Electrical · EV charging
Biggest EV charger your panel can handle (NEC 220.87)
The load calculator, inverted: from your service size and your measured demand, the largest EV charger that fits, and how an automatic load-management device (an EVEMS) raises that answer without a panel upgrade. The branch is always sized to the full charger output.
Compute your biggest charger
Enter your service size and your measured 12-month peak demand (or a 30-day recorded peak). The calculator returns the largest standard EV charger that fits and its branch, computed by the NEC 220.87 method through the same locked engines the rest of the site uses.
Intry VerifiedA worked default reading, traceable end to end: what it was calculated from, what it was run with, how it was checked, and who has final say.
Where this number comes fromIntry Verified
- Calculated from
- NEC 220.87 (existing loads), branch at 125% continuous per 210.20(A) / 625.41. Computed from the NEC 220.87 inverse solve against your metered demand, with the EVEMS relaxing only the service calc (220.70 / 625.42(A) / 750.30); the branch is always 125% of the full charger output (210.20(A) / 625.41) on NEC Table 310.16 (75°C only on terminations marked for it, 110.14(C)(1)(a)(3)) with the 240.6(A) breaker and Table 250.122 ground. See the full receipt ↓
- Run with
- Service200 A, 240 V
- Measured peak (example)90 A (12-month utility peak)
- New loadEV charger (continuous, 625.42)
- Load managementNone (base 220.87 solve)
- Checked
- Every figure an Intry calculator computes comes from a locked source module, not hand-typed. 35,938 automated checks, one suite for the whole site rather than a per-tool count, re-derive the numbers before each deploy from the tables this site holds, read from the cited NEC section. This is our own deterministic gate, not a third-party audit.
- Final say
- Your AHJ and your actual metered demand have final say; any EVEMS must be listed and installed per its instructions, and the branch is always sized to the full charger output.
Intry Verified · NEC 2023 · Build 525536D · 2026-11-13
Three Device Types
A shed device and a throttle device relax the SERVICE load calculation, which NEC 220.70 and 625.42(A) permit for a listed energy management system in accordance with 750.30. A circuit-share switch does not: it shares one existing branch, and the charger stays in the service calculation. None of the three relaxes the branch circuit, and the computation is different for each.
The three EVEMS device types, the named devices, and how each bounds the charger
Swipe the table sideways to see the rest of its columns. →
| Type | Named device | How it bounds the charger |
|---|---|---|
| Shed (disconnect) | DCC (Thermolec / RC Devices / RVE) | Disconnects the charger when the panel nears its limit; charger up to 80% of its pass-through breaker. |
| Throttle (current-modulating) | Emporia | Modulates delivered current to hold total demand under the service; branch wired for full hardware. |
| Throttle (current-modulating) | Wallbox | Modulates delivered current to hold total demand under the service; branch wired for full hardware. |
| Circuit-share | Splitvolt | Time-shares one existing branch; charger up to 80% of that branch breaker, one at a time. |
Biggest Charger by Service Size
The biggest charger that fits for an example measured peak on each service size in the table. These are worked examples; your own metered demand governs, so use the calculator below for your number.
NEC 220.87 inverse solve per service size, at an example 12-month utility peak
Swipe the table sideways to see the rest of its columns. →
| Service | Example peak | Biggest charger | Branch |
|---|---|---|---|
| 100A service | 60A | none | no branch circuit: NEC 220.87 alone fits no charger here |
| 125A service | 70A | 32A | #8 Cu / 40A |
| 150A service | 80A | 48A | #6 Cu (75°C-marked terminations; #4 Cu at 60°C or NM-B) / 60A |
| 200A service | 90A | 48A | #6 Cu (75°C-marked terminations; #4 Cu at 60°C or NM-B) / 60A |
Full grid across demand levels: max charger chart. With vs without a device: with vs without load management.
Two EVs on One Panel
A second EV is a version of this question with a clean answer. Two full-rate chargers can outrun a single service on their own, because two continuous loads eat headroom fast. The move is not two dedicated circuits fighting over the panel; it is one multi-charger load-management system that shares the service's spare capacity between the cars.
The key idea: a multi-port EVEMS does not grant two full chargers, it splits one service's headroom across both. When both cars are plugged in, each gets roughly half the available rate; when only one is charging, it gets the full rate. The device holds the combined draw under the service (NEC 220.70 / 625.42(A) / 750.30), while each branch circuit stays wired and protected for its own charger's full output, never the shared setpoint. A circuit-share switch is the other honest path when you also have a heavy appliance branch to borrow: one load at a time, never both together. Run your service and measured demand through the calculator below to see the headroom you would be sharing.
Load-Management Devices
DCC (Thermolec / RC Devices / RVE)
Shed (disconnect). EV charging-station pass-through breaker rating.
Emporia
Throttle (current-modulating). EVSE hardware output (48A hardwired / 40A plug-in).
Wallbox
Throttle (current-modulating). EVSE hardware output (48A / 40A models).
Splitvolt
Circuit-share. existing shared-branch (dryer) breaker rating.
What voids the method, and what has to be true before a device changes the answer
The panel-capacity method this tool uses is NEC 220.87, and a load-management device can change its answer only where the code's own conditions hold. They are facts about installed equipment, so no calculator can verify them. Each list below is published whole, exactly as the engine carries it, rather than trimmed to the convenient members.
Before an energy management system relaxes the service calculation
All 7 of these, not a selection.
- The energy management system is listed: as a complete energy management system, as a kit for field installation in switch or overcurrent device enclosures, or as listed individual components assembled as a system. (NEC 750.6)
- The system is an EMS in accordance with 750.30. Both the 625.42(A) relaxation and 220.70's single-setpoint value are written on that condition, so a device that does not meet 750.30 relaxes nothing. (NEC 625.42(A) / 220.70)
- The system does not cause a branch circuit, feeder, or service to be overloaded, and where it limits the current on a conductor it also meets the duties 750.30(C)(2) through (C)(4) impose. (NEC 750.30(C))
- The system does not override load shedding controls placed to ensure minimum electrical capacity for fire pumps, emergency systems, legally required standby systems or critical operations power systems, and does not disconnect power to elevators, escalators, moving walks or stairway lift chairs, hazardous-location ventilation, emergency lighting circuits, or essential health care systems. (NEC 750.30(A) / 750.30(B))
- Where one or more pieces of equipment are provided with an integral load management control, the system is marked to indicate that control is provided. (NEC 625.42(A))
- The EMS setpoint counts as a continuous load in the load calculation. This tool checks the service RATING, which NEC 230.79 sets from the calculated load; it does not size service-entrance conductors, and NEC 230.42(A)(1) sizes those from the noncontinuous load plus 125 percent of the continuous load. Whoever sizes or verifies the service conductors has to apply that to the setpoint. (NEC 220.70 / 230.42(A)(1))
- Where the system controls electrical power through a remote means, a directory identifying the controlled devices and circuits is posted on the enclosure of the controller, the disconnect, or the branch-circuit overcurrent device. (NEC 750.50)
The NEC does not define peak load shaving, and where it does use the term, at 700.4(C)(1), it is describing a source running in parallel rather than a device that limits load. Reading an EV energy management system as a form of peak load shaving is our interpretation, and it is the conservative one: check it with the AHJ before relying on a 30-day recorded basis on a service that has one.
A branch-level device, which never reached the service calculation
NEC 625.42(A) reaches the service and feeder load calculation; only (B) changes the EVSE's own ampere rating, which is what 625.41 sizes the branch from. A branch-level device leaves the conductor, breaker and ground sized to 125 percent of the charger's full output. Of the 7 conditions listed above, 4 still attach. That is which members of that list carry over, and not a complete account of what NEC 750.30 asks of a device sitting on a branch circuit:
- The energy management system is listed: as a complete energy management system, as a kit for field installation in switch or overcurrent device enclosures, or as listed individual components assembled as a system. (NEC 750.6)
- The system does not cause a branch circuit, feeder, or service to be overloaded, and where it limits the current on a conductor it also meets the duties 750.30(C)(2) through (C)(4) impose. (NEC 750.30(C))
- The system does not override load shedding controls placed to ensure minimum electrical capacity for fire pumps, emergency systems, legally required standby systems or critical operations power systems, and does not disconnect power to elevators, escalators, moving walks or stairway lift chairs, hazardous-location ventilation, emergency lighting circuits, or essential health care systems. (NEC 750.30(A) / 750.30(B))
- Where the system controls electrical power through a remote means, a directory identifying the controlled devices and circuits is posted on the enclosure of the controller, the disconnect, or the branch-circuit overcurrent device. (NEC 750.50)
Before a dialled-down setting sizes the circuit
Sizing a conductor from an adjusted current setting rather than from the unit's rating is NEC 625.42(B). The 4 below are the conditions this tool can name, and 750.30(C) attaches three of them. They are not the full set: 625.40, 625.54 and 750.30's own capacity requirement are untouched by them. Size from the full rating unless a qualified person has verified these, 625.42(B) itself and the manufacturer's instructions, on site:
- Where the adjusting means is part of an energy management system, that system uses monitoring and controls to automatically cease current flow if it malfunctions. 750.30(C) applies its subdivisions where an EMS is used to limit the current on a conductor. (NEC 750.30(C)(2))
- Access to the ampere adjusting means is restricted by at least one of the five means 750.30(C)(3) names: behind a removable and sealable cover over the adjustment, behind a cover or door that needs a tool to open, behind a locked door accessible only to qualified personnel, password protected with the password held by qualified personnel only, or software whose access to the adjusting means is password protected for qualified personnel only. (NEC 750.30(C)(3))
- The equipment supplying the branch circuit is field marked with the maximum current setting, the date of the calculation and setting, identification of the loads and sources associated with the current limiting feature, and the words "The setting for the EMS current limiting feature shall not be bypassed". Those markings meet the requirements in 110.21(B) and are located so they are clearly visible to qualified persons before examination, adjustment, servicing, or maintenance of the equipment. (NEC 750.30(C)(4))
- The adjustment was made in accordance with the manufacturer's instructions, and the adjusted rating appears on the rating label with enough durability to withstand the environment involved. (NEC 625.42(B) / 110.3(B))
NEC 625.42(B) + 750.30(C) + 110.3(B)
The fix can void the basis of the answer that recommended it
This is the part of NEC 220.87 that catches people out, and it is worth reading before you quote the job. Where a 220.87 answer came from the 30-day recording exception rather than from a full year of demand data, the engine returns this:
Your answer above used the 30-day recorded peak, which is NEC 220.87's exception rather than its main rule. That exception is not permitted where the service has a renewable energy system (solar PV, wind) or any form of peak load shaving. If you install load management here, a later 220.87 check on this service cannot rest on a new 30-day recording; it needs 12 months of utility demand data.
Frequently Asked Questions
What is the biggest EV charger I can install without a panel upgrade?
It depends on your service size and your measured demand, not on a rule of thumb. By NEC 220.87 you take 125% of your 12-month peak demand and subtract it from the service rating; what is left has to cover the charger at its NEC 220.57 value, which is 7,200 VA or the nameplate rating, whichever is larger. On an example 100A service carrying a 60A peak that leaves 6,000 VA, under the 7,200 VA any EVSE is calculated at, so the answer is no charger fits without load management and load management is the route. The same math on a 200A service with a 90A peak allows a 48A charger on #6 Cu (75°C-marked terminations; #4 Cu at 60°C or NM-B) / 60A. Enter your own service and metered demand in the calculator for your number.
How does a load-management device let me install a bigger EV charger?
An automatic load-management device can relax the SERVICE load calculation, which NEC 220.70 and 625.42(A) permit for a listed EMS in accordance with 750.30. Two of the three device types do that: a shed device (DCC) disconnects the charger when the panel nears its limit, so the service stops being the binding constraint; a throttle device (Emporia PowerSmart, Wallbox Power Boost) modulates the delivered current to hold total demand under the service. A circuit-share switch (Splitvolt) does NOT: it time-shares one existing branch so the EV and the appliance never run together, which this tool does not read as a 625.42(A) relaxation, so the charger stays in the service calculation at its full NEC 220.57 value. None of the three makes the branch circuit smaller.
Does a load-management device let me use smaller wire?
No. The branch conductor and breaker are always sized to 125% of the FULL EVSE hardware output (NEC 210.20(A) / 625.41), never the shed or throttle setpoint. An external monitor or throttle does not change the charger's rating: if it fails or is bypassed the EVSE can pull its full current, so the conductor must always carry it. The route this tool recognizes for a smaller branch is the EVSE's own restricted-access adjusted setting under NEC 625.42(B), and it is a route a calculator cannot take for you: the conditions it attaches, under 750.30(C) and the manufacturer's instructions, are facts about installed equipment. The 4 conditions this tool can name are not a full compliance checklist. Size from the full rating unless a qualified person has verified them, and 625.42(B) itself, on site. NEC 625.42(A) reaches the service and feeder load calculation; only (B) changes the EVSE's own ampere rating, which is what 625.41 sizes the branch from.
How big an EV charger does a DCC allow?
A DCC shed device allows a charger up to 80% of its EV pass-through breaker, which is the continuous-load limit of NEC 210.20(A), once the service itself carries the base load, because it disconnects the charger before the panel is overloaded (NEC 625.42(A) with 750.30(C), which requires the system not to cause the service to be overloaded). On a service already over its rating with no charger added, a shed device relieves nothing and this tool says so rather than computing one. Across the DCC breaker sizes that is 20A breaker to a 16A charger, 30A breaker to a 24A charger, 40A breaker to a 32A charger, 50A breaker to a 40A charger, 60A breaker to a 48A charger. The DCC-9, DCC-10, and DCC-12 all compute the same charger; they differ in the internal breaker, the maximum monitored service, and the application. On a 100A main: The DCC-10 Gen3 installation manual's own table permits up to a 60 A EV pass-through breaker on a 100 A main; this tool applies a stricter table and caps it at 50 A.
Is EV charging a continuous load?
Yes, for the branch circuit: NEC 625.42 makes EV charging a continuous load, so the branch circuit and overcurrent device are sized at 125% of the charger output. The NEC 220.87 SERVICE check is a separate calc: there the 125% applies to your existing metered demand, and the new charger is added at 100% of its 220.57 value (7,200 VA or nameplate). Adding 125% to the charger in the service check as well is a stricter conservative screen, not the code-literal reading.
Can my panel handle two EV chargers?
It depends on your measured demand, and the honest answer is that this is two questions. Two Level 2 chargers are two continuous loads: whether they fit as two FULL chargers comes down to your measured demand exactly as a single charger does, so run each through the calculator. What a multi-charger load-management system actually does is the part that decides the answer. It does not give you two full chargers; it SHARES one service's spare headroom between the cars, throttling them so their COMBINED draw stays under the service (NEC 220.70 / 625.42(A) / 750.30). So the same headroom that fits one 48A charger becomes, for two cars, roughly 24A each when both are plugged in, and the full rate for whichever one is charging alone. Each branch circuit is still wired and protected for its charger's full output; only the shared draw is managed.
Related Tools
Load Calculator (NEC 220)
The forward direction: NEC 220.82 service sizing and the 220.87 existing-load check.
EV Charger Calculator
Wire, breaker, and panel capacity for a Level 2 charger per NEC Article 625.
Wire Size Calculator
The correct conductor per NEC 310.16 with derating and the 110.14(C) terminal cap.
Heat Pump Water Heater Circuit
Breaker and wire for every heat pump water heater line, plus the 120V shared-circuit rule.
120V Induction Range Circuit
The battery-buffered plug-in range that skips the 240V circuit, and whether it can share one (NEC 210.23(B)(1)).
Run this inside your AI assistant
Prefer to just ask? Add this to Claude.
Connect Intry to Claude once, then just say “use Intry to…” to run the biggest ev charger calculator from a plain-English question, on your phone, on the job. You get the number (computed live, not guessed), what it means, and the cited NEC section. Works on every Claude plan.