HVAC · Commissioning

Nitrogen Pressure Test Calculator

How much of a nitrogen pressure-test drop is temperature and how much is a real leak, from the pressure and gas temperature at the start and the end. The required test pressure, hold time and pass or fail stay with the manufacturer and AHJ.

Field brief
Overnight dropa 300 psig test at 75°F that cools to 50°F should read 285.3 psig by morning. That 14.7 psi drop is temperature, not a leak.285.3 psig
Per 10°Fpressure moves about 4.05 psi per 10°F at 200 psig but 9.72 psi at 500 psig. The flat "5 psi per 10°" rule only fits the middle of the range, so use the computed value for your pressure.4.05–9.72 psi
Leak vs tempresidual = measured − temperature-corrected expected. Within gauge tolerance means no leak indicated; a large negative residual means investigate before you charge.P₁T₂/T₁
Start of test (when you pressurized)
End of test (when you came back)

Use the temperature of the gas (pipe/coil surface), not the room. The gauge follows the gas.

Expected pressure now (temperature only)
285.3 psig
what a leak-free system should read at 50°F
Change is temperature only, no leak indicated
Your actual change-15 psi
Temperature accounts for-14.7 psi
Unexplained residual-0.3 psi
Tolerance band±2.2 psi

The pressure change is within tolerance of what the temperature change alone predicts, so no leak is indicated over this interval. This is a diagnostic, not a certified pass: hold time and required pressure are set by the manufacturer and AHJ.

Show the math

Gay-Lussac (constant volume): P₁/T₁ = P₂/T₂ in ABSOLUTE units

P₂(gauge) = (P₁ + 14.696)(T₂ + 459.67)/(T₁ + 459.67) − 14.696

= (300 + 14.696)(50 + 459.67)/(75 + 459.67) − 14.696 = 285.3 psig

Residual = measured − expected = 285 − 285.3 = -0.3 psi

Constants: standard atmosphere 14.696 psi and the 459.67 °F→Rankine offset (NIST).

Where this number comes fromIntry Verified
Calculated from
Gay-Lussac constant-volume gas law; NIST standard atmosphere + Rankine offset. Computed by the Gay-Lussac engine from the NIST standard atmosphere (14.696 psi) and the 459.67 Fahrenheit-to-Rankine offset; the residual is your measured pressure minus the temperature-corrected expected pressure. See the full receipt ↓
Run with
  • Start300 psig @ 75°F
  • End285 psig @ 50°F
  • Expected now285.3 psig
  • Residual-0.3 psi
Checked
Every figure an Intry calculator computes comes from a locked source module, not hand-typed. 31163 automated checks, one suite for the whole site rather than a per-tool count, re-derive the numbers before each deploy from the tables this site transcribed from the NIST standard-atmosphere and Rankine constants it was computed from. This is our own deterministic gate, not a third-party audit.
Final say
The equipment manufacturer and your AHJ have the final say on the required test pressure, the hold time, and pass or fail.
What Intry Verified means

Intry Verified · Build 2731D30 · 2026-10-15

This is a diagnostic, not a code pass. It tells you how much of the pressure change is temperature and how much is a real loss. It does not certify the test: the required test pressure, the hold time, and pass/fail are set by the equipment manufacturer and your AHJ. Always run the nitrogen through a pressure regulator and never apply bottle pressure directly (a cylinder holds 2,000+ psi and can rupture the system). Test at or below the rating of the lowest-rated component in the sealed section, and use dry nitrogen only, never oxygen or a flammable gas.
Residual -0.3 psitemp only

Pressure Change per Degree by Test Pressure (at 70°F)

Gay-Lussac sensitivity dP/dT = (gauge + 14.696) / (temp F + 459.67), evaluated at a 70°F reference. Standard atmosphere 14.696 psi and the 459.67 Rankine offset are NIST values.
Test pressure (psig)Change per 1°F (psi)Change per 10°F (psi)
1500.3113.11
2000.4054.05
3000.5945.94
4000.7837.83
5000.9729.72
6001.16111.61

The change per degree grows with the test pressure because it tracks the absolute pressure. This is why a high-pressure test looks like it is bleeding down faster when it is only cooling: at 600 psig the same 10°F swing moves nearly twice the psi it does at 300 psig. Use your own temperatures in the calculator above; this table is the fixed-reference sensitivity, not a substitute for the two-reading correction.


The temperature-correction formula

A sealed test is a fixed volume of gas, so Gay-Lussac's law applies: P₁ / T₁ = P₂ / T₂ in absolute units. Convert gauge pressure to absolute by adding the standard atmosphere (14.696 psi) and convert Fahrenheit to absolute Rankine by adding 459.67. The pressure a leak-free system should read at the ending temperature is:

P₂(gauge) = (P₁ + 14.696) × (T₂ + 459.67) / (T₁ + 459.67) − 14.696

Subtract that expected pressure from your measured pressure to get the residual. A residual within gauge tolerance is temperature only; a residual well below zero is a real loss. The 14.696 psi standard atmosphere and the 459.67 Rankine offset are NIST values (standard atmosphere = 101,325 Pa; NIST SP 811).


Nitrogen Pressure Test FAQs

Does nitrogen pressure drop overnight without a leak?

Yes. A sealed nitrogen pressure test loses pressure whenever the gas cools, with no leak at all, because pressure follows absolute temperature (Gay-Lussac's law). A 300 psig test that cools from 75 F to 50 F should read 285.3 psig in the morning, a 14.7 psi drop that is entirely temperature. The way to tell a real leak from temperature is to correct for the temperature change, which is what this calculator does: enter both pressures and both temperatures and it tells you how much of the drop is unexplained.

How much does nitrogen test pressure change per degree?

It depends on the test pressure. At 200 psig it changes about 4.05 psi for every 10 F of gas-temperature change, but at 500 psig it changes about 9.72 psi per 10 F. The change scales with absolute pressure: dP per degree F = (gauge pressure + 14.696) divided by (temperature F + 459.67). This is why the flat "5 psi per 10 degrees" rule of thumb is only right near the middle of the usual test range: below about 250 psig it overstates the change and above it, it understates it badly. Use the pressure-specific value from the table, not the rule of thumb.

How do I know if my nitrogen pressure test failed from temperature or a leak?

Correct for temperature first. Compute the pressure a leak-free system should read at the ending temperature (starting absolute pressure times ending absolute temperature divided by starting absolute temperature), then subtract it from your measured pressure. If the leftover residual is within your gauge tolerance, the change was temperature and no leak is indicated. If the measured pressure is well below the temperature-corrected expected pressure, that gap is a real loss, so soap the joints and recheck the fittings before charging.

What pressure do you test HVAC line sets with nitrogen?

Test at or below the pressure rating of the lowest-rated component in the sealed section, and never above what the equipment manufacturer specifies. Many residential split systems are pressure-tested in the few-hundred-psi range, but the exact test pressure is set by the manufacturer and your local authority having jurisdiction, not by a rule of thumb. Always use dry nitrogen, never oxygen or a flammable gas, and never test a system past a component's rated pressure. This calculator does not set or certify the test pressure; it only separates temperature from leakage.

How long should you hold a nitrogen pressure test?

Hold time is set by the manufacturer and the AHJ, not by this tool. As field practice, residential jobs are often held long enough to see a stable reading and VRF and larger commercial systems are held much longer, sometimes a full day. The longer the hold, the more the ambient temperature swings, which is exactly why you correct the reading for temperature before calling it pass or fail. A two-reading test (pressure and temperature at the start, again at the end) is what makes the correction possible.

Why did my pressure go up overnight on a nitrogen test?

The gas warmed. Pressure rises with absolute temperature just as it falls, so a test left in the sun or one that started cold and warmed through the day will read higher than it did when you pressurized it. If this calculator says your reading is higher than temperature predicts, recheck the entered start and end temperatures, because a rising reading with no temperature change would be physically impossible on a sealed system.


Next in the commissioning job

A pressure test is one step in a line-set and charge job. Size the line set, pull the vacuum, then verify the charge with superheat and subcooling: