The standard
Intry Verified
A reading from any of the 60 Intry calculators in the table below carries the same four facts, in the same order, across both trades: what it was calculated from, what it was run with, how it was checked, and who has final say. This is the standard, so you can follow any number backwards without taking our word for it.
The four facts on a traced result
- Calculated from
- The exact authority the number came from: the cited NEC section for electrical tools (the 2023 edition for the table tools, and for the outdoor GFCI tool the edition each state enforces, shown in its row), the manufacturer pressure-temperature data for refrigerant tools, the UL 60335-2-40 / ANSI/ASHRAE 15.2-2024 or AHRI-certified NEEP standard for A2L charge limits and cold-climate capacity, the EPA rule (40 CFR) for refrigerant compliance, the ACCA Manual J basis for load sizing, or the bender geometry for a bend. It is reused word for word from the engine, never re-written for the page.
- Run with
- The exact inputs the engine consumed for that run: the materials, the terminal ratings, the conditions. A number is only correct given its inputs, so we show them. Nothing the engine did not use appears here.
- Checked
- How the number is held to its source. Before any deploy, an automated test suite does two things: it re-derives calculated figures from a locked data module so a number cannot be copied wrong onto the page, and it checks values against values recorded from what they cite - the NEC section, the manufacturer chart, the federal rule - so a number is held to what its source printed, not just to itself. It is our own deterministic gate that runs on every update, not a third-party audit, and we say so.
- Final say
- Who has the last word, in plain terms. Your AHJ and local amendments on an electrical install, the unit nameplate and the manufacturer's charging chart on a refrigerant system, a full Manual J on the actual house. The standard's last line is deliberately not ours.
How a number earns it
Two rules make the standard checkable instead of aspirational. First, derive, never hand-type: every calculated number traces to a locked data module (an NEC table, a manufacturer PT chart), so it cannot be copied wrong. Second, declare, never restate: which authority governs a tool is declared once, in one place, so an HVAC result is structurally incapable of claiming the electrical code, and the reverse.
Those rules are enforced by a test suite that runs before every deploy. It does two jobs: it re-derives calculated figures from their locked source so a number cannot be copied wrong onto the page, and it checks values against values recorded from the source they cite, so a number is held to what that source printed, not just to itself. When a covered value drifts from its source, or a new calculator ships without registering its check, the build stops and the change never ships. As of the current build that suite holds 35,006 checks, and this very page passed through it.
Two things follow. First, a number is held to the code book, spec sheet, or federal rule it actually comes from, not to our own say-so. Second, it stays that way: the same gate runs on every future update, and every new calculator has to register its check before it can go live. This is our own deterministic gate, run on every build. It is not a third-party audit, and it is not a certificate on any one reading: your AHJ, the unit nameplate, and a full Manual J still have the last word.
The same discipline covers the pictures. On the conduit bending calculator, the interactive 3D bend is not a drawing: every vertex, arc, and mark is re-derived from the same locked engine that computes the marks, and the drawing is checked against that engine to a millionth of an inch before every deploy. So the pipe you spin, and the flat diagram beside it, cannot drift from the numbers they are built on.
The receipt for each traced calculator
One row for each of the 60 calculators whose result carries the Intry Verified trace: the authority its numbers are derived from, the code or data edition they are keyed to, and whether an AI assistant can run the tool and get a result that is checked against the locked engine on every deploy. This table is generated by the same gate it describes, and it is published as machine-readable JSON at /api/verified. The 35,006 checks above gate every deploy as one suite; the receipt below adds no per-tool count, because a single check can guard several tools at once.
| Tool | Trade | Derived from | Edition | Runnable + result checked vs engine |
|---|---|---|---|---|
| Wire Size Calculator | electrical | NEC Table 310.16 · NEC 210.19(A) and 210.20(A) · NEC 110.14(C) · NEC 310.15(B)(1) with Table 310.15(B)(1)(1), and Table 310.15(C)(1) · NEC 240.6(A) and 240.4(B) · NEC 240.4(D) · NEC Table 250.122 | NEC 2023 | Runnable via MCP; result asserted equal to the locked engine |
| Voltage Drop Calculator | electrical | NEC Chapter 9, Table 9 · NEC Chapter 9, Table 8 · NEC 210.19 and 215.2 Informational Notes · NEC 250.122(B) · NEC 210.19(A), 215.2(A) and 430.22, by circuit | NEC 2023 | Runnable via MCP; result asserted equal to the locked engine |
| Conduit Fill Calculator | electrical | NEC Chapter 9, Table 1 · NEC Chapter 9, Table 4 · NEC Chapter 9, Table 5 · NEC Chapter 9, Note 7 | NEC 2023 | Runnable via MCP; result asserted equal to the locked engine |
| Box Fill Calculator | electrical | NEC Table 314.16(B)(1) · NEC 314.16(B)(1) through (B)(6) · NEC Table 314.16(A) | NEC 2023 | Runnable via MCP; result asserted equal to the locked engine |
| EV Charger Circuit Calculator | electrical | NEC 625.41 and 625.42 · NEC 625.44, 625.54, and 210.21(B)(1) · NEC 110.14(A) · NEC Table 310.16 · NEC 240.6(A), 240.4(B), 240.4(D), and Table 250.122 · NEC 110.14(C)(1)(a)(3), 334.80, 334.104 and 250.122(B) · NEC Chapter 9, Table 8 and NEC 210.19, its Informational Note (voltage drop) · NEC Table 310.15(B)(1)(1) and Table 310.15(C)(1) · NEC 750.6, 750.30, and 750.50, energy management systems · NEC 625.42(B) + 750.30(C) + 110.3(B) · NEC 220.60 · NEC 230.79 and NEC 230.42(A)(1) · NEC 230.90 and NEC 240.4 · NEC 210.20(A) · NEC 700.4(C)(1), informational note · The charger makers' installation manuals · The vehicle makers' and EPA's documents | NEC 2023 | Runnable via MCP; result asserted equal to the locked engine |
| Existing-Load Panel Check (NEC 220.87) | electrical | NEC 220.82 · NEC 220.40 · NEC 220.87 · NEC 220.83 · NEC 220.57 · NEC 210.20(A) · NEC 240.6(A) | NEC 2023; the existing-dwelling method answers from the edition chosen on the page: the 2020, 2023 or 2026 text | Runnable via MCP; result asserted equal to the locked engine |
| Water Heater Circuit Calculator | electrical | NEC 422.13 · NEC 210.20(A) · NEC Table 310.16 and NEC 110.14(C) · NEC 240.6(A) and 240.4(D) · NEC Table 250.122 · NEC 210.23(B) and 210.23(B)(2) · NEC 422.13 with 210.23(B)(2) · NEC 422.11(A), 422.16(A) and 110.3(B) · The water heater makers' documents | NEC 2023 | Runnable via MCP; result asserted equal to the locked engine |
| 120V Induction Range Circuit Calculator | electrical | NEC 210.23(B)(1) and 210.23(B)(2) · NEC 210.21(B)(2) and Table 210.21(B)(2) · NEC 210.20(A) and Article 100 (continuous load) · NEC 210.19(C) · NEC Table 220.55 · NEC Table 310.16, 240.4(D), and Table 250.122 · NEC 110.14(C)(1)(a)(3) and 334.80 · NEC 210.19(A)(1) and Table 240.6(A) · NEC 210.8(D), 210.8(D)(8) and 210.8(D)(10) · NEC 210.21(B)(1) · The range and cooktop makers' documents | NEC 2023 | Runnable via MCP; result asserted equal to the locked engine |
| Biggest EV Charger Calculator (EVEMS) | electrical | NEC 220.87 · NEC 220.70 · NEC 625.42 and 750.30 · NEC 210.20(A) and 625.41 · NEC Table 310.16 · NEC 110.14(C)(1)(a)(3) and 334.80 · NEC 240.6(A), 240.4(D), and Table 250.122 · NEC 750.30(C)(1) through (C)(4), and 750.50 · NEC 220.60 · NEC 210.20(A) · NEC 230.90 and NEC 240.4 · NEC 110.3(B) · The load management devices' own documents · NEC 750.6, 750.30, and 750.50, energy management systems · NEC 230.79 and NEC 230.42(A)(1) · NEC 625.42(B) + 750.30(C) + 110.3(B) · NEC 700.4(C)(1), informational note | NEC 2023 | Runnable via MCP; result asserted equal to the locked engine |
| Conduit Bending Calculator | electrical | Bender-manufacturer offset multiplier table · Bend geometry (trigonometry) · Bender-manufacturer 3-point saddle table · Bender-manufacturer shrink-per-inch table · Hand-bender take-up (EMT) and gain (every type) | NEC 2023 Chapter 9 Table 2 (minimum bend radii), for the feasibility check only; the bend math is geometry and the bender maker's chart | Runnable via MCP; result asserted equal to the locked engine |
| MCA & MOCP Breaker Calculator | hvac | NEC 440.33, 440.34, 440.35 and 430.24 · NEC 440.22, 440.22(A), 440.22(B)(1) and 440.22(B)(2) · NEC 240.6(A) · NEC 240.4(G) (Article 440) · NEC 440.1, 440.21, 424.4(B) and 424.19 (a circuit with no compressor) · NEC 310.15(B)(1) and 310.15(C)(1) · NEC 310.15(B)(2) · NEC 110.14(C) · NEC 440.14, 440.12 and 110.26(A) · NEC 440.52 · NEC Table 310.16 · NEC Table 250.122 · NEC 250.122(A) and 250.122(B) · NEC 440.4(B) and 110.3(B) · NEC Chapter 9, Table 8 and NEC 210.19, its Informational Note (voltage drop) | NEC 2023 | Runnable via MCP; result asserted equal to the locked engine |
| A2L Changeout Circuit Check | hvac | NEC 440.4(B) and 110.3(B) · NEC 440.35 and 440.4(B) · NEC Table 310.16 · NEC 310.15(B)(1) and 310.15(C)(1) · NEC 310.15(B)(2) · NEC 110.14(C) · NEC 440.22, 440.22(A) and 440.22(B) · NEC 240.6(A) · NEC 240.4(G) (Article 440) · NEC 440.14, NEC 440.12 and NEC 110.26(A) | NEC 2023 | Reference engine (not runnable via MCP) |
| Superheat & Subcooling Calculator | hvac | CEC-400-2025-010-AP, Reference Appendix RA3 Table RA3.2-1 (Installer Testing at Final) · CEC-400-2025-010-AP, Reference Appendix RA3 Table RA3.2-2 (target superheat) · California Energy Commission, 2025 Reference Appendices (CEC-400-2025-010-AP), Table RA3.2-1, page RA3-19 (the TXV superheat default and the subcooling tolerance) · Lennox 13ACC Installation Instructions (form 504726), page 14, Table 6 (a fixed-orifice subcooling target with the maker's own tolerance) · Sporlan (Parker) Bulletin 10-9, March 2011, page 14, Table 7 (TXV superheat settings, shown for reference) · CEC-400-2022-010-AP, Joint Appendix JA6.1.6.3 (the airflow precondition; 2022 edition; JA6.1 is RESERVED in the 2025 edition) · Carrier PH5SAN5, Carrier SM10-R454B-03, Carrier 25SCA5, Goodman IOG-4048C, ICP 428 01 5106 00, Trane 88-M5MHWUN-1A-EN, Rheem RD16AY, and Bosch service literature · The per-machine charge-target corpus (registered manufacturer books, cited by form number) · The heat pump's heating-mode check (each maker's own heat pump book, cited by form number and page) · York ST-022-12, Figures 1 and 2 (example charging charts) · Rheem RD16AY / RD18AY section 5.7, and Lennox 13ACX 506374-01 page 20 · Copeland discharge-temperature guidance, and Proctor Engineering on airflow and capacity · The manufacturer installation books these steps quote · Honeywell, March 2016 version 8 · Honeywell, 3455 FP I (August 2019) · Chemours, C-10023 (1/16) · Arkema (Forane), 2025 edition · Arkema (Forane), PPC/SDC/08-2020 · Honeywell, G 525-013 · Copeland, 2021ET-31 (7/21) · Copeland, 95-14 R11 (7/21) · Copeland, AE4-1344 R21 · Copeland, AE22-1182 R26 · Copeland, AE 104 R2 (10/06) · Copeland, AE-105 R3 (5/18) · Heatcraft Refrigeration Products, H-IM-CU-0725 Version 010, Part No. 25014601 · Heatcraft Refrigeration Products, H-IM-UC-0626 Version 04, Part No. 25008201 | CEC Title 24 Tables RA3.2-1 (installer compliance criteria) and RA3.2-2 (fixed-orifice target superheat); the rest is manufacturer data and physics | Runnable via MCP; result asserted equal to the locked engine |
| Cold-Climate Heat Pump Capacity Calculator | hvac | AHRI-certified NEEP ccASHP database · Manufacturer submittal · Linear interpolation of the MAX-capacity curve (derived) | not a code table | Runnable via MCP; result asserted equal to the locked engine |
| A2L Line Set Calculator | hvac | Goodman/Amana IOG-4047 · Carrier LLG-R454B-01 · Goodman/Amana IOG-4047, p.1 (changeover cautions) · An R-410A line, and the pressures the cautions print · Carrier R-454B FAQ, Bosch A2L Change Guide, Lennox/York R-454B IOMs | not a code table | Runnable via MCP; result asserted equal to the locked engine |
| A2L Refrigerant Charge Limit Calculator | hvac | UL 60335-2-40 (4th ed) Annex GG · ANSI/ASHRAE 15.2-2024 · ASHRAE 34-2019 Addendum f (LFL values) · IEC 60335-2-40 ed 6 / EN 378 (gravity-only) | UL 60335-2-40 4th ed / ANSI/ASHRAE 15.2-2024 | Runnable via MCP; result asserted equal to the locked engine |
| Outdoor HVAC GFCI Requirement (NEC 210.8(F)) | electrical | NEC 210.8(F), read from the printed books (2020, 2023, 2026) and the 2020 edition's TIA · TIA 20-19 and TIA 23-3, the lineage of the exception itself · Each state's own amendment to 210.8(F), where we hold it · Each state's own current-code listing, for what is in force today · The NEC adoption table, for the edition shown where the tool holds no state amendment · The state documents this tool answers from · NFPA's documents on 210.8(F) · The adoption table's documents this page shows | the edition each state enforces on the job date: the NEC 2020, 2023 or 2026 text of 210.8(F), as that state amends it | Runnable via MCP; result asserted equal to the locked engine |
| BTU / HVAC Load Calculator | hvac | ACCA Manual J (simplified): the load model · ACCA Manual S, Table N2-1: the equipment-fit window · IECC 2021 climate zones (the zone boundaries only) · ACCA Manual S (equipment fit) · NREL/TP-5500-60801 (November 2014): the oversizing energy penalty, and its scope · ENERGY STAR Room Air Conditioner sizing table | not a code table | Reference engine (not runnable via MCP) |
| Solar Backfeed Breaker Calculator (NEC 705.12) | electrical | NEC 705.12(B)(2) · NEC 705.12(B)(1) · NEC 408.36 · NEC 240.6(A) | NEC 2023 | Runnable via MCP; result asserted equal to the locked engine |
| Sub-Panel Wire Size Calculator | electrical | NEC Table 310.16 · NEC Table 250.122 · NEC 240.6(A) · NEC Chapter 9 and 215.2(A) · NEC 215.6, 408.40, and 250.24 · NEC 250.32 | NEC 2023 | Reference engine (not runnable via MCP) |
| Neutral Current-Carrying Conductor | electrical | NEC 2023 310.15(E), neutral conductor · NEC 2023 310.15(F), grounding or bonding conductor · NEC 2023 Table 310.15(C)(1) and its footnote · NEC 2023 Table 310.16, Equation 310.15(B)(1) and 110.14(C) | NEC 2023 | Reference engine (not runnable via MCP) |
| Tap Conductor Calculator | electrical | NEC 2023 240.21(B)(1) through (B)(5), feeder taps · NEC 2023 240.21(B) preamble, no next-size rounding on a tap · NEC 2023 240.21(C)(2) through (C)(6), transformer secondary conductors · NEC 2023 240.1, the 1000 volt scope · NEC 310.15(B) and 310.15(C), not applied here · NEC Table 310.16, allowable ampacities | NEC 2023 | Reference engine (not runnable via MCP) |
| Transformer OCPD Calculator | electrical | NEC 2023 450.1, the transformers Article 450 does not cover · NEC 2023 450.3(B) and Table 450.3(B), with Notes 1, 2 and 3 · NEC 2023 240.6(A) and Table 240.6(A), standard ampere ratings · NEC 2023 240.4(F) and 240.21(C)(1), primary-only protection | NEC 2023 | Reference engine (not runnable via MCP) |
| Three-Phase Motor Calculator | electrical | NEC 2023 Table 430.250, Full-Load Current, Three-Phase AC Motors · NEC 2023 Table 430.248, Full-Load Currents, Single-Phase AC Motors · NEC 2023 430.6(A)(1), which current to use · NEC 2023 430.22, Table 310.16 and 110.14(C)(1)(a), the conductor · NEC 2023 430.52(C)(1) with Table 430.52(C)(1), and 240.6(A) standard ratings · NEC 2023 240.4(B), 240.4(D) and 250.122(B), the ordinary-circuit rules this page compares against · NEC 2023 240.4(G) and Table 240.4(G), why a motor branch circuit may sit under a larger breaker | NEC 2023 | Reference engine (not runnable via MCP) |
| What Size Breaker Do I Need | electrical | NEC 240.6(A) and 210.20(A) · NEC Table 310.16, 240.4(B) and 240.4(D) · NEC Table 250.122 · NEC 424.4(B), 424.22(B), 110.14(C)(1) and 110.3(B) (fixed electric heat) · NEC 210.19(C) and Table 220.55 · NEC 422.13, 625.41 and 625.42 · NEC Article 440 and Article 430 | NEC 2023 | Reference engine (not runnable via MCP) |
| Conductor Capacity Check | electrical | NEC Table 310.16 · NEC Equation 310.15(B)(1) · NEC Table 310.15(C)(1) · NEC 110.14(C) · NEC 210.19(A)(1) and 210.20(A) · NEC 240.4(D) · NEC 240.6(A) · NEC Table 250.122 · NEC Chapter 9, Table 9 | NEC 2023 | Reference engine (not runnable via MCP) |
| Ampacity Derating Calculator | electrical | NEC Equation 310.15(B)(1) · NEC Table 310.15(B)(1)(1) · NEC 310.15(B)(2) · NEC Table 310.15(C)(1) · NEC Table 310.16 · NEC 110.14(C) · NEC 240.4(D) · NEC 240.6(A) | NEC 2023 | Reference engine (not runnable via MCP) |
| Ground Wire Size Calculator | electrical | NEC Table 250.122 · NEC 250.122(B) · NEC 250.122(A) · NEC Chapter 9, Table 8 · NEC Table 310.16, Table 310.15(B)(1)(1) and Equation 310.15(B)(1), Table 310.15(C)(1), 210.19(A)(1) and 215.2(A)(1) · NEC 240.4(B) and 240.4(D) | NEC 2023 | Reference engine (not runnable via MCP) |
| Next Standard Size Calculator | electrical | NEC Table 240.6(A) · NEC 240.4(B) · NEC 240.4(D), and the reason it outranks the round-up · NEC 240.4(G) and Table 240.4(G): the Article 440 air-conditioning and refrigeration exception · NEC Table 310.16 and 110.14(C) · NEC Table 250.122 | NEC 2023 | Reference engine (not runnable via MCP) |
| Breaker for Wire Gauge Checker | electrical | NEC Table 310.16 and 110.14(C) · NEC 240.4(B), the next-size-up permission and its condition (1) · NEC 240.4(D), the small-conductor limits · NEC Table 240.6(A) | NEC 2023 | Reference engine (not runnable via MCP) |
| Box Picker | electrical | NEC Table 314.16(A) · NEC 314.16(B)(1) · NEC 314.16(B)(2) through (B)(6) | NEC 2023 | Reference engine (not runnable via MCP) |
| Nitrogen Pressure Test Calculator | hvac | NIST standard atmosphere (101,325 Pa) · NIST SP 811 Fahrenheit-to-Rankine offset (459.67) · Gay-Lussac's law (constant volume) | not a code table | Reference engine (not runnable via MCP) |
| Dual-Fuel Switchover Calculator | hvac | 16 CFR 305 Appendix K1 (FTC EnergyGuide), the 3,412 and 100,000 Btu constants · AHRI 210/240 rating conditions, and the defrost correction · EPA ENERGY STAR certified heat pump data (data.energystar.gov), plausibility-filtered · Manufacturer thermostat installer documentation | not a code table | Reference engine (not runnable via MCP) |
| Combustion Air Calculator | hvac | IFGC 2021 Section 304.5, indoor combustion air: the standard method's 50 ft3 per 1,000 Btu/h · IFGC 2021 Section 304.1, outdoor air where indoor air falls short · IFGC 2021 Section 304.6, outdoor opening divisors · IFGC 2021 Section 304.7, combining indoor and outdoor air · IFGC 2021 Sections 304.5.2, 304.5.3, 304.9 and 304.10 | IFGC 2021 Section 304 (NFPA 54 9.3 cited beside it) | Reference engine (not runnable via MCP) |
| Gas Pipe Sizing Calculator | hvac | Chapter 4 of the fuel gas code, which is MANDATORY: Section 402.3 (Sizing) and Section 402.4 (Sizing tables and equations), with the sizing equation, the Cr and Y values, and the three length methods · The published capacity tables, used as a floor under every steel, copper and polyethylene answer at the drop the table is printed for and at any tighter drop, and as the equation's validation set · Copper and polyethylene bores, and CSST capacities, read from the code's own tables · Section 402.6 of the fuel gas code, the pressure at each appliance inlet · An appliance's input, where a unit's page opens this worksheet: the maker's own row for that model · The appendix's own worked examples, used as an independent check · Appendix A, which says in its own first line that it is INFORMATIVE and not part of the code | no single edition: the fuel gas code family (IFGC, IRC, NFPA 54 or UPC) is chosen on the page and each is cited by its own address | Reference engine (not runnable via MCP) |
| Manual J Load Calculator | hvac | ACCA Manual J, 8th Edition, Abridged Edition (MJ8AE), Form J1 and Form J1ae · ASHRAE Handbook of Fundamentals 2021, Chapter 14, climatic design conditions · US Census Bureau 2020 Gazetteer Files, ZIP Code Tabulation Areas (ZCTA5) | ACCA Manual J 8th Edition (the load procedure) with the ASHRAE Handbook of Fundamentals 2021 Chapter 14 design conditions; not a code table | Runnable via MCP; result asserted equal to the locked engine |
| CFM Calculator | hvac | Standard-air sensible-heat basis (1.08) · ACCA 400 CFM per ton airflow rule | not a code table | Reference engine (not runnable via MCP) |
| Duct Size Calculator | hvac | ASHRAE Fundamentals duct-friction model (Darcy-Colebrook) · ASHRAE Fundamentals 21.3.1 equivalent diameter (Huebscher) · Standard manufactured duct sizes (McGill AirFlow / SMACNA) · ACCA's friction rate range, and the advisory starting rate and velocity bands (secondary sources) | not a code table | Reference engine (not runnable via MCP) |
| Round to Rectangular Duct Converter | hvac | ASHRAE Fundamentals 21.3.1 equivalent diameter (Huebscher) · Standard manufactured duct sizes (McGill AirFlow / SMACNA) | not a code table | Reference engine (not runnable via MCP) |
| Static Pressure & Friction Rate Calculator | hvac | ACCA Manual D friction-rate relation · Total effective length inputs (Manual D Appendix 3) | not a code table | Reference engine (not runnable via MCP) |
| Furnace Temperature Rise Calculator | hvac | Your unit's rating plate (the temperature rise range) · Carrier Service and Technical Support Manual 440 04 4321 10, gas furnace (F/G)9MXT · Velocity Boiler Works Installer's Information Manual 431570g, Section 20 · The sensible-heat relation, for the airflow figure only · 10 CFR 430.2, for what AFUE is and is not | not a code table | Reference engine (not runnable via MCP) |
| Vacuum Decay Test Calculator | hvac | The installation instructions for your equipment (the hold criterion) · Trane Installer's Guide, Condensing Units, 18-AC98D1-5-EN (4TTR6018-061) · Goodman / Amana Condensing Unit Installation & Service Reference, IOG-4036B, December 2022 · York Installation Manual, R-410A 2-Stage Outdoor Split-System Heat Pump, 5391577-UIM-B-0718 (YZT, HC19B, HL19B) · Rheem / Ruud Variable Speed R-454B Heat Pump Outdoor Units Installation Instructions, 92-110354-01-01 · Carrier 26SCA5 Installation Instructions, 26SCA5-1SI, Edition Date 06/24 · Daikin Room Air Conditioner Installation Manual, 3P740830-1B · Daikin VRV Commissioning Guide (a training handbook, not an installation manual), VRV III Pre-Commissioning Check #3 · NIST Chemistry WebBook, Antoine parameters for water (Bridgeman & Aldrich, 1964) · The manufacturer installation books these steps quote | not a code table | Reference engine (not runnable via MCP) |
| EPA Refrigerant Leak Rate Calculator | hvac | 40 CFR 84.106 (AIM Act HFC leak repair) · 40 CFR 84.102 (Leak rate definition) · 40 CFR 84.108 (Automatic leak detection) · 40 CFR 82.157 (Section 608) and part 84 GWP tables · 89 FR 82700 (data center cooling is comfort cooling for ER&R) and 40 CFR 84.54(c)(13) · R-515B composition: 85 FR 79863 at 79865 and 79869 (SNAP listing), ASHRAE 34 designations, Honeywell DS-21-12-EN · The federal rules the refrigerant lines cite | not a code table | Reference engine (not runnable via MCP) |
| Chiller Purge Pump-Out Leak Check | hvac | Trane CTV-SVX05H-EN (August 2020), page 7, Figure 2 · Trane CTV-SVX05H-EN, page 8: what the figure does not give · Trane CVHE-SVX02P-EN (October 2019), CVHE, CVHF, and CVHG Water-Cooled CenTraVac Chillers, Installation, Operation, and Maintenance: Leak Checking Based on Purge Pump Out Time, page 91 · 40 CFR 82.157(a) and 84.106(a)(3)(i); Table 1 to 84.64(b) · The federal rules the refrigerant lines cite | not a code table | Reference engine (not runnable via MCP) |
| Refrigerant Blend Top-Off Check | hvac | Chemours Opteon and Freon product information sheets · Chemours temperature-glide bulletin and the 407C/407A bulletin C-11261 · Chemours Freon 407C Retrofit Guidelines C-11107, Influence of Leak/Recharge on Performance · Chemours Opteon FAQ C-10677; Honeywell Solstice N40 and N15 data sheets · 40 CFR 84.106(b) · This site's CoolProp 8.0.0 run (2026-09-07), for the R-450A glide check only | not a code table | Reference engine (not runnable via MCP) |
| R-134a Chiller Retrofit Eligibility | hvac | EPA SNAP, Substitutes in Centrifugal Chillers (page last updated March 19, 2026) · Johnson Controls / YORK SI0389 (226) and SI0390 (919) · Chemours Opteon XP10 Retrofit Guidelines C-10302 (11/15) and Product Information C-10020; Honeywell R-513A chiller retrofit guide (2023) · Chemours Opteon XP30 C-10864; AGC AMOLEA 1224yd Technical Information (2019); Honeywell Solstice N13 retrofit guideline · This site's CoolProp 8.0.0 cycle model, and 40 CFR 84.106(b) and 84.54 · The federal rules the refrigerant lines cite | not a code table | Reference engine (not runnable via MCP) |
| Chiller Condenser Approach Temperature | hvac | Trane CVHH-SVX001J-EN (October 2019), CVHH Water-Cooled CenTraVac Chillers With Tracer AdaptiView Control, Installation, Operation, and Maintenance: Recommended Maintenance, Condenser, page 110 · YORK Form 160.75-O1 (425), Issue Date 2025-04-24, Model YK Style G with R-134a, R-513A, or R-1234ze, Operations Guide: Operating log sheet (page 16) and Daily inspections (page 17) · This site's PT tables (the superheat and subcooling engine), for saturation from pressure · The effectiveness-NTU algebra, re-run by this site on 2026-09-08 (the derivation behind the illustration table) · Trane CTV-SVX05H-EN Figure 2, through the purge tool · Johnson Controls / YORK SI0389 (226), the YK R-134a to R-513A conversion bulletin | not a code table | Reference engine (not runnable via MCP) |
| Tonnage From Model Number | hvac | The BTU/1000 capacity ladder (024 = 2 tons) · Per-brand model nomenclature (fixed capacity position) · The forms each capacity position is read from, and the refusals they force · Mini split direct BTU class, and the LG single-zone legend that is not one · The independent capacity backtest (AHRI Certification Directory) · The packaged and light commercial lines and the maker forms behind them · Furnace heating size codes, the estimate fallback, and when the tool refuses · Maker documents behind series this tool decodes or estimates, and air handlers it gives no tonnage for · The manufacturer documents that identify these models | not a code table | Reference engine (not runnable via MCP) |
| HVAC Serial Number Lookup | hvac | What each date-code scheme rests on · The documents behind those checks · Carrier family and the ICP reversal · Trane, Goodman, Lennox, Allied, Rheem, York date codes · Refrigerant era and warranty context by year · The federal rules the refrigerant lines cite · Two York documents that bound a York serial's date · The manufacturer documents that identify these models · The warranty statutes this tool reads · EPA's ENERGY STAR certified heat pump list · 10 CFR 430.32(c)(6), the regional efficiency rule the service brief's region line reads · The warranty certificates the warranty lines rest on · The gas furnace warranty certificates the furnace lines rest on · Which of these documents also date furnaces · U.S. Consumer Product Safety Commission recall notices (the recall lines) · Lawrence Berkeley National Laboratory's lifetime study (the lifespan line) · The secondary references these rules are compiled from | not a code table | Reference engine (not runnable via MCP) |
| Water Heater Age Decoder | hvac | Bradford White: the consumer date-code page and the For the Pro bulletin · A.O. Smith: the Service and Warranty Guide for Contracted Service Providers · A. O. Smith, State and Reliance: the catalogs and spec sheets that print a model's tank size and rated input · Rheem, Ruud and Richmond: Technical Service Bulletin 1207 | not a code table | Reference engine (not runnable via MCP) |
| NEMA Plug & Receptacle Identifier | electrical | Hubbell Configuration Chart (Wiring Device-Kellems) · Leviton Industrial Wiring Devices Catalog · Leviton product pages, straight blade 30A / 50A / 60A · Eaton Arrow Hart colour-coded locking devices selector guide | not a code table | Reference engine (not runnable via MCP) |
| Target Superheat Calculator | hvac | the locked CEC Title 24 RA3.2-2 charging table it was computed from, which agrees cell for cell with one manufacturer piston grid and runs a mean 4.77F above another, on the sixth of the table where any manufacturer check exists | CEC Title 24 Table RA3.2-2 | Reference engine (not runnable via MCP) |
| Panel Schedule | electrical | NEC 408.4(A) · NEC 240.15(A) · City of Bellevue panel schedule forms · NEC 220.5(A) · NEC 220.82(A) · Table 240.6(A) and NEC 210.4(B) · NEC 440.22 · The City of Bellevue's copy of the forms | NEC 2023 | Reference engine (not runnable via MCP) |
| Rough-in Checklist | electrical | NEC 210.8 · NEC 422.5, 2020 edition · NEC 210.12 · NEC 210.11(C) · NEC 210.52 · The states' adopting documents | the edition chosen on the page: the 2020, 2023 or 2026 text of NEC 210.8, 210.11(C), 210.12 and 210.52 (and 422.5, where the 2020 text sends its appliances), without any state's amendment | Reference engine (not runnable via MCP) |
| Pull Box Calculator | electrical | NEC 314.28(A) · NEC 314.28(A)(1) · NEC 314.28(A)(2) · NEC 314.28(A)(3) · NEC 314.28(B) · NEC 314.28(C), (D) and (E) · NEC 314.16 · NEC Chapter 9 Table 4 | NEC 2023 | Reference engine (not runnable via MCP) |
| Material Takeoff | electrical | The readings it reads | each reading's own: every line is a saved reading recomputed by its own tool, which names its edition | Reference engine (not runnable via MCP) |
| Heat Strip Circuit Calculator | electrical | NEC 110.3(B) · NEC 424.4(B) · NEC 240.6(A) · NEC 240.4(B) and 240.4(D) · NEC Table 310.16 and 110.14(C)(1) · NEC 424.22(B) · NEC Table 250.122 | NEC 2023 | Reference engine (not runnable via MCP) |
| Can My Panel Handle It (NEC 220.87) | electrical | NEC 220.87 · NEC 220.57 | NEC 2023 | Reference engine (not runnable via MCP) |
| Service Conductor and GEC Sizer (NEC 310.12) | electrical | NEC 310.12(A) and Table 310.12(A) · NEC Table 310.16, 75°C column · NEC 110.14(C)(1)(a)(3) · NEC Table 250.66, 250.66(A) and 250.66(B) | NEC 2023 | Reference engine (not runnable via MCP) |
| Appliance Circuit Fit Check | electrical | NEC 240.4(B) and 240.4(D), and Table 310.16 at 110.14(C) · NEC 210.19(A)(1), 210.19(A)(2), 210.20(A) and Table 240.6(A) · NEC 210.23, 210.23(B)(1) and 210.23(B)(2) · NEC 422.60(A) · NEC 440.62(B) and 440.62(C) (a room air conditioner) · NEC Table 250.122 | NEC 2023 | Reference engine (not runnable via MCP) |
“Derived from” lists the documents the tool’s own source receipt names, generated from that one receipt so this table and the tool page cannot disagree. Where a tool has no receipt yet, it falls back to that tool’s declared authority phrase and says so by being shorter. “Runnable” means the calculator is exposed at the MCP endpoint, and that before each release an automated check confirms the answer it returns is identical to the one the website’s own engine produces.
A page that opens one of these calculators shares its row. Pages without the trace are not listed here, among them the refrigerant PT charts, which carry their own source receipt; and the furnace code lookup and the heat pump no-heat check, which quote the maker’s document and page for the codes and rules they show.
Where you see it
On each of the 60 calculators in the table above, under the result, there is a line that reads where this number comes from. Open it and you get the trace: the four facts for the exact reading on your screen, stamped with the build that checked it, in the same block and the same order. When an assistant runs one of the 18 that are exposed at the Intry MCP endpoint, its result names the source and how it was checked.