Electrical · Motors
Three-Phase Motor Calculator
Horsepower and voltage in, conductor and maximum inverse-time breaker out. Sized from the NEC Table 430.250 full-load current, never from the nameplate.
The short answer. A 10 HP motor at 460V three-phase draws 14A from NEC Table 430.250. Its branch-circuit conductor is sized at 125% of that (17.5A), which takes #14 copper, and its maximum inverse-time breaker is 250% of the FLC at 35A.
The breaker is larger than the wire on purpose, and that is the part worth understanding before you use the number. A motor circuit splits two jobs that an ordinary branch circuit gives to one device, so the rule that a breaker never exceeds the conductor ampacity does not apply here.
Why a motor circuit is not sized like an ordinary branch circuit
On an ordinary branch circuit the breaker protects the wire, so the breaker never exceeds the conductor ampacity. A motor circuit splits that job in two, and once you see the split the numbers stop looking wrong.
The conductor is sized for the motor's continuous running current: NEC 430.22 requires 125% of the table full-load current. The branch-circuit device is sized for something else entirely, the inrush at start, and NEC 430.52 with Table 430.52 permits an inverse-time breaker up to 250% of the FLC. NEC 240.4(G) then exempts these conductors from the small-conductor rules of 240.4(D) that would otherwise cap the breaker.
What protects the conductor from a sustained overload is the running overload device required by NEC 430.32, sized from the motor nameplate. That is the one place the nameplate is used. A 25 HP 460V motor shows the effect clearly: 34A FLC, #8 copper, and a 90A maximum breaker.
Worked example: 25 HP, 460V, three-phase
Every step below is the calculator's own arithmetic, written out. Nothing here is a separate transcription of the answer; the figures are read from the same function the tool reads, so this example cannot drift away from the result above.
- Look up the current, do not measure it. NEC Table 430.250, 25 HP at 460V three-phase: 34A. The motor's nameplate may read something different; per 430.6(A)(1) the table value is what sizes this circuit.
- Size the conductor at 125%. NEC 430.22: 34A × 1.25 = 42.5A of required ampacity. The smallest copper conductor meeting that in the 75C column of Table 310.16 is #8.
- Size the branch device at 250%. NEC 430.52(C)(1) with Table 430.52: 34A × 2.5 = 85A. Where that is not a standard rating, Exception 1 permits the next standard size up, giving 90A from the 240.6(A) ladder.
- Protect the conductor separately. The 90A breaker does not protect #8 from overload and is not meant to. The running overload device under NEC 430.32 does that, and it is sized from the nameplate, not from the table.
Single-phase motors use a different table
Switching the phase selector moves the lookup to NEC Table 430.248, which publishes its own currents rather than a conversion of the three-phase ones. The difference is large enough that guessing at it would size the wrong circuit: a 5 HP motor at 230V draws 28A single-phase against 15.2A three-phase at the same horsepower and the same voltage, so it takes #10 copper and a 70A maximum breaker instead of #14 and 40A. Table 430.248 stops at 10 HP; above that the tool offers three-phase only, because the table does.
What this calculator does not do
It sizes a single motor on its own branch circuit. It does not size a feeder for several motors, which follows NEC 430.24 and 430.62 and gives a different answer. It does not include voltage drop, which can require a larger conductor on a long run. It does not size the disconnecting means, the controller, or the running overload device. It returns code minimums and code maximums; your AHJ and any local amendments govern the installation.
The 250% branch-circuit figure is the induction-type squirrel-cage and synchronous row of NEC Table 430.52. Wound-rotor and DC motors take a lower percentage from that same table, so this result does not apply to them and the tool says so beside the answer rather than letting the squirrel-cage figure quietly cover a motor the code treats differently.
The values come from NEC Tables 430.248 and 430.250, which are unchanged across the 2017, 2020 and 2023 editions. Conductors are copper at the 75C column of Table 310.16, with no ambient or conduit-fill correction applied. Where a motor needs more ampacity than the largest single conductor in that table provides, the tool says so and points at parallel conductors under NEC 310.10(G) instead of naming a wire that cannot carry the load.
Frequently asked questions
What size wire and breaker do I need for a 10 HP three-phase motor?
A 10 HP motor at 460V three-phase has a full-load current of 14A from NEC Table 430.250. The branch-circuit conductor is sized at 125% of that, so 17.5A, which takes #14 copper at the 75C column. The maximum inverse-time breaker is 250% of the FLC rounded up to the next standard size, which is 35A.
Why is the breaker so much bigger than the wire can carry?
Because a motor draws several times its running current for the first moments of a start, and a breaker sized to the conductor would trip every time. NEC 240.4(G) exempts motor branch-circuit conductors from the small-conductor limits in 240.4(D), so the branch breaker is allowed to exceed the conductor ampacity. The conductor is protected from overload by the running overload device required by 430.32, not by the branch-circuit breaker. This is the single most common reason a motor circuit looks wrong to someone used to sizing ordinary branch circuits.
Do I use the motor nameplate amps or the NEC table?
You use the table. NEC 430.6(A)(1) is explicit that the values in Tables 430.247 through 430.250 are what size the conductors, the ampacity, the disconnect, and the branch-circuit short-circuit and ground-fault protective device. The nameplate full-load amps are used only to size the running overload device, per 430.6(A)(2) and 430.32. Sizing a branch circuit from the nameplate is the most common error on motor work, and it is why this calculator asks for horsepower rather than amps.
What is the full-load current of a 5 HP motor at 230V three-phase?
15.2A, from NEC Table 430.250. That gives a conductor sizing ampacity of 19A at 125%, which takes #14 copper, and a maximum inverse-time breaker of 40A.
Does this work for single-phase motors too?
Yes. Switch the phase selector to single-phase and the lookup moves to NEC Table 430.248, which is a different set of currents rather than a conversion of the three-phase ones. A 5 HP single-phase motor at 230V is 28A, which is nearly double the 15.2A the same horsepower draws at 230V three-phase, and it takes #10 copper with a 70A maximum breaker. Everything else about the method is identical.
Does this cover wound-rotor or DC motors?
No. The 250% branch-circuit figure this tool applies is the row of NEC Table 430.52 for induction-type squirrel-cage and synchronous motors, which is the ordinary case. Table 430.52 gives wound-rotor and DC motors a lower percentage, so applying this result to one would permit a larger branch-circuit device than the code allows. Size those directly from Table 430.52. The full-load current tables cover them; the branch-circuit percentage does not.
Does this calculator include voltage drop?
No. It returns the code-minimum conductor for ampacity under NEC 430.22 and the maximum branch-circuit protection under 430.52. A long run can require a larger conductor to hold voltage drop within the informational 3% branch-circuit recommendation, and motor starting makes drop more noticeable. Size the circuit here first, then check the run length in the voltage drop calculator.
Does this cover more than one motor on a circuit?
No. This sizes a single motor on its own branch circuit, which is the ordinary case. A feeder supplying several motors follows NEC 430.24 and 430.62, which size from 125% of the largest motor plus the sum of the rest, and that is a different calculation with a different result. Do not use a single-motor branch answer for a multi-motor feeder.
Related tools
Motor Full-Load Current Chart
The whole of NEC Tables 430.248 and 430.250 to read across, when you want the table rather than one answer.
Voltage Drop Calculator
The check this tool does not make. A long motor run often needs a conductor larger than ampacity alone requires.
Wire Size Calculator
General branch-circuit conductors, where the 240.4(D) small-conductor rule this motor circuit is exempt from does apply.
MCA and MOCP Calculator
For nameplate-rated equipment such as HVAC, where the nameplate MCA and MOP govern instead of a table lookup.
Standard Breaker Sizes
The NEC 240.6(A) ladder the maximum breaker on this page is rounded up to.
Breaker Size for a Wire Gauge
The ordinary-circuit relationship between wire and breaker, which motor circuits are the exception to.
Keep going