The standard

Intry Verified

A reading from any of the 51 Intry calculators in the table below carries the same four facts, in the same order, across both trades: what it was calculated from, what it was run with, how it was checked, and who has final say. This is the standard, so you can follow any number backwards without taking our word for it.

What it is: a provenance standard, not a badge. Every figure an Intry calculator computes comes from a locked source module, not hand-typed. 30696 automated checks, one suite for the whole site rather than a per-tool count, re-derive the numbers before each deploy from the tables this site transcribed from its cited, published source. This is our own deterministic gate, not a third-party audit.

The four facts on a traced result

Calculated from
The exact authority the number came from: the cited NEC 2023 section for electrical tools, the manufacturer pressure-temperature data for refrigerant tools, the UL 60335-2-40 / ANSI/ASHRAE 15.2-2024 or AHRI-certified NEEP standard for A2L charge limits and cold-climate capacity, the EPA rule (40 CFR) for refrigerant compliance, the ACCA Manual J basis for load sizing, or the bender geometry for a bend. It is reused verbatim from the engine, never re-written for the page.
Run with
The exact inputs the engine consumed for that run: the materials, the terminal ratings, the conditions. A number is only correct given its inputs, so we show them. Nothing the engine did not use appears here.
Checked
How the number is held to its source. Before any deploy, an automated test suite does two things: it re-derives calculated figures from a locked data module so a number cannot be transcribed wrong onto the page, and it source-checks values against what they cite - the NEC section, the manufacturer chart, the federal rule - so a number is held to its real source, not just to itself. It is our own deterministic gate that runs on every update, not a third-party audit, and we say so.
Final say
Who has the last word, in plain terms. Your AHJ and local amendments on an electrical install, the unit nameplate and the manufacturer's charging chart on a refrigerant system, a full Manual J on the actual house. The standard's last line is deliberately not ours.

How a number earns it

Two rules make the standard checkable instead of aspirational. First, derive, never hand-type: every calculated number traces to a locked data module (an NEC table, a manufacturer PT chart), so it cannot be transcribed wrong. Second, declare, never restate: which authority governs a tool is declared once, in one place, so an HVAC result is structurally incapable of claiming the electrical code, and the reverse.

Those rules are enforced by a test suite that runs before every deploy. It does two jobs: it re-derives calculated figures from their locked source so a number cannot be transcribed wrong onto the page, and it source-checks values against the actual source they cite, so a number is held to its real source, not just to itself. When a covered value drifts from its source, or a new calculator ships without registering its check, the build stops and the change never ships. As of the current build that suite holds 30696 checks, and this very page passed through it.

Two things follow. First, a number is held to the code book, spec sheet, or federal rule it actually comes from, not to our own say-so. Second, it stays that way: the same gate runs on every future update, and every new calculator has to register its check before it can go live. This is our own deterministic gate, run on every build. It is not a third-party audit, and it is not a certificate on any one reading: your AHJ, the unit nameplate, and a full Manual J still have the last word.

The same discipline covers the pictures. On the conduit bending calculator, the interactive 3D bend is not a drawing: every vertex, arc, and mark is re-derived from the same locked engine that computes the marks, and the render is checked against that engine to a millionth of an inch before every deploy. So the pipe you spin, and the flat diagram beside it, cannot drift from the numbers they are built on.

Intry Verified · Build E989BC2 · 2026-10-06 · 30696 checks passing

The receipt for each traced calculator

One row for each of the 51 calculators whose result carries the Intry Verified trace: the authority its numbers are derived from, the code or data edition they are keyed to, and whether an AI assistant can run the tool and get a result that is checked against the locked engine on every deploy. This table is generated by the same gate it describes, and it is published as machine-readable JSON at /api/verified. The 30696 checks above gate every deploy as one suite; the receipt below adds no per-tool count, because a single check often guards several tools at once.

ToolTradeDerived fromEditionRunnable + result checked vs engine
Wire Size CalculatorelectricalNEC Table 310.16 · NEC 210.19(A) and 210.20(A) · NEC 110.14(C) · NEC 310.15(B)(1) with Table 310.15(B)(1)(1), and Table 310.15(C)(1) · NEC 240.6(A) and 240.4(B) · NEC 240.4(D) · NEC Table 250.122NEC 2023Runnable via MCP; result asserted equal to the locked engine
Voltage Drop CalculatorelectricalNEC Chapter 9, Table 9 · NEC Chapter 9, Table 8 · NEC 210.19 and 215.2 Informational NotesNEC 2023Runnable via MCP; result asserted equal to the locked engine
Conduit Fill CalculatorelectricalNEC Chapter 9, Table 1 · NEC Chapter 9, Table 4 · NEC Chapter 9, Table 5 · NEC Chapter 9, Note 7NEC 2023Runnable via MCP; result asserted equal to the locked engine
Box Fill CalculatorelectricalNEC Table 314.16(B)(1) · NEC 314.16(B)(1) through (B)(6) · NEC Table 314.16(A)NEC 2023Runnable via MCP; result asserted equal to the locked engine
EV Charger Circuit CalculatorelectricalNEC 625.41 and 625.42 · NEC 625.44, 625.54, and 210.21(B)(1) · NEC Table 310.16 · NEC 240.6(A), 240.4(B), 240.4(D), and Table 250.122 · NEC 110.14(C)(1)(a)(3), 334.80 and 250.122(B) · NEC Chapter 9 (voltage drop) and 210.19(A) · NEC Table 310.15(B)(1)(1) and Table 310.15(C)(1) · NEC 750.6, 750.30, and 750.50, energy management systems · NEC 625.42(B) + 750.30(C) + 110.3(B) · NEC 220.60 · NEC 230.79 and NEC 230.42(A)(1) · NEC 230.90 and NEC 240.4 · NEC 210.20(A)NEC 2023Runnable via MCP; result asserted equal to the locked engine
Existing-Load Panel Check (NEC 220.87)electricalNEC 220.82 · NEC 220.87 · NEC 220.57 · NEC 210.20(A) · NEC 240.6(A)NEC 2023Runnable via MCP; result asserted equal to the locked engine
Water Heater Circuit CalculatorelectricalNEC 422.13 · NEC 210.20(A) · NEC Table 310.16 and NEC 110.14(C) · NEC 240.6(A) and 240.4(D) · NEC Table 250.122 · NEC 210.23(B) and 210.23(B)(2) · NEC 210.19(A) and 210.20(A)NEC 2023Runnable via MCP; result asserted equal to the locked engine
120V Induction Range Circuit CalculatorelectricalNEC 210.23(B)(1) and 210.23(B)(2) · NEC 210.21(B)(2) and Table 210.21(B)(2) · NEC 210.20(A) and Article 100 (continuous load) · NEC 210.19(C) · NEC Table 220.55 · NEC Table 310.16, 240.4(D), and Table 250.122 · NEC 110.14(C)(1)(a)(3) and 334.80NEC 2023Runnable via MCP; result asserted equal to the locked engine
Biggest EV Charger Calculator (EVEMS)electricalNEC 220.87 · NEC 220.70 · NEC 625.42 and 750.30 · NEC 210.20(A) and 625.41 · NEC Table 310.16 · NEC 110.14(C)(1)(a)(3) and 334.80 · NEC 240.6(A), 240.4(D), and Table 250.122 · NEC 750.30(C)(1) through (C)(4), and 750.50 · NEC 220.60 · NEC 210.20(A) · NEC 230.90 and NEC 240.4 · NEC 110.3(B)NEC 2023Runnable via MCP; result asserted equal to the locked engine
Conduit Bending CalculatorelectricalBender-manufacturer offset multiplier table · Bend geometry (trigonometry) · Bender-manufacturer 3-point saddle table · Bender-manufacturer shrink-per-inch table · Hand-bender take-up (EMT) and gain (every type)NEC 2023 Chapter 9 Table 2 (minimum bend radii), for the feasibility check only; the bend math is geometry and the bender maker's chartRunnable via MCP; result asserted equal to the locked engine
MCA & MOCP Breaker CalculatorhvacNEC 440.33, 440.34, 440.35 and 430.24 · NEC 440.22, 440.22(A) and 440.22(B)(1) · NEC 240.6(A) · NEC 240.4(G) (Article 440) · NEC 440.1, 440.21, 424.4(B) and 424.19 (a circuit with no compressor) · NEC 310.15(B)(1) and 310.15(C)(1) · NEC 310.15(B)(2) · NEC 110.14(C) · NEC 440.14, 440.12 and 110.26(A) · NEC 440.52 · NEC Table 310.16 · NEC Table 250.122 · NEC 440.4(B) and 110.3(B) · NEC Chapter 9 (voltage drop) and 210.19(A)NEC 2023Runnable via MCP; result asserted equal to the locked engine
A2L Changeout Circuit CheckhvacNEC 440.4(B) and 110.3(B) · NEC 440.35 and 440.4(B) · NEC Table 310.16 · NEC 310.15(B)(1) and 310.15(C)(1) · NEC 310.15(B)(2) · NEC 110.14(C) · NEC 440.22, 440.22(A) and 440.22(B) · NEC 240.6(A) · NEC 240.4(G) (Article 440) · NEC 440.14, NEC 440.12 and NEC 110.26(A)NEC 2023Reference engine (not runnable via MCP)
Superheat & Subcooling CalculatorhvacCEC-400-2022-010-AP, Reference Appendix RA3 Table RA3.2-1 (Installer Testing at Final) · CEC-400-2022-010-AP, Reference Appendix RA3 Table RA3.2-2 (target superheat) · CEC-400-2022-010-AP, Joint Appendix JA6.1.6.3 (the airflow precondition) · Carrier PH5SAN5, Carrier SM10-R454B-03, Carrier 25SCA5, Goodman IOG-4048C, ICP 428 01 5106 00, Trane 88-M5MHWUN-1A-EN, Rheem RD16AY, and Bosch service literature · The per-machine charge-target corpus (registered manufacturer books, cited by form number) · The heat pump's heating-mode check (each maker's own heat pump book, cited by form number and page) · York ST-022-12, Figures 1 and 2 (example charging charts) · Rheem RD16AY / RD18AY section 5.7, and Lennox 13ACX 506374-01 page 20 · Copeland discharge-temperature guidance, and Proctor Engineering on airflow and capacity · The manufacturer installation books these steps quoteCEC Title 24 Tables RA3.2-1 (installer compliance criteria) and RA3.2-2 (fixed-orifice target superheat); the rest is manufacturer data and physicsRunnable via MCP; result asserted equal to the locked engine
Cold-Climate Heat Pump Capacity CalculatorhvacAHRI-certified NEEP ccASHP database · Manufacturer submittal · Linear interpolation of the MAX-capacity curve (derived)not a code tableRunnable via MCP; result asserted equal to the locked engine
A2L Line Set CalculatorhvacGoodman/Amana IOG-4047 · Carrier LLG-R454B-01 · Goodman/Amana IOG-4047, p.1 (changeover cautions) · An R-410A line, and the pressures the cautions print · Carrier R-454B FAQ, Bosch A2L Change Guide, Lennox/York R-454B IOMsnot a code tableRunnable via MCP; result asserted equal to the locked engine
A2L Refrigerant Charge Limit CalculatorhvacUL 60335-2-40 (4th ed) Annex GG · ANSI/ASHRAE 15.2-2024 · ASHRAE 34-2019 Addendum f (LFL values) · IEC 60335-2-40 ed 6 / EN 378 (gravity-only)UL 60335-2-40 4th ed / ANSI/ASHRAE 15.2-2024Runnable via MCP; result asserted equal to the locked engine
Outdoor HVAC GFCI Requirement (NEC 210.8(F))electricalNEC 2023 and NEC 2020, 210.8(F), read from the printed book · TIA 20-19 and TIA 23-3, the lineage of the exception itself · Each state's own amendment to 210.8(F), where we hold it · Each state's own current-code listing, for what is in force today · The compiled adoption dataset, published as the weaker sourceNEC 2023Runnable via MCP; result asserted equal to the locked engine
BTU / HVAC Load CalculatorhvacACCA Manual J (simplified): the load model · ACCA Manual S, Table N2-1: the equipment-fit window · IECC 2021 climate zones (the zone boundaries only) · ACCA Manual S (equipment fit) · NREL/TP-5500-60801 (November 2014): the oversizing energy penalty, and its scope · ENERGY STAR Room Air Conditioner sizing tablenot a code tableReference engine (not runnable via MCP)
Solar Backfeed Breaker Calculator (NEC 705.12)electricalNEC 705.12(B)(2) · NEC 705.12(B)(1) · NEC 408.36 · NEC 240.6(A)NEC 2023Runnable via MCP; result asserted equal to the locked engine
Sub-Panel Wire Size CalculatorelectricalNEC Table 310.16 · NEC Table 250.122 · NEC 240.6(A) · NEC Chapter 9 and 215.2(A) · NEC 215.6, 408.40, and 250.24 · NEC 250.32NEC 2023Reference engine (not runnable via MCP)
Neutral Current-Carrying ConductorelectricalNEC 2023 310.15(E), neutral conductor · NEC 2023 310.15(F), grounding or bonding conductor · NEC 2023 Table 310.15(C)(1) and its footnote · NEC 2023 Table 310.16, Equation 310.15(B)(1) and 110.14(C)NEC 2023Reference engine (not runnable via MCP)
Tap Conductor CalculatorelectricalNEC 2023 240.21(B)(1) through (B)(5), feeder taps · NEC 2023 240.21(B) preamble, no next-size rounding on a tap · NEC Table 310.16, allowable ampacitiesNEC 2023Reference engine (not runnable via MCP)
Transformer OCPD CalculatorelectricalNEC 2023 450.3(B) and Table 450.3(B), with Notes 1, 2 and 3 · NEC 2023 240.6(A) and Table 240.6(A), standard ampere ratings · NEC 2023 240.4(F) and 240.21(C)(1), primary-only protectionNEC 2023Reference engine (not runnable via MCP)
Three-Phase Motor CalculatorelectricalNEC 2023 Table 430.250, Full-Load Current, Three-Phase AC Motors · NEC 2023 Table 430.248, Full-Load Currents, Single-Phase AC Motors · NEC 2023 430.6(A)(1), which current to use · NEC 2023 430.22, Table 310.16 and 110.14(C)(1)(a), the conductor · NEC 2023 430.52(C)(1) with Table 430.52, and 240.6(A) standard ratings · NEC 2023 240.4(G) and Table 240.4(G), why a motor branch circuit may sit under a larger breakerNEC 2023Reference engine (not runnable via MCP)
What Size Breaker Do I NeedelectricalNEC 240.6(A) and 210.20(A) · NEC Table 310.16, 240.4(B) and 240.4(D) · NEC Table 250.122 · NEC 424.4(B), 424.22(B), 110.14(C)(1) and 110.3(B) (fixed electric heat) · NEC 210.19(C) and Table 220.55 · NEC 422.13, 625.41 and 625.42 · NEC Article 440 and Article 430NEC 2023Reference engine (not runnable via MCP)
Conductor Capacity CheckelectricalNEC Table 310.16 · NEC Equation 310.15(B)(1) · NEC Table 310.15(C)(1) · NEC 110.14(C) · NEC 210.19(A)(1) and 210.20(A) · NEC 240.4(D) · NEC 240.6(A) · NEC Table 250.122 · NEC Chapter 9, Table 9NEC 2023Reference engine (not runnable via MCP)
Ampacity Derating CalculatorelectricalNEC Equation 310.15(B)(1) · NEC Table 310.15(B)(1)(1) · NEC 310.15(B)(2) · NEC Table 310.15(C)(1) · NEC Table 310.16 · NEC 110.14(C) · NEC 240.4(D) · NEC 240.6(A)NEC 2023Reference engine (not runnable via MCP)
Ground Wire Size CalculatorelectricalNEC Table 250.122 · NEC 250.122(B) · NEC 250.122(A) · NEC Chapter 9, Table 8 · NEC Table 310.16, Table 310.15(B)(1)(1) and Equation 310.15(B)(1), Table 310.15(C)(1), 210.19(A)(1) and 215.2(A)(1) · NEC 240.4(B) and 240.4(D)NEC 2023Reference engine (not runnable via MCP)
Next Standard Size CalculatorelectricalNEC Table 240.6(A) · NEC 240.4(B) · NEC 240.4(D), and the reason it outranks the round-up · NEC 240.4(G) and Table 240.4(G): the Article 440 air-conditioning and refrigeration exception · NEC Table 310.16 and 110.14(C) · NEC Table 250.122NEC 2023Reference engine (not runnable via MCP)
Box PickerelectricalNEC Table 314.16(A) · NEC 314.16(B)(1) · NEC 314.16(B)(2) through (B)(6)NEC 2023Reference engine (not runnable via MCP)
Nitrogen Pressure Test CalculatorhvacNIST standard atmosphere (101,325 Pa) · NIST SP 811 Fahrenheit-to-Rankine offset (459.67) · Gay-Lussac's law (constant volume)not a code tableReference engine (not runnable via MCP)
Dual-Fuel Switchover Calculatorhvac16 CFR 305 Appendix K1 (FTC EnergyGuide), the 3,412 and 100,000 Btu constants · AHRI 210/240 rating conditions, and the defrost correction · EPA ENERGY STAR certified heat pump data (data.energystar.gov), plausibility-filtered · Manufacturer thermostat installer documentationnot a code tableReference engine (not runnable via MCP)
Combustion Air CalculatorhvacIFGC 2021 Section 304.5, the 50 ft3 per 1,000 Btu/h confined-space threshold · IFGC 2021 Section 304.1, outdoor air where indoor air falls short · IFGC 2021 Section 304.6, outdoor opening divisors · IFGC 2021 Section 304.7, combining indoor and outdoor air · IFGC 2021 Sections 304.5.2, 304.5.3, 304.9 and 304.10IFGC 2021 Section 304 (NFPA 54 9.3 cited beside it)Reference engine (not runnable via MCP)
Gas Pipe Sizing CalculatorhvacChapter 4 of the fuel gas code, which is MANDATORY: the sizing equation, the Cr and Y values, and the three length methods · The published capacity tables, used as a floor under every steel, copper and polyethylene answer at the drop the table is printed for and at any tighter drop, and as the equation's validation set · Copper and polyethylene bores, and CSST capacities, read from the code's own tables · Section 402.6 of the fuel gas code, the pressure at each appliance inlet · The appendix's own worked examples, used as an independent check · Appendix A, which says in its own first line that it is INFORMATIVE and not part of the codeno single edition: the fuel gas code family (IFGC, IRC, NFPA 54 or UPC) is chosen on the page and each is cited by its own addressReference engine (not runnable via MCP)
Manual J Load CalculatorhvacACCA Manual J, 8th Edition, Abridged Edition (MJ8AE), Form J1 and Form J1ae · ASHRAE Handbook of Fundamentals 2021, Chapter 14, climatic design conditions · US Census Bureau 2020 Gazetteer Files, ZIP Code Tabulation Areas (ZCTA5)ACCA Manual J 8th Edition (the load procedure) with the ASHRAE Handbook of Fundamentals 2021 Chapter 14 design conditions; not a code tableRunnable via MCP; result asserted equal to the locked engine
CFM CalculatorhvacHVAC School sensible-heat basis (1.08) · ACCA 400 CFM per ton airflow rulenot a code tableReference engine (not runnable via MCP)
Duct Size CalculatorhvacASHRAE Fundamentals duct-friction model (Darcy-Colebrook) · ASHRAE Fundamentals 21.3.1 equivalent diameter (Huebscher) · Standard manufactured duct sizes (McGill AirFlow / SMACNA) · Advisory design targets (Manual D basis, hvacprosales velocity bands)not a code tableReference engine (not runnable via MCP)
Round to Rectangular Duct ConverterhvacASHRAE Fundamentals 21.3.1 equivalent diameter (Huebscher) · Standard manufactured duct sizes (McGill AirFlow / SMACNA)not a code tableReference engine (not runnable via MCP)
Static Pressure & Friction Rate CalculatorhvacACCA Manual D friction-rate relation · Total effective length inputs (Manual D Appendix 3)not a code tableReference engine (not runnable via MCP)
Furnace Temperature Rise CalculatorhvacYour unit's rating plate (the temperature rise range) · Carrier Service and Technical Support Manual 440 04 4321 10, gas furnace (F/G)9MXT · Velocity Boiler Works Installer's Information Manual 431570g, Section 20 · The sensible-heat relation, for the airflow figure only · 10 CFR 430.2, for what AFUE is and is notnot a code tableReference engine (not runnable via MCP)
Vacuum Decay Test CalculatorhvacThe installation instructions for your equipment (the hold criterion) · Trane Installer's Guide, Condensing Units, 18-AC98D1-5-EN (4TTR6018-061) · Goodman / Amana Condensing Unit Installation & Service Reference, IOG-4036B, December 2022 · York Installation Manual, R-410A 2-Stage Outdoor Split-System Heat Pump, 5391577-UIM-B-0718 (YZT, HC19B, HL19B) · Rheem / Ruud Variable Speed R-454B Heat Pump Outdoor Units Installation Instructions, 92-110354-01-01 · Carrier 26SCA5 Installation Instructions, 26SCA5-1SI, Edition Date 06/24 · Daikin Room Air Conditioner Installation Manual, 3P740830-1B · Daikin VRV Commissioning Guide (a training handbook, not an installation manual), VRV III Pre-Commissioning Check #3 · NIST Chemistry WebBook, Antoine parameters for water (Bridgeman & Aldrich, 1964) · The manufacturer installation books these steps quotenot a code tableReference engine (not runnable via MCP)
EPA Refrigerant Leak Rate Calculatorhvac40 CFR 84.106 (AIM Act HFC leak repair) · 40 CFR 84.102 (Leak rate definition) · 40 CFR 84.108 (Automatic leak detection) · 40 CFR 82.157 (Section 608) and part 84 GWP tables · 89 FR 82700 (data center cooling is comfort cooling for ER&R) and 40 CFR 84.54(c)(13) · R-515B composition: 85 FR 79863 at 79865 and 79869 (SNAP listing), ASHRAE 34 designations, Honeywell DS-21-12-EN · The federal rules the refrigerant lines citenot a code tableReference engine (not runnable via MCP)
Chiller Purge Pump-Out Leak CheckhvacTrane CTV-SVX05H-EN (August 2020), page 7, Figure 2 · Trane CTV-SVX05H-EN, page 8: what the figure does not give · Trane CVHE-SVX02P-EN (October 2019), CVHE, CVHF, and CVHG Water-Cooled CenTraVac Chillers, Installation, Operation, and Maintenance: Leak Checking Based on Purge Pump Out Time, page 91 · 40 CFR 82.157(a) and 84.106(a)(3)(i); Table 1 to 84.64(b) · The federal rules the refrigerant lines citenot a code tableReference engine (not runnable via MCP)
Refrigerant Blend Top-Off CheckhvacChemours Opteon and Freon product information sheets · Chemours temperature-glide bulletin and the 407C/407A bulletin C-11261 · Chemours Freon 407C Retrofit Guidelines C-11107, Influence of Leak/Recharge on Performance · Chemours Opteon FAQ C-10677; Honeywell Solstice N40 and N15 data sheets · 40 CFR 84.106(b) · This site's CoolProp 8.0.0 run (2026-09-07), for the R-450A glide check onlynot a code tableReference engine (not runnable via MCP)
R-134a Chiller Retrofit EligibilityhvacEPA SNAP, Substitutes in Centrifugal Chillers (page last updated March 19, 2026) · Johnson Controls / YORK SI0389 (226) and SI0390 (919) · Chemours Opteon XP10 Retrofit Guidelines C-10302 (11/15) and Product Information C-10020; Honeywell R-513A chiller retrofit guide (2023) · Chemours Opteon XP30 C-10864; AGC AMOLEA 1224yd Technical Information (2019); Honeywell Solstice N13 retrofit guideline · This site's CoolProp 8.0.0 cycle model, and 40 CFR 84.106(b) and 84.54 · The federal rules the refrigerant lines citenot a code tableReference engine (not runnable via MCP)
Chiller Condenser Approach TemperaturehvacTrane CVHH-SVX001J-EN (October 2019), CVHH Water-Cooled CenTraVac Chillers With Tracer AdaptiView Control, Installation, Operation, and Maintenance: Recommended Maintenance, Condenser, page 110 · YORK Form 160.75-O1 (425), Issue Date 2025-04-24, Model YK Style G with R-134a, R-513A, or R-1234ze, Operations Guide: Operating log sheet (page 16) and Daily inspections (page 17) · This site's PT tables (the superheat and subcooling engine), for saturation from pressure · The effectiveness-NTU algebra, re-run by this site on 2026-09-08 (the derivation behind the illustration table) · Trane CTV-SVX05H-EN Figure 2, through the purge tool · Johnson Controls / YORK SI0389 (226), the YK R-134a to R-513A conversion bulletinnot a code tableReference engine (not runnable via MCP)
Tonnage From Model NumberhvacThe BTU/1000 capacity ladder (024 = 2 tons) · Per-brand model nomenclature (fixed capacity position) · The forms each capacity position is read from, and the refusals they force · Mini split direct BTU class, and the LG single-zone legend that is not one · The independent capacity backtest (AHRI Certification Directory) · The packaged and light commercial lines and the maker forms behind them · Furnace MBH exclusion, the estimate fallback, and when the tool refuses · Maker documents behind series this tool decodes or estimates, and air handlers it gives no tonnage for · The manufacturer documents that identify these modelsnot a code tableReference engine (not runnable via MCP)
HVAC Serial Number LookuphvacWhat each date-code scheme rests on · How the decoder is checked against dated serials · The documents behind those checks · Carrier family and the ICP reversal · Trane, Goodman, Lennox, Allied, Rheem, York date codes · Ambiguous and non-encoded formats · Refrigerant era and warranty context by year · The federal rules the refrigerant lines cite · Two York documents that bound a York serial's date · The manufacturer documents that identify these models · The warranty certificates the warranty lines rest on · The gas furnace warranty certificates the furnace lines rest on · Which of these documents also date furnaces · U.S. Consumer Product Safety Commission recall notices (the recall lines) · The secondary references these rules are compiled fromnot a code tableReference engine (not runnable via MCP)
Water Heater Age DecoderhvacBradford White: the consumer date-code page and the For the Pro bulletin · Rheem, Ruud and Richmond: Technical Service Bulletin 1207not a code tableReference engine (not runnable via MCP)
NEMA Plug & Receptacle IdentifierelectricalHubbell Configuration Chart (Wiring Device-Kellems) · Leviton Industrial Wiring Devices Catalog · Leviton product pages, straight blade 30A / 50A / 60A · Eaton Arrow Hart colour-coded locking devices selector guidenot a code tableReference engine (not runnable via MCP)
Target Superheat Calculatorhvacthe locked CEC Title 24 RA3.2-2 charging table it was computed from, which agrees cell for cell with one manufacturer piston grid and runs a mean 4.77F above another, on the sixth of the table where any manufacturer check existsCEC Title 24 Table RA3.2-2Reference engine (not runnable via MCP)

“Derived from” lists the documents the tool’s own source receipt names, generated from that one receipt so this table and the tool page cannot disagree. Where a tool has no receipt yet, it falls back to that tool’s declared authority phrase and says so by being shorter. “Runnable” means the calculator is exposed at the MCP endpoint, and that before each release an automated check confirms the answer it returns is identical to the one the website’s own engine produces.

A page that opens one of these calculators shares its row. Pages without the trace are not listed here, among them the fixed electric heat calculator for heat strips and electric furnaces, which prints its NEC sections on its own result; the refrigerant PT charts, which carry their own source receipt; and the furnace code lookup and the heat pump no-heat check, which quote the maker’s document and page for the codes and rules they show.


Where you see it

On each of the 51 calculators in the table above, under the result, there is a line that reads where this number comes from. Open it and you get the trace: the four facts for the exact reading on your screen, stamped with the build that checked it, in the same block and the same order. When an assistant runs one of the 18 that are exposed at the Intry MCP endpoint, its result names the source and how it was checked.

Intry Pro, coming soon, keeps the source beside each number Intry calculates in a job record. See Intry Pro ›