NEC 310.15(B)(1)
Ampacity Derating Calculator
The ambient temperature correction factor at the temperature you actually have. The code prints fifteen 5°C bands plus an open-ended “10 or less” row, and it also prints the equation behind them, so we compute the equation and give you the factor at the ambient you actually have.
Embed the Ampacity Derating Calculator on Your Site
Add it to any website, blog, or training page. One line of code, always the deployed engine, no login, no API key.
- Copy the code below.
- Paste it into any page, post, or CMS (WordPress, Squarespace, Webflow, raw HTML).
- Done. It always runs the currently deployed engine. Keep the credit line so readers know where it comes from.
Correction Factors at 5°F Steps
Computed from Equation 310.15(B)(1) for every 5°F across roughly the span the code’s table spans. The 2023 edition publishes sixteen bands and nothing between them, so this grid is finer than the one it prints. Use the calculator above for a temperature that falls between these rows.
| Ambient °F | Ambient °C | 60°C wire | 75°C wire | 90°C wire |
|---|---|---|---|---|
| 50 | 10.0 | 1.291 | 1.202 | 1.155 |
| 55 | 12.8 | 1.255 | 1.176 | 1.134 |
| 60 | 15.6 | 1.217 | 1.149 | 1.114 |
| 65 | 18.3 | 1.179 | 1.122 | 1.093 |
| 70 | 21.1 | 1.139 | 1.094 | 1.072 |
| 75 | 23.9 | 1.097 | 1.066 | 1.050 |
| 80 | 26.7 | 1.054 | 1.036 | 1.027 |
| 85 | 29.4 | 1.009 | 1.006 | 1.005 |
| 90 | 32.2 | 0.962 | 0.975 | 0.981 |
| 95 | 35.0 | 0.913 | 0.943 | 0.957 |
| 100 | 37.8 | 0.861 | 0.909 | 0.933 |
| 105 | 40.6 | 0.805 | 0.875 | 0.908 |
| 110 | 43.3 | 0.745 | 0.839 | 0.882 |
| 115 | 46.1 | 0.680 | 0.801 | 0.855 |
| 120 | 48.9 | 0.609 | 0.762 | 0.828 |
| 125 | 51.7 | 0.527 | 0.720 | 0.799 |
| 130 | 54.4 | 0.430 | 0.676 | 0.770 |
| 135 | 57.2 | 0.304 † | 0.629 | 0.739 |
| 140 | 60.0 | none | 0.577 | 0.707 |
| 145 | 62.8 | none | 0.521 | 0.674 |
| 150 | 65.6 | none | 0.458 | 0.638 |
| 155 | 68.3 | none | 0.385 | 0.601 |
| 160 | 71.1 | none | 0.294 † | 0.561 |
| 165 | 73.9 | none | 0.157 † | 0.518 |
| 170 | 76.7 | none | none | 0.471 |
| 175 | 79.4 | none | none | 0.419 |
| 180 | 82.2 | none | none | 0.360 |
| 185 | 85.0 | none | none | 0.289 |
Conductor Bundling Adjustment (NEC 310.15(C)(1))
Unlike the ambient correction above, this one has no equation behind it. NEC 310.15(C)(1) sets these values directly, so we cite them rather than compute them. The calculator applies the one that matches your conductor count, and the count is the part people get wrong, so the rules for counting are below.
There is no adjustment for three or fewer current-carrying conductors: at that count you use the ampacity as published. Our calculators carry a 1–3 = 1.00 selection so that “no derating” is something you can pick; it is an input we add, not a factor from NEC 310.15(C)(1).
The count starts at the total number of conductors in the raceway or cable, including spare conductors, and is then adjusted: a neutral that carries only the unbalanced current from the other conductors of the same circuit is not required to be counted (NEC 310.15(E)(1)), and the equipment grounding or bonding conductor is not counted either (NEC 310.15(F)). A neutral taken from a 4-wire 3-phase wye system may be a different case: (E)(2) counts the neutral of a 3-wire circuit of two phase conductors and the neutral of such a system, and (E)(3) counts it on a 4-wire 3-phase wye circuit where the major portion of the load is nonlinear. A 4-wire wye circuit under a mostly linear load is still (E)(1). So which of the three branches your circuit is in settles whether the neutral is in this count at all. Conductors connected to equipment that cannot be energized at the same time are not counted. Leaving spares out lowers the count, which raises the adjustment factor and undersizes the conductor.
Where the Correction Factor Comes From
A conductor’s ampacity is set by how much heat it can shed before the insulation reaches its rating, and the heat it can shed goes with the square root of the temperature difference available to it. NEC 310.15(B)(1) prints that relationship as Equation 310.15(B)(1): I' = I × sqrt((Tc − Ta') / (Tc − Ta)), where Tc is the conductor temperature rating, Ta' is your ambient and Ta is the ambient the table was built on, which is 30°C for Table 310.15(B)(1)(1). The same section says ampacities may be corrected using the table or calculated using the equation.
That is why the two answers track each other so closely: the table is a rounded tabulation of the equation, evaluated at the top of each 5°C band. It is also why the table stops printing a factor for 60°C insulation above 55°C ambient. Once the ambient reaches the conductor’s own rating there is no temperature difference left to carry heat away, the term (Tc − Ta') goes to zero, and the conductor has no ampacity to correct. The dash in the book and the refusal in the calculator are the same statement.
Worked Example
#6 THHN, 108°F attic, 6 current-carrying conductors
Base: #6 THHN at 90°C = 75A (NEC Table 310.16)
Temperature: sqrt((90 − 42.2) / (90 − 30)) = 0.8924
Conductor count: 6 conductors = 0.80 (NEC 310.15(C)(1))
75 × 0.8924 × 0.80 = 53.5A
Result: 53.5A of usable ampacity, well under the 65A that #6 copper carries at the 75°C terminal column, so the derated figure governs. This is why a #6 that looks good for 65A ends up on a 50A load once it is in a hot, crowded raceway.
Frequently Asked Questions
What is the temperature correction factor at 103 degrees F?
At 103 degrees F on 90 C insulation the computed factor is 0.918. NEC Table 310.15(B)(1)(1) puts that temperature in a band and prints 0.91 for it, because each band is evaluated at its hottest end. Both are permitted: 310.15(B)(1) says ampacities may be corrected using the table or calculated using Equation 310.15(B)(1).
Can I calculate a correction factor instead of using the NEC table?
Yes. NEC 310.15(B)(1) states that ampacities for ambient temperatures other than those shown in the ampacity tables shall be corrected in accordance with Table 310.15(B)(1)(1) or Table 310.15(B)(1)(2), or shall be permitted to be calculated using Equation 310.15(B)(1). The equation is I' = I x sqrt((Tc - Ta') / (Tc - Ta)), where Tc is the conductor temperature rating, Ta' is your ambient and Ta is the ambient the table is based on, which is 30 C for Table 310.15(B)(1)(1).
Why does the calculated factor differ from the table?
The table is banded in 5 C steps and each band is evaluated at its hottest end, so a conductor at the cool end of a band is corrected as if it were at the hot end. The equation uses your actual ambient. At the top of a band, wherever the code prints a factor at all, the two agree to two decimals. Below it the calculated factor is larger, which permits a smaller conductor, so use it only when the ambient you entered is the real one.
How do I derate ampacity for more than 3 conductors?
Per NEC 310.15(C)(1), for 4 to 6 current-carrying conductors multiply ampacity by 0.80, for 7 to 9 by 0.70, for 10 to 20 by 0.50, for 21 to 30 by 0.45, for 31 to 40 by 0.40, and for 41 or more by 0.35. The adjustment applies when conductors are bundled longer than 24 inches. This one is a table of values the code sets; there is no equation behind it to compute.
What happens on a rooftop in direct sunlight?
NEC 310.15(B)(2) adds 33 C (60 F) to the outdoor temperature for raceways or cables exposed to direct sunlight where the distance from the roof to the bottom of the raceway is less than 19 mm (3/4 in). Type XHHW-2 conductors are excepted. A 95 F afternoon becomes a 155 F ambient for correction purposes, which is why rooftop runs get spaced off the deck.
Does the neutral count as a current-carrying conductor?
It depends on which of the three printed conditions in NEC 310.15(E) describes the circuit. Under (E)(1) a neutral that carries only the unbalanced current from the other conductors of the same circuit is not required to be counted, which is the case for a 120/240V three-wire circuit as the text is printed. Under (E)(2) the neutral of a 3-wire circuit taken from a 4-wire, 3-phase, wye-connected system is counted. Under (E)(3) the neutral of a 4-wire, 3-phase wye circuit is counted where the major portion of the load consists of nonlinear loads. The NEC prints no percentage for that phrase. The equipment grounding conductor is never counted, under 310.15(F). A 2-wire circuit is a fourth case the three conditions do not name: it has no other conductor to be unbalanced against, so its neutral carries the full load current and (E)(1) does not exclude it. Which branch a circuit falls in is worked out by the neutral current-carrying conductor tool.
Which ampacity column do you start derating from?
Start from the 90 C column of NEC Table 310.16 for THHN, THWN-2, and XHHW-2, apply the correction and adjustment factors, then confirm the derated result does not exceed the 60 C or 75 C terminal rating of the equipment per NEC 110.14(C).
Related Calculators & Charts
Wire Size Calculator
Goes the other way: give it a load and it sizes the conductor, derating included.
Conductor Capacity Check (310.16)
What a conductor already in place carries once this correction is applied, and the device it takes, copper and aluminum at 60/75/90°C.
Conduit Fill Chart
More than three conductors in a raceway triggers both fill limits and the count adjustment.
Sizing a conductor, not just a factor?
The wire size calculator takes the load, pulls the base ampacity, applies temperature and conductor count, and enforces the terminal rating in one pass.
Keep going