Code Reference

NEC 2026 Changes: What Changed From NEC 2023

The 2026 National Electrical Code changes that matter in the field, each read from both books, NFPA 70’s 2023 and 2026 editions, by section and printed page: what the 2023 code said, what the 2026 code says, and why it matters on the job.

Quick answer: The 2026 NEC moves load calculations from Article 220 to a new Article 120, cuts the dwelling lighting load from 3 VA to 2 VA per square foot, drops the optional-method 100 percent tier from 10 kVA to 8 kVA, counts EV chargers in that method at 100 percent of their 120.57 load, and drops the 7,200 VA EVSE minimum. Outdoor dwelling GFCI under 210.8(F) reaches circuits of 60 A or less, and nonlocking 30, 50, and 60 A receptacles used for EV charging must be listed for EVSE and WPTE use per 625.44.

Read from NFPA 70, 2023 edition, and NFPA 70, 2026 edition (issued August 20, 2025, effective September 9, 2025), each change by section and page, in our own words with short quotes where the words decide the rule. Your adopted edition and your AHJ govern.

NEC 2023 to 2026 Changes at a Glance

NEC 2023-to-2026 changes by section, each read from NFPA 70, 2023 and 2026 editions. The printed pages are on each change below and in the code index at the foot of the page. Your adopted edition and AHJ govern.

Swipe the table sideways to see the rest of its columns. →

2026 section (was 2023)What changed
Article 120 (was Article 220)Load calculations move from Article 220 to Article 120
120.41 and 120.82(B) (was 220.41 and 220.82(B))Dwelling general lighting load: 3 VA to 2 VA per square foot
120.82(B) (was 220.82(B))Optional method: the 100 percent first tier drops from 10 kVA to 8 kVA
120.82(D) (new)EV chargers enter the optional method at 100 percent of their 120.57 load
120.5(E) (new)Load calculations need not take continuous loads at 125 percent
120.7 (new)Power control systems in load calculations
Article 130 (was Article 750)Energy management moves to Article 130, with a new part on power control systems
120.57 (was 220.57)EVSE load: the 7,200 VA minimum is gone
120.83 (was 220.83)Existing dwelling: one table with new percentages
120.87 (was 220.87)Metered demand: removed loads may be subtracted
625.4 (new rule under an old number)Permanently installed EV equipment is installed by qualified persons
625.5 (new)EV chargers carry permanent markings
625.43Emergency shutoff for EV charging outside one- and two-family dwellings, and a disconnect for every hardwired charger
625.44Nonlocking 30, 50 and 60 A receptacles for EV charging must be listed for EVSE and WPTE use
625.41 and 625.42EV load management moves to power control systems
625.54 (625.22 removed)EV receptacles keep GFCI protection; the personnel protection system section is gone
210.8(F)Outdoor GFCI rises from 50 A to 60 A, and Class C SPGFCI is allowed for HVAC
210.8 (informational notes)GFCIs marked HF or HF+ appear in the notes
210.52(A)(5) (new)Receptacles below a fixed room divider's counter: not within 24 inches
300.4(C) (new)Damaged conductors and wiring methods must be replaced
110.16Arc-flash marking: no ampere threshold, and four required items
230.70 and 225.41 (230.85 removed)Dwelling emergency disconnect: the service disconnect goes outdoors, or an emergency disconnect under 225.41
110.3(B)Equipment instructions must result in a code-compliant installation
408.6Panelboards gain a field-marked short-circuit current rating, outside one- and two-family dwellings
705.11 and 705.20Unprotected power source conductors inside buildings get length limits
215.18(A) and 230.67(A)Surge protection reaches emergency-service sleeping quarters

Load Calculations: Article 220 Becomes Article 120

Article 120 (was Article 220)

Load calculations move from Article 220 to Article 120

NEC 2023: Article 220, Branch-Circuit, Feeder, and Service Load Calculations, in seven parts. (NEC 2023 220.1, page 70-92)

NEC 2026: Article 120, under the same title. 220.57, 220.82, 220.83 and 220.87 become 120.57, 120.82, 120.83 and 120.87, and the article gains parts for recreational vehicle parks and for mobile and manufactured homes. The book's Annex L maps Article 220 to Article 120. (NEC 2026 120.1, page 70-78; NEC 2026 120.57, page 70-83; NEC 2026 120.82, page 70-83; NEC 2026 120.83, page 70-85; NEC 2026 120.87, page 70-86)

Why it matters: Permit forms, worksheets, study guides and plan reviews that cite a 220 section point at numbering the 2026 book no longer uses. Where your state adopts the 2026 edition, cite the 120 number.

Reports said Article 120 gathers load rules from Articles 210, 215 and 220; the book does not say so, and its Annex L maps only Article 220 to Article 120.

120.41 and 120.82(B) (was 220.41 and 220.82(B))

Dwelling general lighting load: 3 VA to 2 VA per square foot

NEC 2023: Not less than 3 VA per square foot for the dwelling unit load (220.41), on a floor area that leaves out open porches and unfinished areas not adaptable for future use (220.5(C)), and the same 3 VA in the optional method (220.82(B)), whose floor area also leaves out garages and unused spaces. (NEC 2023 220.41, page 70-94; NEC 2023 220.5(C), page 70-93; NEC 2023 220.82(B), page 70-98)

NEC 2026: Not less than 2 VA per square foot, in 120.41, in the optional method (120.82(B)) and in the existing-dwelling method (120.83). The floor area follows 120.5(C) in the standard, optional and existing-dwelling methods, which leaves out detached garages, open porches, and unfinished areas not adaptable for future use. (NEC 2026 120.41, page 70-81; NEC 2026 120.82(B), page 70-85; NEC 2026 120.5(C), page 70-78; NEC 2026 120.83, page 70-85)

Why it matters: A dwelling service or feeder calculation by the standard, optional or existing-dwelling method starts from a smaller lighting load under 2026, so a service that fails a 2023 calculation can pass under 2026, which matters when you add an EV charger or a heat pump. Check the floor area too: where 2023's optional method left out every garage, 2026 leaves out only a detached one.

120.82(B) (was 220.82(B))

Optional method: the 100 percent first tier drops from 10 kVA to 8 kVA

NEC 2023: 100 percent of the first 10 kVA of the general loads plus 40 percent of the remainder. (NEC 2023 220.82(B), page 70-98)

NEC 2026: "Not less than 100 percent of the first 8 kVA plus 40 percent of the remainder" of the general loads. (NEC 2026 120.82(B), page 70-85)

Why it matters: This lowers the calculated demand: up to 2 kVA moves from 100 percent to 40 percent, about 1,200 VA less on a house whose general loads pass 10 kVA, adding to the lighting cut. A worksheet must know its edition: the 2023 and 2026 answers differ for the same house.

120.82(D) (new)

EV chargers enter the optional method at 100 percent of their 120.57 load

NEC 2023: The optional method has subdivisions (A) to (C) and names no EVSE. Its general loads, 100 percent of the first 10 kVA and 40 percent of the rest, list appliances fastened in place, permanently connected or located to be on a specific circuit. (NEC 2023 220.82, page 70-98)

NEC 2026: New subdivision (D): "The total load of an EVSE shall be calculated at 100 percent in accordance with 120.57," added beside the general loads, outside the 40 percent remainder. Under 120.57 that load is the nameplate rating if available, or 7,200 VA if not. (NEC 2026 120.82(D), page 70-85; NEC 2026 120.57, page 70-83)

Why it matters: A charger can no longer sit in the 40 percent remainder. A 48 A charger with an 11,520 VA nameplate adds all 11,520 VA, which can decide whether a 100 A service keeps the charger or needs an upgrade or a power control system.

120.5(E) (new)

Load calculations need not take continuous loads at 125 percent

NEC 2023: 220.5 covers voltages, fractions of an ampere and floor area and says nothing about continuous loads. 220.70 counted an energy management system's setpoint as a continuous load. (NEC 2023 220.5, page 70-93; NEC 2023 220.70, page 70-98)

NEC 2026: "Load calculations shall not require continuous loads to be calculated at 125 percent." Its informational note says continuous loads bear on conductor and overcurrent device sizing. Article 120 still prints 125 percent where it names it, such as the metered maximum demand in 120.87. (NEC 2026 120.5(E), page 70-79; NEC 2026 120.87, page 70-86)

Why it matters: The load calculation states the load, and the 125 percent shows up where you size conductors and overcurrent devices. A worksheet that inflates every continuous load inside the calculation is following habit, not the 2026 text.

Reports said the 125 percent now lives only in conductor and overcurrent device sizing; Article 120 still applies it in places, such as 120.87.

120.7 (new)

Power control systems in load calculations

NEC 2023: Where an energy management system limits the current to a feeder or service under 750.30, a single value equal to its maximum ampere setpoint may be used in that feeder's or service's load calculation. (NEC 2023 220.70, page 70-98; NEC 2023 750.30, page 70-668)

NEC 2026: A power control system (PCS) may be used in a branch-circuit, feeder or service load calculation when it meets Article 130 Part II, its setting is determined by qualified persons and is no greater than 80 percent of the rating of the overcurrent device on the circuit it monitors (120.7(B)), and the calculated load is the controlled loads plus the noncontrolled loads (120.7(C)). (NEC 2026 120.7, page 70-79; NEC 2026 120.7(B), page 70-79; NEC 2026 120.7(C), page 70-79)

Why it matters: This is the code path for adding an EV charger or a heat pump to a full panel without a service upgrade. Where the PCS monitors only the loads it controls, the calculation counts its setting for them; where it also monitors noncontrolled loads, it counts the controlled loads at their minimum operating current (120.7(C)).

Article 130 (was Article 750)

Energy management moves to Article 130, with a new part on power control systems

NEC 2023: Article 750, Energy Management Systems: alternate power sources, load management and shedding, and a current setpoint that may be used in the load calculation (750.30). (NEC 2023 750.30, page 70-668)

NEC 2026: Article 130, Energy Management Systems, with the same scope, and a new Part II on power control systems: what a PCS is (130.50); monitoring and automatic controls that prevent overloading conductors, power sources and distribution equipment, and what happens on a malfunction (130.60); and settings in amperes, treated as a continuous load and changeable only by qualified persons (130.70). The book's Annex L maps Article 750 to Article 130. (NEC 2026 130.50, page 70-90; NEC 2026 130.60, page 70-90; NEC 2026 130.70, page 70-90)

Why it matters: Together with 120.7 and 625.42, one article now covers the smart panels and load-management gear going into houses with EV chargers, solar and batteries. A cite to Article 750 for energy management points at the 2023 numbering.

120.57 (was 220.57)

EVSE load: the 7,200 VA minimum is gone

NEC 2023: Either 7,200 VA or the nameplate rating, "whichever is larger". (NEC 2023 220.57, page 70-96)

NEC 2026: The nameplate rating "if available, or at 7200 watts (volt-amperes) if the nameplate is not available". (NEC 2026 120.57, page 70-83)

Why it matters: A 16 A Level 2 charger (a 3,840 VA nameplate) counts 7,200 VA under 2023 and 3,840 VA under 2026. On a tight panel that can decide the call. The EV charger calculator and the load calculator's optional and standard methods use the 2023 rule; the load calculator's existing-dwelling method uses the rule of the edition you choose, so this charger enters it at its 3,840 VA nameplate under 2020 and 2026.

120.83 (was 220.83)

Existing dwelling: one table with new percentages

NEC 2023: Two tables: one where no air conditioning or electric space heating is added (the first 8 kVA at 100 percent, the remainder at 40), and one where it is (air conditioning and central electric space heating at 100 percent, the first 8 kVA of all other loads at 100, the remainder at 40). (NEC 2023 220.83, page 70-99)

NEC 2026: One table, Table 120.83: the first 8 kVA of existing and new load at 100 percent, the remainder of the existing load at 40, new EVSE at 80, new central electric resistance space heating at 80, and all other new loads at 50. It counts the larger of air conditioning or space heating, not both, and has no row of its own for air conditioning. (NEC 2026 120.83, page 70-85)

Why it matters: Adding an EV charger or central electric resistance heat to an older house gets its own percentage, and other new loads come in at 50 percent, where 2023 took added air conditioning and central electric heat at 100, so for those 2026 is lower. Other added load, an EV charger among it, can calculate higher under 2026 than in the 40 percent remainder of 2023's first table.

120.87 (was 220.87)

Metered demand: removed loads may be subtracted

NEC 2023: The maximum demand at 125 percent plus the new load must not exceed the feeder ampacity or the service rating. (NEC 2023 220.87, page 70-100)

NEC 2026: "The maximum demand at 125 percent plus the new load minus any removed load" must not exceed it. (NEC 2026 120.87, page 70-86)

Why it matters: Swapping electric resistance heat for a heat pump can now credit the load you take out when you check whether the new one fits.

EV Charging: Article 625

625.4 (new rule under an old number)

Permanently installed EV equipment is installed by qualified persons

NEC 2023: 625.4 is Voltages, a different rule. The 2023 article has no qualified-persons requirement. (NEC 2023 625.4, page 70-556)

NEC 2026: "Permanently installed electric vehicle power transfer system equipment shall be installed by qualified persons." (NEC 2026 625.4, page 70-627)

Why it matters: A hardwired charger install now has a specific section behind it, which electricians can point to when quoting against unlicensed work. Do not map 2023's 625.4 to 2026's: same number, different rule.

625.5 (new)

EV chargers carry permanent markings

NEC 2023: No 625.5; the article prints no such marking rule.

NEC 2026: Permanent markings on the outside of the enclosure, visible after installation: the supply voltage, number of phases, frequency and full-load current for each incoming supply circuit, and a short-circuit current rating from a listed and labeled assembly or set by an approved method. The section does not say who applies them. (NEC 2026 625.5, page 70-627)

Why it matters: Inspectors get something to check at final, and the next electrician gets the ratings at the equipment instead of hunting for a spec sheet.

625.43

Emergency shutoff for EV charging outside one- and two-family dwellings, and a disconnect for every hardwired charger

NEC 2023: A disconnecting means only for EVSE and WPTE rated more than 60 A or more than 150 V to ground, and no emergency shutoff. (NEC 2023 625.43, page 70-557)

NEC 2026: Every permanently connected EVSE and WPTE gets a readily accessible disconnect that can be locked open. In other than one- and two-family dwellings they also need an emergency disconnect: readily accessible, not less than 20 ft nor more than 100 ft from the equipment and in sight from it, cutting power to all EVSE and WPTE within sight of it, marked with the two warnings the section prints, of the manual reset type, and opening all ungrounded conductors at once. The equipment disconnect may serve as it if it meets all of that. (NEC 2026 625.43, page 70-628)

Why it matters: At a house, a hardwired charger of any rating now needs its lockable disconnect. Commercial, workplace and multifamily projects carry the emergency shutoff in the design and the bid.

625.44

Nonlocking 30, 50 and 60 A receptacles for EV charging must be listed for EVSE and WPTE use

NEC 2023: Receptacles of these ratings for cord-and-plug equipment, with no listing for EV charging. (NEC 2023 625.44, page 70-557)

NEC 2026: Nonlocking 2-pole, 3-wire receptacles at 30 or 50 A, and 3-pole, 4-wire 125/250 V receptacles at 30, 50 or 60 A, must be "listed for EVSE and WPTE use"; a 14-50 (3-pole, 4-wire, 125/250 V, 50 A) is one of them. A cord-and-plug charger's attachment plug is rated at least 125 percent of its maximum rating, and a 50 A receptacle may not go on a 40 A branch circuit. (NEC 2026 625.44, page 70-628)

Why it matters: A 14-50 that serves an EV charger has to carry the EVSE listing, so price a listed receptacle into the quote rather than a general-purpose one.

625.41 and 625.42

EV load management moves to power control systems

NEC 2023: 625.41 sized the overcurrent protection at not less than 125 percent of the equipment's maximum load, and 625.42 called EV charging loads continuous and let an energy management system under Article 750 limit the load. 625.48 is Interactive Equipment. (NEC 2023 625.41, page 70-557; NEC 2023 625.42, page 70-557; NEC 2023 625.48, page 70-557)

NEC 2026: 625.41 now carries the continuous-load rule that 2023 printed in 625.42. 625.42 lets a power control system under Article 130 Part II set the maximum load on the service, feeder and branch circuit, and covers chargers with adjustable settings. 625.48 is still Interactive Equipment, and none of the three relieves EV charging of the 125 percent. (NEC 2026 625.41, page 70-628; NEC 2026 625.42, page 70-628; NEC 2026 625.48, page 70-629)

Why it matters: Size a multi-charger install from the PCS setting and the continuous-load rules, not from a relief the book does not print.

625.54 (625.22 removed)

EV receptacles keep GFCI protection; the personnel protection system section is gone

NEC 2023: 625.22 required EVSE to have a listed system of protection against electric shock of personnel, and 625.54 required GFCI protection for personnel on every receptacle installed for EV charging. (NEC 2023 625.22, page 70-557; NEC 2023 625.54, page 70-559)

NEC 2026: 625.54 is unchanged: "All receptacles installed for the connection of electric vehicle charging shall have ground-fault circuit-interrupter protection for personnel." The article no longer carries a 625.22. (NEC 2026 625.54, page 70-631)

Why it matters: A receptacle for an EV charger needs GFCI protection under either edition.

Some reports said EV circuits move to a 5 mA Class A GFCI in place of a 20 mA device; neither book prints 5 mA, 20 mA or CCID in Article 625.

GFCI and Safety

210.8(F)

Outdoor GFCI rises from 50 A to 60 A, and Class C SPGFCI is allowed for HVAC

NEC 2023: For dwellings, outdoor outlets on single-phase branch circuits of 150 V or less to ground and 50 A or less need GFCI protection. Exception No. 2 spares listed HVAC equipment: "This exception shall expire September 1, 2026." (NEC 2023 210.8(F), page 70-81)

NEC 2026: The same, at 60 A or less, with the same Exception No. 2 and the same printed expiry. New Exception No. 3 permits listed Class C SPGFCI protection for listed HVAC equipment, with the HVAC disconnect marked to say so. (NEC 2026 210.8(F), page 70-96; NEC 2026 210.8(A), page 70-95)

Why it matters: Outdoor condenser and heat pump circuits need GFCI protection where a state has not amended the exception, and under 2026 a listed Class C SPGFCI may provide it. Texas has had the 2026 NEC in force since September 1, 2026, with 210.8(F) Exception No. 2, the listed-HVAC GFCI exception, extended without an expiration date (16 TAC Section 73.100), so a listed HVAC unit stays exempt from 210.8(F) there; the outdoor receptacle a unit plugs into is still under 210.8(A), whose outdoors item has no HVAC exception. Other states may amend too, so check your adoption.

210.8 (informational notes)

GFCIs marked HF or HF+ appear in the notes

NEC 2023: No mention of HF or HF+. (NEC 2023 210.8, page 70-80)

NEC 2026: Two informational notes, not requirements: Class A GFCIs marked HF or HF+ are evaluated for loads with high-frequency leakage current from drives and inverters (under 210.8), and SPGFCIs marked HF or HF+ are described under 210.8(F) Exception No. 3. They are markings on existing classes of device, and no code text requires one. (NEC 2026 210.8, page 70-95; NEC 2026 210.8(F), page 70-96)

Why it matters: If an inverter heat pump or charger trips a GFCI, an HF-marked device is what the notes point to; the code does not require it.

A report called HF and HF+ new GFCI types; the book prints them only as markings, in notes.

210.52(A)(5) (new)

Receptacles below a fixed room divider's counter: not within 24 inches

NEC 2023: The general provisions run from spacing to countertops and print no such limit. (NEC 2023 210.52, page 70-86)

NEC 2026: Where receptacle outlets serve the space of a fixed room divider, such as a freestanding bar-type counter or a railing, and sit below a countertop or work surface, they may not be within 24 inches of the countertop or work surface. (NEC 2026 210.52(A)(5), page 70-102)

Why it matters: Kitchen and bar rough-in layouts change, so check the edition before slab and rough.

Reports said receptacles are barred from any wall within 24 inches below a countertop; the book limits it to the spaces of fixed room dividers.

300.4(C) (new)

Damaged conductors and wiring methods must be replaced

NEC 2023: 300.4 is Protection Against Physical Damage, and the book prints no rule for replacing damaged conductors. (NEC 2023 300.4, page 70-167)

NEC 2026: "Conductors and wiring methods that are no longer suitable for use due to damage, such as overheating, fire damage, corrosive influences, or water, shall be replaced." The 2023 300.4, Protection Against Physical Damage, is now 300.6. (NEC 2026 300.4(C), page 70-199; NEC 2026 300.6, page 70-200)

Why it matters: Inspectors get a specific rule for rejecting heat-damaged or flooded wiring, which comes up on restoration jobs.

110.16

Arc-flash marking: no ampere threshold, and four required items

NEC 2023: In other than dwelling units, a warning on equipment likely to be worked on while energized, and a permanent arc-flash label on service and feeder-supplied equipment rated 1000 A or more, with the date the label was applied. (NEC 2023 110.16, page 70-65)

NEC 2026: In other than dwelling units, a permanent arc-flash marking on service equipment and feeder-supplied equipment likely to be worked on while energized, with no ampere threshold, giving the nominal system voltage, the arc-flash boundary, the available incident energy or the minimum required PPE level, and the date the assessment was completed. (NEC 2026 110.16, page 70-68)

Why it matters: Commercial and industrial gear needs an incident-energy assessment behind its label whatever its rating. Dwelling units are outside it.

Reports said arc-flash labels extend to service and feeder equipment of 1000 A or more; the 2026 section prints no ampere threshold, and the 1000 A figure is 2023's.

Services, Panels, and Workmanship

230.70 and 225.41 (230.85 removed)

Dwelling emergency disconnect: the service disconnect goes outdoors, or an emergency disconnect under 225.41

NEC 2023: 230.85 required an emergency disconnecting means for one- and two-family dwelling units, in a readily accessible outdoor location on or within sight of the dwelling, marked as an emergency disconnect in white on red, letters at least 1/2 in. high, including when service equipment was replaced, unless only meter sockets, service entrance conductors or their raceways and fittings were. 230.70 put the service disconnect outside or inside nearest the point of entrance. (NEC 2023 230.85, page 70-114; NEC 2023 230.70, page 70-112)

NEC 2026: 230.85 is gone. For one- and two-family dwellings the service disconnect itself goes in a readily accessible outdoor location, on or within sight of the dwelling (110.29: visible and not more than 50 ft), unless an emergency disconnect is installed under 225.41, which now carries the emergency disconnect rules and is itself not needed where the service disconnect is outdoors that way or a 225.31 disconnect is in a readily accessible outdoor location, on or within sight of the dwelling. Their service disconnect enclosure is marked EMERGENCY DISCONNECT, white on red, letters at least 1/2 in. high (230.70(B)). Replacing their service equipment brings these rules (230.70(E)); where only meter sockets, service entrance conductors or their raceways and fittings are replaced, the outdoor location and the EMERGENCY DISCONNECT marking are not required, while the SERVICE DISCONNECT marking still is. A remote control that operates the service disconnect is not a service disconnect (230.70(F)). (NEC 2026 230.70(A), page 70-118; NEC 2026 225.41, page 70-112; NEC 2026 225.31, page 70-110; NEC 2026 110.29, page 70-73; NEC 2026 230.70(B), page 70-118; NEC 2026 230.70(E), page 70-118; NEC 2026 230.70(F), page 70-118; NEC 2026 110.21(B), page 70-69)

Why it matters: Replacing a house's service equipment brings the outdoor service disconnect or an emergency disconnect, as 230.85 did under 2023; swapping only the meter socket, the service entrance conductors or their raceways does not. The marking must be permanent and not handwritten (110.21(B)).

Reports said 230.85 merged into 230.70; its emergency disconnect rules went to 225.41, and 230.70(A)(1) moved the service disconnect itself outdoors.

110.3(B)

Equipment instructions must result in a code-compliant installation

NEC 2023: Listed, labeled or identified equipment is installed and used as its listing, labeling or identification instructs. (NEC 2023 110.3(B), page 70-63)

NEC 2026: The same, plus one sentence: "Such instructions shall result in an installation and use that complies with the requirements within this code." (NEC 2026 110.3(B), page 70-66)

Why it matters: Following an instruction sheet does not excuse an installation that falls outside the code: the instructions themselves must land inside it.

Reports said manufacturer instructions cannot reduce code requirements; the book's addition is the sentence quoted above, which puts it as instructions that must result in a compliant installation.

408.6

Panelboards gain a field-marked short-circuit current rating, outside one- and two-family dwellings

NEC 2023: In other than one- and two-family dwelling units, the available fault current and the date of the calculation field marked on the enclosure at the point of supply. (NEC 2023 408.6, page 70-304)

NEC 2026: In other than one- and two-family dwellings: that marking, at the line terminals and in a readily accessible location; a field-marked short-circuit current rating for switchboards and panelboards, at nominal circuit voltage, based on the overcurrent devices installed; the calculation documented; the ratings checked again and the marking adjusted after a modification; and added or replaced overcurrent devices with an interrupting rating at least the marked available fault current. (NEC 2026 408.6, page 70-348)

Why it matters: Multifamily and commercial gear carries more field markings and a paper trail; a one- or two-family house panel is outside it.

705.11 and 705.20

Unprotected power source conductors inside buildings get length limits

NEC 2023: No length limit on power source connection conductors. 705.20 already allowed a single disconnecting means for several power sources. (NEC 2023 705.11, page 70-639; NEC 2023 705.20, page 70-640)

NEC 2026: Power source service conductors inside a building get overcurrent protection within 10 ft of conductor length from the point of connection in dwelling units, and within 16.5 ft in other than dwelling units, with longer options there under engineering supervision. A power source service disconnect that meets 705.11 and the requirements of 705.20 removes the need for a separate source disconnect. (NEC 2026 705.11, page 70-710; NEC 2026 705.20, page 70-712)

Why it matters: A supply-side solar or battery connection inside a house needs its protection within 10 ft of the connection, which can move equipment on the wall.

A report listed a single disconnect for several power sources as new; 2023's 705.20 already allowed it.

215.18(A) and 230.67(A)

Surge protection reaches emergency-service sleeping quarters

NEC 2023: Dwelling units, dormitory units, hotel and motel guest rooms and suites, and nursing home and limited-care patient sleeping rooms. (NEC 2023 215.18(A), page 70-92; NEC 2023 230.67(A), page 70-112)

NEC 2026: The same, plus areas designed only as sleeping quarters in fire, police, ambulance, rescue and ranger stations and similar locations. (NEC 2026 215.18(A), page 70-108; NEC 2026 230.67(A), page 70-118)

Why it matters: Service and feeder work on public-safety buildings picks up a surge protective device.

A report listed dormitories as new; the 2023 lists already named dormitory units.


Where This List Comes From

Every change above is read from the two books, section by section, and each card names the sections and printed pages it rests on. We also read the 2026 change reports of 7 trade sources that circulate online and checked what they say against the books. On 10 of the changes above a report says something the books do not print, and each of those cards says what the report claimed. The books are the source of truth, and this page follows them.


When Does Any of This Apply to You?

Publication is not adoption. The 2026 edition was issued by the NFPA Standards Council on August 20, 2025, but nothing on this page is enforceable until your state or local jurisdiction adopts it. Massachusetts (since April 24, 2026), Maine (since July 1, 2026), North Dakota (since July 1, 2026), Colorado (since August 1, 2026), Minnesota (since August 17, 2026), Texas (since September 1, 2026), Arkansas (since September 3, 2026) and Oregon (since October 1, 2026) have it in force. In Washington, the 2026 NEC replaces the 2023 edition on December 31, 2026 (WAC 296-46B-010). 31 of the 51 jurisdictions we track name the 2023 or 2020 edition in a state rule or code (some reach only some buildings), and 3 an older one. Until your jurisdiction adopts, the current local edition governs every permit you pull.

We track the NEC edition in force for all 50 states plus DC, with effective dates, the source for every row, and 2026 adoption status (each row read from its state's own documents, October 2026, not on an automatic schedule), in our NEC adoption by state table.


Frequently Asked Questions

When does the NEC 2026 take effect in my state?

It depends entirely on your state's adoption cycle. Massachusetts (since April 24, 2026), Maine (since July 1, 2026), North Dakota (since July 1, 2026), Colorado (since August 1, 2026), Minnesota (since August 17, 2026), Texas (since September 1, 2026), Arkansas (since September 3, 2026) and Oregon (since October 1, 2026) have the 2026 NEC in force. In Washington, the 2026 NEC replaces the 2023 edition on December 31, 2026 (WAC 296-46B-010). 31 of the 51 jurisdictions we track name the 2023 or 2020 edition in a state rule or code (some reach only some buildings). See our NEC adoption by state table for the current status of all 50 states and DC, each with its source (each row read from its state's own documents, October 2026, not on an automatic schedule).

Does the NEC 2026 change residential load calculations?

Yes. The load calculation article is renumbered from 220 to 120. The dwelling general lighting load for service and feeder sizing drops from 3 VA to 2 VA per square foot (120.41). The optional method's 100 percent tier shrinks from 10 kVA to 8 kVA (120.82(B)), and new 120.82(D) adds an EV charger at 100 percent of its 120.57 load. That load is the nameplate rating, or 7,200 VA where there is no nameplate, so the 7,200 VA minimum of 2023 is gone. And 120.5(E) says load calculations need not take continuous loads at 125 percent. The same house can produce a different service size under the two editions, so know which one your jurisdiction enforces.

Is my NEC 2023 study guide obsolete?

Not obsolete, but some section numbers are. Load calculations move from Article 220 to Article 120, so 220.82 becomes 120.82, and energy management moves from Article 750 to Article 130. If your exam is based on the 2023 edition, your 2023 guide is the right one. Massachusetts (since April 24, 2026), Maine (since July 1, 2026), North Dakota (since July 1, 2026), Colorado (since August 1, 2026), Minnesota (since August 17, 2026), Texas (since September 1, 2026), Arkansas (since September 3, 2026) and Oregon (since October 1, 2026) have the 2026 NEC in force, so candidates there should confirm with their licensing board which edition their exam uses.

Why did Article 220 become Article 120?

The book does not give a reason. What it does print: Article 120 keeps Article 220's title, Branch-Circuit, Feeder, and Service Load Calculations, and its Annex L, which maps article numbers across editions, puts load calculations at Article 120 and energy management at Article 130, both in Chapter 1. These four sections keep their numbers after the point: 220.57 becomes 120.57, 220.82 becomes 120.82, 220.83 becomes 120.83, and 220.87 becomes 120.87.

Do outdoor AC units and heat pumps need GFCI protection under the NEC 2026?

Under the NEC's own text, yes, unless your state amended it; Texas kept the exception for listed HVAC equipment, as this answer goes on to say. The exception that spared outdoor listed HVAC equipment from GFCI was written into the 2023 NEC itself (210.8(F) Exception No. 2) with a built-in expiration of September 1, 2026, and the 2026 edition prints the same exception with the same date. So even in a state still on the 2023 edition, where the state has not amended it, that carve-out expired on September 1, 2026 and outdoor HVAC equipment now needs GFCI protection (210.8(F) covers outdoor dwelling outlets of 50 A or less under the 2023 edition and 60 A or less under the 2026 edition, which also permits a listed Class C SPGFCI for listed HVAC equipment). States amend this in both directions. Some keep the exception with no expiry: Texas has had the 2026 NEC in force since September 1, 2026, with 210.8(F) Exception No. 2, the listed-HVAC GFCI exception, extended without an expiration date (16 TAC Section 73.100), so a listed HVAC unit stays exempt from 210.8(F) there; the outdoor receptacle a unit plugs into is still under 210.8(A), whose outdoors item has no HVAC exception. Oregon goes its own way: it strikes the exception but limits the section to outdoor general-purpose receptacles, so a hardwired condenser falls outside it (a narrowing, not a clearance; read its own text). Some states never had the exception. Confirm the adopted text for your jurisdiction, or use the outdoor HVAC GFCI tool, which answers only where we have read the state's own documents.

Can I still install a regular 14-50 receptacle for an EV charger?

Under the 2026 NEC, only one listed for EVSE and WPTE use. Section 625.44 requires nonlocking 30, 50, and 60 A receptacles used for EV charging to carry that listing, and a 14-50 is one of them, so check the receptacle's listing before you install it. In states still on the 2023 or earlier editions, the old rules apply until adoption.

What is a Power Control System and why does the 2026 NEC care?

A power control system (PCS) is an energy management system that provides the controls that keep conductors and equipment from being overloaded (130.50). Section 120.7 lets a PCS be used in load calculations: its setting is determined by qualified persons and is no greater than 80 percent of the rating of the overcurrent device on the circuit it monitors, and the calculation adds the controlled loads to the noncontrolled ones. It is the code path for adding an EV charger or heat pump to a full panel without a service upgrade, and Article 130 Part II carries the system requirements.

How many changes are on this page?

26, the ones that bear on how electricians calculate, install, and pass inspection, each read from both books by section and printed page. It is not the whole list of 2026 revisions. We also read the 2026 change reports of 7 trade sources that circulate online and checked what they say against the books. On 10 of the changes here a report says something the books do not print, and each of those changes says what the report claimed. The books are the source of truth, and this page follows them.


Related Tools

First question on any job: which edition is in force?

Nothing above applies until your state adopts it. Check the edition your jurisdiction enforces before you calculate, bid, or pull the permit.