Electrical Calculators

Free NEC Electrical Calculators

Organized by the job: adding a big load, sizing wire and breakers, running conduit, and which NEC edition your state enforces. Under each job the calculators, charts, and guides are labeled so you grab the right kind fast. Every code result names the NEC table it used.


Adding a big load? Panel & service capacity

An EV charger, heat pump, water heater, or induction range comes down to one question: can the service take it, and if not, what is the workaround? Start here.

Start here

Can My Panel Handle It?

Adding an EV charger, heat pump, water heater, or induction range? Pick the load and get the exact calculator, plus the NEC 220.87 check and the workarounds that add it without a service upgrade.

Electrical Load Calculator

NEC 220.82 service sizing and the 220.87 existing-load check. Answers the question behind every electrification job: can this panel handle an EV charger or heat pump?

Runs in your AI
New

Tap Conductor Calculator

Feeder taps under NEC 240.21(B). Picks the rule your run falls under, shows the ampacity floors it sets and which one governs, and sizes the conductor from Table 310.16. The 10 ft rule is not one-tenth by default.

Sub-Panel Wire Size Calculator

Feeder conductor, equipment ground, breaker, conduit, and voltage drop for a 60-200A sub-panel per NEC Table 310.16 and 250.122, plus the 4-wire feeder and neutral-isolation rules that pass inspection.

EV Charger Installation Calculator

Size wire, breaker, and panel capacity for Level 2 EV charger installations per NEC 2023 Article 625. Includes GFCI requirements, charging performance, and a parts list for the circuit itself.

Runs in your AI

EV Load Management (Biggest Charger)

The biggest EV charger a service can take by NEC 220.87, and how a load-management device (DCC, Emporia, Wallbox Power Boost, Splitvolt) raises it without a panel upgrade.

Runs in your AI

Heat Pump Water Heater Circuit

Breaker and wire size for every major heat pump water heater line, 240V hybrids and the new 120V plug-in class, plus the NEC 210.23(B)(2) shared-circuit rule.

Runs in your AI

120V Induction Range Circuit

Can a battery-buffered 120V plug-in induction range (Copper, Impulse, Electra) share a circuit? The breaker, wire, and NEC 210.23(B)(1), sized from the wall draw not the burner kW.

Runs in your AI

Can My Panel Handle Solar?

The max solar backfeed breaker your busbar can take by the NEC 705.12 120% rule: 120% of the bus less the main, rounded down to a standard size, with the inverter output it supports.

Runs in your AI

Sizing the heat pump first? Cold-climate heat pump capacity at 5F.


Sizing wire, breakers & circuits

Most popular

Wire Size Calculator

Find the correct wire gauge per NEC 310.16 with temperature derating, bundling adjustment, continuous load support, and NEC 110.14(C) terminal temperature enforcement.

Runs in your AI

Voltage Drop Calculator

Calculate voltage drop percentage for any circuit run length. Includes reverse-solve to find the minimum wire size that meets NEC 3% branch / 5% total recommendations.

Runs in your AI

MCA & MOCP Breaker Calculator

What breaker and wire does this condenser need? Enter the nameplate MCA and MOCP and get the wire size, breaker, ground, and voltage drop per NEC Article 440.

Runs in your AI
New

Transformer OCPD Calculator

Transformer protection under NEC Table 450.3(B). Shows the cell that applies, the percentage ceiling it sets, and which way that cell rounds. The 250 percent primary rounds down: Note 1 is scoped to 125 percent and does not reach it.

New

Three-Phase Motor Calculator

Conductor and maximum inverse-time breaker for a single motor, from horsepower and voltage per NEC Table 430.250. Sized from the table full-load current, never the nameplate: 430.6(A)(1) is explicit, and the nameplate sizes only the running overload device.

New

Is the Neutral a Current-Carrying Conductor?

NEC 310.15(E) has exactly three printed branches and which one you are in decides it. A 120/240V three-wire neutral is not covered by (E)(2), because (E)(2) is scoped to a wye. Counts the whole raceway, including pulled spares, and carries the count through the adjustment to a conductor size.

New

NEMA Plug & Receptacle Identifier

Identify a plug or receptacle from what you can see, without knowing the designation: straight blade or twist-lock, how many slots, whether one is a ground pin. 10-30 and 14-30 are both 30A at 125/250V and only one has an equipment ground, so grounding is printed as its own answer.

More calculators

Conduit, bending & boxes

More calculators

Which NEC year applies? Editions & adoption

Which edition your jurisdiction enforces, what changed, how the load calc differs between 2023 and 2026, and whether the listed-HVAC GFCI exception still exists where you work.


Frequently Asked Questions

Which NEC edition do these calculators use?

The NEC-table calculators reference the NEC 2023 edition (NFPA 70-2023), and each names the table or section it used. The bending tools are pure geometry and cite their bender profiles instead, not a code edition. Check your local jurisdiction for adopted edition, since some areas still enforce the 2020 or 2017 NEC.

Can I use these calculators for permit applications?

These calculators are educational tools that help you verify your work. Always confirm calculations against the NEC code book and consult with your local AHJ (Authority Having Jurisdiction) for permit requirements.

Why do wire size results enforce the 75°C column?

Per NEC 110.14(C), conductor ampacity is limited by the terminal temperature rating of connected equipment, typically 75°C for most breakers and devices. Even with 90°C-rated wire like THHN, the final ampacity cannot exceed the 75°C column value. The 90°C rating is only used as the starting point for derating calculations.

Running the business side too?

The code math is only half the job. Check your hourly rate against real overhead numbers, or clear up markup vs margin before your next bid.