NEC Table 314.16

What Size Box Do I Need?

Tell it what is going in the box. It names the box to buy, what it leaves you, and whether it still fits when the next device goes in. Computed from NEC 314.16.

Count a conductor that passes through once, and a loop or coil of unbroken conductor at least twice the free length 300.14 requires as two (314.16(B)(1)).

Add a second conductor size (a switch leg, a travellers pair)

NEC 314.16(B)(1) allows each conductor at its own size, but this picker charges the yokes, the clamps, the grounds and the terminal blocks at the LARGEST conductor in the box (the code takes a yoke at the largest conductor connected to it, the grounds at the largest ground and a terminal block at the largest conductor on it, none of them larger), so mixing sizes costs more than it looks.

A device wider than a single 2 in. device box counts as one device for each gang it needs (314.16(B)(4)). Ground wires are counted at the largest conductor above; if a ground is larger than every conductor listed, use the box fill calculator, which asks for its size.

All the clamps together take ONE allowance, at the largest conductor present (314.16(B)(2)).

Terminal blocks and fixture fittings

Each type of fitting takes one allowance at the largest conductor present (314.16(B)(3)).

22.5 cubic inches of fill, NEC 314.16(B)
FITS, BUT NOT ANOTHER DEVICE
FD double
24 cu in · 1.5 cu in spare · 94% full
shape: FD double · no device box in Table 314.16(A) holds this
27cu in with
one more device

Adding one more device breaks this box. One more yoke takes the fill to 27 cubic inches against the FD double’s 24, so a second device does not go in this one. If there is any chance of one more device here, buy the 4-11/16x1-1/2 square (29.5 cu in) instead and it costs you pennies today rather than a second trip later.

Show the math
  1. GIVENThe largest conductor in the box, by its Table 314.16(B)(1) allowance: #12 AWG; every yoke, clamp, ground wire, terminal block and fitting is charged at it
  2. MATH#12 conductors: 6 × 2.25 = 13.5 cu inNEC 314.16(B)(1), Table 314.16(B)(1)
  3. MATH#14 conductors: 0 × 2 = 0 cu inNEC 314.16(B)(1), Table 314.16(B)(1)
  4. MATHDevice yokes: 1 × 4.5 = 4.5 cu inNEC 314.16(B)
  5. MATHInternal clamps (all): 1 × 2.25 = 2.25 cu inNEC 314.16(B)
  6. MATHEquipment grounding (all): 1 × 2.25 = 2.25 cu inNEC 314.16(B)
  7. RESULTFill required: 22.5 cu inNEC 314.16(B)
  8. RESULTThe smallest printed box that holds it: FD double, 24 cu in, 1.5 cu in spareNEC Table 314.16(A)
  9. RESULTWith one more device: 27 cu in, held by 4-11/16x1-1/2 square (29.5 cu in)NEC 314.16(B)(4)

Device yokes take two allowances each at the largest conductor connected to them (314.16(B)(4)); all internal clamps together take one (314.16(B)(2)); up to four grounds take one between them, with a quarter allowance for each one after that (314.16(B)(5)). This picker charges each of them at the largest conductor you entered, which is never smaller than the code’s size for a yoke or a clamp; for a ground larger than every conductor, use the box fill calculator.

Where this number comes fromIntry Verified
Calculated from
NEC 314.16(B) volume allowances against the box volumes printed in NEC Table 314.16(A). Computed from the NEC 314.16(B) volume allowances for your conductors, devices, clamps and grounds, ranked against the box volumes printed in NEC Table 314.16(A). See the full receipt ↓
Run with
  • Conductors6 x #12 AWG
  • Devices1
  • Ground wires2
  • Internal clampsyes
  • Fill required22.5 cu in
Checked
Every figure an Intry calculator computes comes from a locked source module, not hand-typed. 35,938 automated checks, one suite for the whole site rather than a per-tool count, re-derive the numbers before each deploy from the tables this site holds, read from the cited NEC section. This is our own deterministic gate, not a third-party audit.
Final say
Your AHJ and local amendments have final say. Confirm before rough-in.
What Intry Verified means

Intry Verified · NEC 2023 · Build 525536D · 2026-11-13

Every box NEC Table 314.16(A) prints, ranked against this make-up’s 22.5 cubic inches. Boxes that hold it come first, smallest first, because the smallest box that fits is the one you buy.

Swipe the table sideways to see the rest of its columns. →

BoxShapeVolumeSpareFullOne more device
FD doubleFD double241.594%no
4-11/16x1-1/4 squaresquare25.5388%no
4-11/16x1-1/2 squaresquare29.5776%yes
4x2-1/8 squaresquare30.37.874%yes
4-11/16x2-1/8 squaresquare4219.554%yes
3x2x1-1/2 devicedevice7.5-15300%–
3x2x2 devicedevice10-12.5225%–
4x2-1/8x1-1/2–10.3-12.2218%–
3x2x2-1/4 devicedevice10.5-12214%–
3x2x2-1/2 devicedevice12.5-10180%–
4x1-1/4 round/octagonalround/octagonal12.5-10180%–
4x2-1/8x1-7/8–13-9.5173%–
FS singleFS single13.5-9167%–
3x2x2-3/4 devicedevice14-8.5161%–
masonry 3-3/4x2x2-1/2masonry14-8.5161%–
4x2-1/8x2-1/8–14.5-8155%–
4x1-1/2 round/octagonalround/octagonal15.5-7145%–
3x2x3-1/2 devicedevice18-4.5125%–
4x1-1/4 squaresquare18-4.5125%–
FD singleFD single18-4.5125%–
FS doubleFS double18-4.5125%–
4x1-1/2 squaresquare21-1.5107%–
masonry 3-3/4x2x3-1/2masonry21-1.5107%–
4x2-1/8 round/octagonalround/octagonal21.5-1105%–

Table 314.16(A) prints different shapes at identical volumes, so where two boxes tie this ranking prefers the shape that suits what is going in: a device box when there is a yoke, a round or octagonal box when there is a luminaire stud or hickey. That preference only ever breaks ties, and it can never promote a box that does not fit.

These are the METAL box volumes. NEC Table 314.16(A) is titled Metal Boxes, and a nonmetallic box of the same nominal dimensions can be a different volume. Every nonmetallic box, and any box of 100 cubic inches or less not on this table, is required to be durably marked with its own cubic-inch capacity (314.16(A)(2)), and that marking governs over anything here. Read the box.

314.16 is a volume rule and nothing else. It does not check the six inches of free conductor 300.14 requires at each opening, whether the yoke and the wirenuts physically clear the box, or how the cable clamps eat the corners. A box that passes here at 95 percent is legal and still a brutal make-up, which is what the “one more device” column is for.

22.5 cu inFD double
Run this in your AI. Ask Claude or ChatGPT to add up the box fill for a device box with three 12 AWG and two 14 AWG conductors and it runs the Intry Box Fill Calculator live, handing back the verdict with its cited source instead of a guess. Then keep the reading as one job in the Intry app.

Intry Verified. The volumes and box sizes the calculator on this page returns are rendered from the same module our box fill calculator computes from, cited to NEC 314.16(B)(1) and 314.16(A) (NFPA 70-2023). Allowances quoted in the FAQ and the surrounding copy are read from the same printed table rather than computed. Confirm the edition your jurisdiction has adopted; a listed box marked with its own volume governs instead. Those figures are computed by a locked engine straight from the source it cites, not hand-typed, and that computation re-runs inside a deterministic test on every deploy. Source-checked. Locked. This is our own deterministic gate, not a third-party audit. What Intry Verified means


The Six Things That Count

Box fill is the sum of six categories, each from NEC 314.16(B), and the total must stay at or below the box volume from 314.16(A):

  • Conductors (B)(1): each conductor that runs through or terminates counts as one volume at its own size. A conductor that only passes through counts once. A loop or coil of unbroken conductor at least twice the free length 300.14 requires counts as two conductor volumes.
  • Clamps (B)(2): all internal cable clamps together count as one volume at the largest conductor in the box.
  • Support fittings (B)(3): one volume for each type present (a luminaire stud, a hickey) at the largest conductor in the box.
  • Devices (B)(4): each yoke or strap (receptacle, switch) counts as two volumes at the largest conductor connected to it, and a device wider than a single 2 in. device box counts two for each gang it needs.
  • Grounds (B)(5): all equipment grounding conductors together count as one volume at the largest ground, covering up to four EGCs; each additional EGC beyond four adds another 1/4 of that largest-ground volume.
  • Terminal blocks (B)(6): one volume for each terminal block, at the largest conductor terminated on it.

Worked Example

Device box with two 12-2 cables, one receptacle, internal clamps

#12 conductors: 4 x 2.25 = 9

Device yokes: 1 x 4.5 = 4.5

Internal clamps (all): 1 x 2.25 = 2.25

Equipment grounding (all): 1 x 2.25 = 2.25

Total = 18 cu in

Result: the box must be at least 18 cubic inches. The smallest box NEC Table 314.16(A) prints at or above that is the 3x2x3-1/2 device at 18 cu in, leaving 0 to spare. Add one more device and the same make-up needs 22.5 cubic inches, which takes you to the FD double (24 cu in).


Frequently Asked Questions

What is the box fill volume for #12 wire?

Each #12 conductor counts as 2.25 cubic inches for box fill per NEC Table 314.16(B)(1). A #14 is 2.00, #10 is 2.50, #8 is 3.00, and #6 is 5.00 cubic inches.

What is the box fill volume for #14 wire?

Each #14 conductor counts as 2.00 cubic inches per NEC Table 314.16(B)(1). So a box with six #14 conductors uses 12.0 cubic inches of conductor fill before devices and clamps.

How much box fill does a receptacle or switch take?

Each device yoke (receptacle or switch) counts as two conductor volumes based on the largest conductor connected to it, per NEC 314.16(B)(4). For a device on #12 that is 2 x 2.25 = 4.50 cubic inches.

How do you count grounds in box fill?

All equipment grounding conductors in the box together count as one single conductor volume, based on the largest ground, per NEC 314.16(B)(5). That single volume covers up to four EGCs; each additional EGC beyond four adds another 1/4 of that largest-ground volume. Four #12 grounds still count as just 2.25 cubic inches, not four.

Do cable clamps count toward box fill?

Yes. One or more internal cable clamps together count as one conductor volume based on the largest conductor in the box, per NEC 314.16(B)(2). Cable connectors on the outside of the box do not count.

How many #12 conductors fit in a 4-square box?

A 4 x 1-1/2 inch square box is 21.0 cubic inches (NEC Table 314.16(A)). At 2.25 cubic inches each, it holds up to 9 #12 conductors (21.0 / 2.25 = 9.3) if there are no devices, clamps, or grounds. Each of those subtracts from the count.


Related Calculators & Charts

Know the volumes. Let the calculator do the count.

Box fill is easy to get wrong by one device or ground. The box fill calculator applies the 314.16(B) allowances to what you enter and tells you the minimum box size in cubic inches.