding conductor to pull
#12 AWG
Table 250.122 prints
#12 AWG
minimum this circuit needs
1.00x
the circular mils

Table 250.122 prints #12 AWG at a 20 A device, and here that is the answer. #12 AWG copper is the minimum this circuit needs in these conditions, so nothing was increased and 250.122(B) never engages.

Check the conduit fill → Conduit fill counts every conductor in the pipe, neutrals included, and this #12 AWG ground wire (NEC Chapter 9, Table 1 and Note 3). This tool does not see the pull: enter them in the conduit fill calculator.

Show the math
  1. GIVENThe overcurrent device ahead of the circuit: 20 A
  2. GIVENThe ungrounded conductors in the pipe: #12 AWG copper
  3. TABLETable 250.122 at a 20 A device, copper column: #12 AWG (6,530 cmil, Chapter 9 Table 8)NEC Table 250.122
  4. TABLEThe smallest copper conductor the 20 A device may protect at 86°F with 1-3 current-carrying conductors, 75°C insulation and 75°C terminations: #12 AWG (6,530 cmil)NEC 240.4, Table 310.16, 310.15(B), 310.15(C)(1)
  5. MATH#12 AWG 6,530 cmil / #12 AWG 6,530 cmil = 1.0000NEC 250.122(B)
  6. MATH#12 AWG 6,530 cmil × 1.0000 = 6,530 cmilNEC 250.122(B)
  7. ROUNDThe smallest printed size at or above 6,530 cmil: #12 AWGNEC Chapter 9 Table 8, 250.122(A)
  8. RESULTGround wire to pull: #12 AWG copperNEC Table 250.122

The circular mils are the printed cells of NEC Chapter 9 Table 8, never the AWG geometric series. What the code does not say. 250.122(B) requires the increase to be proportionate to “the increase in circular mil area of the ungrounded conductors” but never defines what the increase is measured FROM. This tool measures it from the smallest conductor the device may protect in the conditions above (NEC 240.4, with 240.4(B)’s next size up unless the box above says the circuit feeds more than one receptacle for portable loads), and for a load above that conductor’s ampacity, from the smallest conductor that carries the load (printed as load bands when that happens). That is the only baseline that makes the rule computable and it is how the rule is applied in the field, but it is our reading of an undefined term rather than something printed in the code, which is why the baseline is on screen where you can check it.

Where this number comes fromIntry Verified
Calculated from
NEC Table 250.122 with 250.122(A) and 250.122(B), circular mils from NEC Chapter 9 Table 8, minimum conductor from Table 310.16 with Table 310.15(B)(1)(1) or Equation 310.15(B)(1), whichever allows the smaller, and Table 310.15(C)(1), protected under NEC 240.4(B) and 240.4(D). Computed from NEC Table 250.122 at the overcurrent device, with the 250.122(B) proportional increase taken against the printed NEC Chapter 9 Table 8 circular mils and held between the 250.122(A) table floor and the circuit-conductor ceiling. See the full receipt ↓
Run with
  • Device20 A
  • Ungrounded conductor#12 AWG copper, 75°C
  • Ground wire materialcopper
  • Ambient86°F (30.0°C)
  • Current-carrying conductors1-3 (1.00)
  • Terminations75°C
  • More than one receptacle for portable loadsno
  • Minimum for this circuit#12 AWG
Checked
Every figure an Intry calculator computes comes from a locked source module, not hand-typed. 35,938 automated checks, one suite for the whole site rather than a per-tool count, re-derive the numbers before each deploy from the tables this site holds, read from the cited NEC section. This is our own deterministic gate, not a third-party audit.
Final say
Your AHJ and local amendments have final say. Confirm before rough-in.
What Intry Verified means

Intry Verified · NEC 2023 · Build 525536D · 2026-11-13

Standard devices from 15 A to 400 A with #12 AWG copper in the pipe, at 86°F with 1-3 current-carrying conductors and 75°C terminations. The picker above goes to 1200 A; this table stops at 400 A, where branch and feeder work ends. A dash in the last two columns means one of two different things, and the Minimum conductor column says which: if it names a size, your conductors are smaller than the smallest that device may protect, so there is no increase to scale. If it is dashed too, nothing in Table 310.16 carries that device in these conditions at all. The minimum conductor is the smallest the device may protect (NEC 240.4, including 240.4(B)'s next size up). Where that conductor carries less than the device, it is the minimum only for a load within its own ampacity, counting the noncontinuous load plus 125 percent of the continuous load (NEC 210.19(A)(1) for a branch circuit, 215.2(A)(1) for a feeder); a larger load needs a larger conductor, and the ground wire in the last column is measured from that smallest conductor, which gives the largest answer.

Swipe the table sideways to see the rest of its columns. →

DeviceTable 250.122Minimum conductorIncreaseGround wire to pull
15 A#14 AWG#14 AWG1.59x#12 AWG
20 A#12 AWG#12 AWG1.00x#12 AWG
25 A#10 AWG#10 AWG––
30 A#10 AWG#10 AWG––
35 A#10 AWG#8 AWG––
40 A#10 AWG#8 AWG––
45 A#10 AWG#8 AWG––
50 A#10 AWG#8 AWG––
60 A#10 AWG#6 AWG––
70 A#8 AWG#6 AWG––
80 A#8 AWG#4 AWG––
90 A#8 AWG#4 AWG––
100 A#8 AWG#3 AWG––
110 A#6 AWG#2 AWG––
125 A#6 AWG#2 AWG––
150 A#6 AWG#1 AWG––
175 A#6 AWG2/0 AWG––
200 A#6 AWG3/0 AWG––
225 A#4 AWG4/0 AWG––
250 A#4 AWG4/0 AWG––
300 A#4 AWG250 kcmil––
350 A#3 AWG350 kcmil––
400 A#3 AWG500 kcmil––

The last column is the one a printed table cannot carry: it depends on the conductor in your pipe, the ambient and the conductor count, none of which the code book knows. Rows in red are where 250.122(B) takes the grounding conductor above what Table 250.122 prints.

This is not the grounding electrode conductor. Table 250.122 sizes the EQUIPMENT grounding conductor, the one pulled with the circuit, from the overcurrent device. The grounding ELECTRODE conductor that goes to your ground rod or your rebar is Table 250.66, sized from the service-entrance conductors, and 250.66(A) caps it at #6 copper where it runs to a rod. Sizing either one from the other’s table is the mistake this paragraph exists to stop.

250.122(B) carries an exception this tool does not apply for you: a qualified person is permitted to size the grounding conductor to provide an effective ground-fault current path under 250.4(A)(5) or (B)(4) instead of by this proportion. That is an engineered judgement rather than arithmetic, so the tool gives you the proportional answer and names the exception rather than quietly assuming it.

20 A, #12 AWG Cu#12 AWG Cu ground

Intry Verified. The ground wire sizes the calculator on this page returns are computed from NEC Table 250.122 with 250.122(A) and 250.122(B), against the circular mils printed in NEC Chapter 9 Table 8 (NFPA 70-2023). Figures quoted in the FAQ and the surrounding copy are read from the same printed tables rather than computed. Confirm the edition your jurisdiction has adopted; the authority having jurisdiction has final say. Those figures are computed by a locked engine straight from the source it cites, not hand-typed, and that computation re-runs inside a deterministic test on every deploy. Source-checked. Locked. This is our own deterministic gate, not a third-party audit. What Intry Verified means


The Rule Everyone Knows, and the One They Miss

The first half is simple: read NEC Table 250.122 across from the rating of the overcurrent device protecting the circuit. A 50A breaker on #6 copper, where #6 is the smallest conductor the circuit needs, takes #10 copper, because the equipment grounding conductor tracks the breaker rather than the phase conductors. That is the part a chart by breaker alone prints.

The second half is NEC 250.122(B), and it is where the red tags come from. If the ungrounded conductors are increased in size for any reason other than the corrections required by 310.15(B) or 310.15(C), the grounding conductor has to be increased in the same proportion by circular mil area. It is ratio arithmetic against a table you may not have open, on a conductor that is easy to overlook, and it is invisible the moment the cover goes on.

One reason it is missed is that it does not only bite on a deliberate design upsize. It bites when the wire in the pipe is bigger than the circuit needs for any reason but the 310.15(B) or (C) corrections, which on an existing installation is the ordinary state of the world.


Worked Example

100A sub-panel feeder, conductors upsized for a long run

A 100A feeder needs #3 copper at the table’s own conditions on 75°C-marked terminations (at 60°C or on NM-B cable it is #2 copper, and only for a load of 95A or less, by 240.4(B)), and Table 250.122 prints #8 copper for the ground. Run it as designed and #8 is the whole answer.

1/0 = 105,600 cmil / #3 = 52,620 cmil = 2.01x

#8 = 16,510 cmil x 2.01 = 33,133 cmil

Now upsize the feeder to 1/0 for voltage drop. That is 2.01 times the circular mils the circuit needed, so the ground wire goes up by the same factor. The next printed size at or above 33,133 circular mils is #4 copper, per NEC 250.122(B). Two sizes up from what the table alone would have told you.


Frequently Asked Questions

What size ground wire do I need for a 100 amp breaker?

The equipment grounding conductor for a 100A circuit is #8 copper per NEC Table 250.122. In aluminum the EGC is #6 (aluminum on terminals identified for aluminum, NEC 2023, 110.14(A)). The EGC is sized from the rating of the overcurrent device protecting the circuit, not from the load. But read the next question before you pull it: if the ungrounded conductors are larger than the circuit needs, NEC 250.122(B) makes the answer larger than #8.

What size ground wire for a 50 amp breaker?

The EGC for a 50A breaker is #10 copper. NEC Table 250.122 lists 60A at #10, and any rating up to that row (30A, 40A, 50A) uses the same #10 copper. In aluminum it is #8 (aluminum on terminals identified for aluminum, NEC 2023, 110.14(A)).

What size ground wire for a 20 amp circuit?

The EGC for a 20A circuit is #12 copper per NEC 250.122, which is why 12-2 nonmetallic cable includes a #12 or bare equivalent ground. A 15A circuit uses #14 copper.

Does the ground wire size depend on the breaker or the wire size?

Both, and the second half is the part that gets missed. The EGC starts from the overcurrent device rating per NEC Table 250.122. Then NEC 250.122(B) says that if the ungrounded conductors are increased in size for any reason other than the corrections required by 310.15(B) or 310.15(C), the equipment grounding conductor is increased in size proportionately to the increase in circular mil area. So a #12 EGC on a 20A circuit becomes a much larger conductor if somebody ran #2 for that circuit. The calculator on this page computes that ratio for you.

Does 250.122(B) apply if the conductors were already oversized when I got there?

On the text as printed, yes. 250.122(B) reads "if ungrounded conductors are increased in size for any reason other than as required in 310.15(B) or 310.15(C)". It names no actor and no point in time: it does not say increased by the designer, or increased during this job. What it does not define is what the increase is measured FROM, and that is a genuine gap in the code text rather than something we can look up. This tool measures it from the smallest conductor the device may protect in the conditions you enter (NEC 240.4, including 240.4(B)'s next size up where the circuit qualifies) and, for a load above that conductor's ampacity, from the smallest conductor that carries the load, counting the noncontinuous load plus 125 percent of the continuous load (NEC 210.19(A)(1), 215.2(A)(1)); the calculator prints the answer for each load band. Under heat or bundling each band's ground wire is measured from the smallest conductor the code allows for any load in the band however it splits between continuous and noncontinuous (210.19(A)(1) and 215.2(A)(1) compare the 125 percent figure with the ampacity before the correction and adjustment factors, 210.19(A)(2) and 215.2(A)(2) the load itself with the ampacity after them), so it is never smaller than the code requires. That is the only baseline that makes the rule computable and is how it is applied in the field. That baseline is printed on screen so you can check it, and your AHJ has the final say on the reading.

If I upsized the wire because of heat or conduit fill, does the ground go up too?

No, and the code is explicit about it. 250.122(B) excludes increases required by 310.15(B), the ambient temperature correction, and 310.15(C), the adjustment for more than three current-carrying conductors. A conductor that is bigger only because of heat or bundling is not "increased in size" for the purposes of this rule. The calculator handles this without asking you to declare a reason: the minimum it measures against already has the correction and adjustment applied, so a heat-driven upsize lands exactly on that minimum and produces no increase.

Is the equipment grounding conductor the same as the grounding electrode conductor?

No. The equipment grounding conductor (EGC) bonds equipment back to the source and is sized by NEC 250.122 from the breaker rating. The grounding electrode conductor (GEC) connects the system to earth (ground rod, water pipe, Ufer) and is sized by NEC 250.66 from the service conductor size, with 250.66(A) capping the run to a rod at #6 copper. They are different conductors with different tables, and sizing one from the other's table is a serious mistake.

Can the ground wire ever need to be bigger than the circuit conductors?

No. NEC 250.122(A) says the equipment grounding conductor is not required to be larger than the circuit conductors supplying the equipment, so the proportional increase is capped there. The calculator applies that cap and tells you when it fired.


Related Calculators

Upsizing for drop is what pulls the ground up with it.

Work out the drop on the run first. If it forces a larger conductor, bring that size back here and this will tell you what the ground wire becomes.