Electrical · Motors

Three-Phase Motor Calculator

Horsepower and voltage in, conductor and maximum inverse-time breaker out. Sized from the NEC Table 430.250 full-load current rather than the nameplate (NEC 430.6(A)(1); 430.6(A)(2) names the exceptions).

Field brief
FLC from the table a 10 HP motor at 460V three-phase draws 14A from NEC Table 430.250. 430.6(A)(1): size the conductors, switch and breaker from the table, not the nameplate; the nameplate governs the overload device (430.6(A)(2)). 14 A
Conductor at 125% 17.5A (NEC 430.22). #14 copper holds on the 75°C column only for a motor marked design letter B, C or D (NEC 110.14(C)(1)(a)(4)) or equipment listed and identified for 75°C conductors (110.14(C)(1)(a)(3)), with the breaker and controller terminals rated 75°C too; otherwise the 60°C column applies and it takes #12 copper. #14
Breaker at 250% the maximum inverse-time breaker is 35A (430.52), larger than the wire on purpose: a motor circuit splits overload and short-circuit protection between two devices, so the breaker-never-exceeds-ampacity rule does not apply. 35 A
Where you left off
Saved in this browser, which can get cleared. The app keeps 10x the readings.Saved in this app.
Intry Pro keeps your saved readings on every device. See Intry Pro ›

Enter the motor's horsepower, not its nameplate amps. NEC 430.6(A)(1) sizes the branch circuit from the table full-load current; the nameplate current sizes the separate running overload device (430.6(A)(2), 430.32).

10 HP, 460V, three-phase
#14 Cu / 35A
conductor and maximum inverse-time breaker

#14 copper holds on the 75°C column only for a motor marked design letter B, C or D (NEC 110.14(C)(1)(a)(4)) or equipment listed and identified for 75°C conductors (110.14(C)(1)(a)(3)), with the breaker and controller terminals rated 75°C too; otherwise the 60°C column applies and it takes #12 copper.

Table full-load current
NEC Table 430.250
14 A
Conductor sizing ampacity
NEC 430.22, 125% of FLC
17.5 A
Minimum copper conductor
75C column, NEC Table 310.16, 110.14(C)(1)(a)
#14
Maximum inverse-time breaker
NEC Table 430.52(C)(1) and 430.52(C)(1)(a), 250% of FLC
35 A

The 35A breaker is deliberately larger than the #14 conductor's ampacity so the motor can draw its starting current without tripping. That is code-correct: NEC 240.4(G) exempts motor branch-circuit conductors from the small-conductor limits of 240.4(D), and the running overload device (430.32), not the branch breaker, is what protects the conductor from overload.

This is the largest standard breaker that Table 430.52(C)(1) and 430.52(C)(1)(a) permit for a single motor on this branch circuit. NEC 430.52(C)(1)(b) permits a higher standard rating only where this one is not sufficient for the motor's starting current, and never above 400 percent of the table FLC. A lower maximum applies where the motor controller's overload relay table or the equipment's marking sets one (NEC 430.52(C)(2)). Long runs may need a larger conductor for voltage drop, which this calculation does not include; a wire-type ground goes up in proportion with it (NEC 250.122(B)). Your AHJ and local amendments govern the install.

What this sizes. One single-phase motor or three-phase squirrel-cage motor in continuous duty, alone on its branch circuit, with copper conductors: the ordinary case, on rows of NEC Table 430.52(C)(1) that give this 250%. A three-phase synchronous motor's full-load current is in Table 430.250's own synchronous columns, which this tool does not read, so no answer here applies to one. A wound-rotor or DC motor takes a lower branch-circuit percentage from a different row of Table 430.52(C)(1), so the breaker here does not apply to one, and a motor in short-time, intermittent, periodic or varying duty takes its conductor under 430.22(E), so the conductor here does not apply to one.

Check voltage drop on the run →Check the conduit fill for these conductors →

Carries 3 conductors into the fill calculator. This tool sizes no equipment grounding conductor, so add the one you pull there: Chapter 9 Note 3 counts it.

Size a motor circuit by horsepower →
Show the math
  1. GIVENMotor: 10 HP, 460 V, three-phase
  2. TABLENEC Table 430.250: 14 A full-load current, read from the table rather than the nameplate (NEC 430.6(A)(1)). Low-speed, high-torque, canned-pump and multispeed motors, and motors larger than the tables, use the nameplate (430.6(A)(2)); 430.6(A)(1) Exceptions No. 2 and 3 send some fan, blower and listed appliance motors to the equipment nameplateNEC Table 430.250, NEC 430.6(A)(1)
  3. MATH14 A × 1.25 = 17.5 A (NEC 430.22)NEC 430.22
  4. TABLESmallest copper conductor carrying 17.5 A in the 75°C column of Table 310.16: #14. #14 copper holds on the 75°C column only for a motor marked design letter B, C or D (NEC 110.14(C)(1)(a)(4)) or equipment listed and identified for 75°C conductors (110.14(C)(1)(a)(3)), with the breaker and controller terminals rated 75°C too; otherwise the 60°C column applies and it takes #12 copper.NEC Table 310.16, 110.14(C)(1)(a)
  5. MATH14 A × 2.50 = 35 A (Table 430.52(C)(1), inverse-time breaker)NEC Table 430.52(C)(1)
  6. ROUNDThat is already a standard rating in Table 240.6(A), so the maximum is 35 ANEC 430.52(C)(1)(a), Table 240.6(A)
  7. RESULTMinimum copper conductor: #14 at 75°CNEC 430.22, Table 310.16
  8. RESULTMaximum inverse-time breaker: 35 ANEC 430.52(C)(1)(a)

The 250% above is the percentage Table 430.52(C)(1) gives an inverse-time breaker on a single-phase, squirrel-cage or synchronous motor. A wound-rotor or DC motor takes a different percentage, and a three-phase synchronous motor reads its current from Table 430.250's own synchronous columns, so this working does not carry across to them.

Where this number comes fromIntry Verified
Calculated from
NEC Table 430.250, NEC 430.6(A)(1), 430.22, Table 310.16, 110.14(C)(1)(a), Table 430.52(C)(1), 430.52(C)(1)(a), 240.6(A). Full-load current read from NEC 2023 Table 430.250 (three-phase) or Table 430.248 (single-phase) per 430.6(A)(1); conductor computed at 125 percent of that current against Table 310.16 per 430.22, at the 60C column and, where 110.14(C)(1)(a) permits it (a motor marked design letter B, C or D, or equipment listed for it), the 75C column; maximum inverse-time breaker computed at 250 percent against the standard ratings in 240.6(A) per Table 430.52(C)(1) and 430.52(C)(1)(a). See the full receipt ↓
Run with
  • PhaseThree-phase
  • Voltage460 V
  • Horsepower10 HP
  • Table FLC14 A
  • Conductor materialCopper
  • Terminals75°C (design B, C or D motor or 75°C-listed equipment)
Checked
Every figure an Intry calculator computes comes from a locked source module, not hand-typed. 35,006 automated checks, one suite for the whole site rather than a per-tool count, re-derive the numbers before each deploy from the tables this site holds, read from the cited NEC Table 430.250 and 430.248 full-load currents and the Article 430 branch-circuit rules. This is our own deterministic gate, not a third-party audit.
Final say
Your AHJ has final say. The table current sizes the branch circuit; your motor's nameplate sizes the running overload device (430.32), which this tool does not size. Wound-rotor and DC motors take a different percentage from Table 430.52(C)(1) and are out of scope; so is a three-phase synchronous motor, whose current is in Table 430.250's own synchronous columns, and a motor in other than continuous duty (430.22(E)).
What Intry Verified means

Intry Verified · NEC 2023 · Build AF0D4B6 · 2026-11-11

10 HP 460V#14 at 75°C, #12 at 60°C / 35A

Why a motor circuit is not sized like an ordinary branch circuit

On an ordinary branch circuit the breaker protects the wire, so the breaker is sized to the conductor ampacity (NEC 240.4(B) permits the next standard rating above it only under its listed conditions). A motor circuit splits that job in two, and once you see the split the numbers stop looking wrong.

The conductor is sized for the motor's continuous running current: NEC 430.22 requires 125% of the table full-load current. The branch-circuit device is sized for something else entirely, the inrush at start, and NEC 430.52 with Table 430.52(C)(1) permits an inverse-time breaker up to 250% of the FLC, or the next standard rating above it (430.52(C)(1)(a)). NEC 240.4(G) then exempts these conductors from the small-conductor rules of 240.4(D) that would otherwise cap the breaker.

What protects the conductor from a sustained overload is the running overload device required by NEC 430.32, sized from the motor nameplate. For a motor 430.6(A)(1) sizes from the table, that is the one place the nameplate is used. A 25 HP 460V motor shows the effect clearly: 34A FLC, #8 copper (design B, C or D motor or 75°C-listed equipment; #6 Cu at 60°C), and a 90A maximum breaker.

Worked example: 25 HP, 460V, three-phase

Every step below is the calculator's own arithmetic, written out. Nothing here is a separate transcription of the answer; the figures are read from the same function the tool reads, so this example cannot drift away from the result above.

  1. Look up the current, do not measure it. NEC Table 430.250, 25 HP at 460V three-phase: 34A. The motor's nameplate may read something different; per 430.6(A)(1) the table value is what sizes this circuit.
  2. Size the conductor at 125%. NEC 430.22: 34A × 1.25 = 42.5A of required ampacity. The smallest copper conductor meeting that in the 75C column of Table 310.16 is #8. #8 copper holds on the 75°C column only for a motor marked design letter B, C or D (NEC 110.14(C)(1)(a)(4)) or equipment listed and identified for 75°C conductors (110.14(C)(1)(a)(3)), with the breaker and controller terminals rated 75°C too; otherwise the 60°C column applies and it takes #6 copper.
  3. Size the branch device at 250%. NEC 430.52(C)(1) with Table 430.52(C)(1): 34A × 2.5 = 85A. Where that is not a standard rating, 430.52(C)(1)(a) permits the next standard size up, giving 90A from the 240.6(A) ladder.
  4. Protect the conductor separately. The 90A breaker does not protect #8 from overload and is not meant to. The running overload device under NEC 430.32 does that, and it is sized from the nameplate, not from the table.

Check your working

Each problem is a single motor on copper conductors in continuous duty, alone on its branch circuit: a three-phase squirrel-cage motor or a single-phase motor, sized the way the calculator above sizes it. A three-phase synchronous motor reads its current from Table 430.250's own synchronous columns, so no answer here applies to it; a wound-rotor or DC motor takes a lower breaker percentage from Table 430.52(C)(1), so the breaker answers do not apply to it; and a motor in short-time, intermittent, periodic or varying duty takes its conductor under 430.22(E), so the conductor answers do not apply to it. Work a problem on paper first, then open its working to check yours. We chose these problems' numbers; your own numbers go in the calculator.

25 HP, 208 V, three-phase squirrel-cage motor

Show the math
  1. GIVENMotor: 25 HP, 208 V, three-phase
  2. TABLENEC Table 430.250: 74.8 A full-load current, read from the table rather than the nameplate (NEC 430.6(A)(1)). Low-speed, high-torque, canned-pump and multispeed motors, and motors larger than the tables, use the nameplate (430.6(A)(2)); 430.6(A)(1) Exceptions No. 2 and 3 send some fan, blower and listed appliance motors to the equipment nameplateNEC Table 430.250, NEC 430.6(A)(1)
  3. MATH74.8 A × 1.25 = 93.5 A (NEC 430.22)NEC 430.22
  4. TABLESmallest copper conductor carrying 93.5 A in the 75°C column of Table 310.16: #3. #3 copper holds on the 75°C column only for a motor marked design letter B, C or D (NEC 110.14(C)(1)(a)(4)) or equipment listed and identified for 75°C conductors (110.14(C)(1)(a)(3)), with the breaker and controller terminals rated 75°C too; otherwise the 60°C column applies and it takes #2 copper.NEC Table 310.16, 110.14(C)(1)(a)
  5. MATH74.8 A × 2.50 = 187 A (Table 430.52(C)(1), inverse-time breaker)NEC Table 430.52(C)(1)
  6. ROUNDNot a standard rating, so 430.52(C)(1)(a) permits the next higher one in Table 240.6(A): 200 ANEC 430.52(C)(1)(a), Table 240.6(A)
  7. RESULTMinimum copper conductor: #3 at 75°CNEC 430.22, Table 310.16
  8. RESULTMaximum inverse-time breaker: 200 ANEC 430.52(C)(1)(a)

50 HP, 230 V, three-phase squirrel-cage motor

Show the math
  1. GIVENMotor: 50 HP, 230 V, three-phase
  2. TABLENEC Table 430.250: 130 A full-load current, read from the table rather than the nameplate (NEC 430.6(A)(1)). Low-speed, high-torque, canned-pump and multispeed motors, and motors larger than the tables, use the nameplate (430.6(A)(2)); 430.6(A)(1) Exceptions No. 2 and 3 send some fan, blower and listed appliance motors to the equipment nameplateNEC Table 430.250, NEC 430.6(A)(1)
  3. MATH130 A × 1.25 = 162.5 A (NEC 430.22)NEC 430.22
  4. TABLESmallest copper conductor carrying 162.5 A in the 75°C column of Table 310.16: 2/0NEC Table 310.16
  5. MATH130 A × 2.50 = 325 A (Table 430.52(C)(1), inverse-time breaker)NEC Table 430.52(C)(1)
  6. ROUNDNot a standard rating, so 430.52(C)(1)(a) permits the next higher one in Table 240.6(A): 350 ANEC 430.52(C)(1)(a), Table 240.6(A)
  7. RESULTMinimum copper conductor: 2/0 at 75°CNEC 430.22, Table 310.16
  8. RESULTMaximum inverse-time breaker: 350 ANEC 430.52(C)(1)(a)

3 HP, 230 V, single-phase motor

Show the math
  1. GIVENMotor: 3 HP, 230 V, single-phase
  2. TABLENEC Table 430.248: 17 A full-load current, read from the table rather than the nameplate (NEC 430.6(A)(1)). Low-speed, high-torque, canned-pump and multispeed motors, and motors larger than the tables, use the nameplate (430.6(A)(2)); 430.6(A)(1) Exceptions No. 2 and 3 send some fan, blower and listed appliance motors to the equipment nameplateNEC Table 430.248, NEC 430.6(A)(1)
  3. MATH17 A × 1.25 = 21.25 A (NEC 430.22)NEC 430.22
  4. TABLESmallest copper conductor carrying 21.25 A in the 60°C column of Table 310.16: #10. #10 copper on the 60°C column, which NEC 110.14(C)(1)(a) makes the rule for this circuit; #12 copper on the 75°C column only where the motor nameplate is marked design letter B, C or D (110.14(C)(1)(a)(4)) or the equipment is listed and identified for 75°C conductors (110.14(C)(1)(a)(3)), with the breaker and controller terminals rated 75°C too.NEC Table 310.16, 110.14(C)(1)(a)
  5. MATH17 A × 2.50 = 42.5 A (Table 430.52(C)(1), inverse-time breaker)NEC Table 430.52(C)(1)
  6. ROUNDNot a standard rating, so 430.52(C)(1)(a) permits the next higher one in Table 240.6(A): 45 ANEC 430.52(C)(1)(a), Table 240.6(A)
  7. RESULTMinimum copper conductor: #10 at 60°CNEC 430.22, Table 310.16
  8. RESULTMaximum inverse-time breaker: 45 ANEC 430.52(C)(1)(a)

Single-phase motors use a different table

Switching the phase selector moves the lookup to NEC Table 430.248, which publishes its own currents rather than a conversion of the three-phase ones. The difference is large enough that guessing at it would size the wrong circuit: a 5 HP motor at 230V draws 28A single-phase against 15.2A three-phase at the same horsepower and the same voltage, so it takes #8 copper (#10 Cu only on a design B, C or D motor or 75°C-listed equipment) and a 70A maximum breaker instead of #14 (design B, C or D motor or 75°C-listed equipment; #12 Cu at 60°C) and 40A. Table 430.248 stops at 10 HP; above that the tool offers three-phase only, because the table does.

What this calculator does not do

It sizes a single motor in continuous duty on its own branch circuit (NEC 430.22; a motor in short-time, intermittent, periodic or varying duty is sized under 430.22(E)). It does not size a feeder for several motors, which follows NEC 430.24 and 430.62 and gives a different answer. It does not include voltage drop, which can require a larger conductor on a long run. It does not size the disconnecting means, the controller, or the running overload device. It returns code minimums and code maximums; your AHJ and any local amendments govern the installation.

The 250% branch-circuit figure comes from the squirrel-cage and synchronous rows of NEC Table 430.52(C)(1). Wound-rotor and DC motors take a lower percentage from that same table, so this result does not apply to them and the tool says so beside the answer rather than letting the squirrel-cage figure quietly cover a motor the code treats differently. A three-phase synchronous motor's full-load current is in Table 430.250's own synchronous columns, which this tool does not read, so it does not size a three-phase synchronous motor.

The values come from NEC Tables 430.248 and 430.250, which are unchanged across the 2017, 2020 and 2023 editions. Conductors are copper from Table 310.16, with no ambient or conduit-fill correction applied. At 100 A or less and on 14 through 1 AWG terminations, NEC 110.14(C)(1)(a) makes the 60C column the rule: a three-phase answer gives the 75C size only with the condition that permits it (a motor marked design letter B, C or D, or equipment listed and identified for 75C conductors) and the 60C size beside it, and a single-phase answer leads with the 60C size. Where a motor needs more ampacity than the largest single conductor in that table provides, the tool says so and points at parallel conductors under NEC 310.10(G) instead of naming a wire that cannot carry the load.

Frequently asked questions

What size wire and breaker do I need for a 10 HP three-phase motor?

A 10 HP motor at 460V three-phase has a full-load current of 14A from NEC Table 430.250. The branch-circuit conductor is sized at 125% of that, so 17.5A. #14 copper holds on the 75°C column only for a motor marked design letter B, C or D (NEC 110.14(C)(1)(a)(4)) or equipment listed and identified for 75°C conductors (110.14(C)(1)(a)(3)), with the breaker and controller terminals rated 75°C too; otherwise the 60°C column applies and it takes #12 copper. The maximum inverse-time breaker is 250% of the FLC rounded up to the next standard size, which is 35A.

Why is the breaker so much bigger than the wire can carry?

Because a motor draws several times its running current for the first moments of a start, and a breaker sized to the conductor would trip every time. NEC 240.4(G) exempts motor branch-circuit conductors from the small-conductor limits in 240.4(D), so the branch breaker is allowed to exceed the conductor ampacity. The conductor is protected from overload by the running overload device required by 430.32, not by the branch-circuit breaker. This is why a motor circuit can look wrong to someone used to sizing ordinary branch circuits.

Do I use the motor nameplate amps or the NEC table?

You use the table. NEC 430.6(A)(1) is explicit that the values in Tables 430.247 through 430.250 are what size the conductors, the ampacity, the disconnect, and the branch-circuit short-circuit and ground-fault protective device. The nameplate full-load amps size the separate running overload device, per 430.6(A)(2) and 430.32; 430.6(A)(2) also sends the nameplate current to the conductors and protection of low-speed, high-torque, canned-pump and multispeed motors. Sizing a branch circuit from the nameplate is an error on motor work, and it is why this calculator asks for horsepower rather than amps.

What is the full-load current of a 5 HP motor at 230V three-phase?

15.2A, from NEC Table 430.250. That gives a conductor sizing ampacity of 19A at 125% and a maximum inverse-time breaker of 40A. #14 copper holds on the 75°C column only for a motor marked design letter B, C or D (NEC 110.14(C)(1)(a)(4)) or equipment listed and identified for 75°C conductors (110.14(C)(1)(a)(3)), with the breaker and controller terminals rated 75°C too; otherwise the 60°C column applies and it takes #12 copper.

Does this work for single-phase motors too?

Yes. Switch the phase selector to single-phase and the lookup moves to NEC Table 430.248, which is a different set of currents rather than a conversion of the three-phase ones. A 5 HP single-phase motor at 230V is 28A, which is nearly double the 15.2A the same horsepower draws at 230V three-phase, and it takes #8 copper (#10 Cu only on a design B, C or D motor or 75°C-listed equipment) with a 70A maximum breaker. Everything else about the method is identical.

Does this cover wound-rotor or DC motors?

No. The 250% branch-circuit figure this tool applies comes from the squirrel-cage and synchronous rows of NEC Table 430.52(C)(1), which is the ordinary case. Table 430.52(C)(1) gives wound-rotor and DC motors a lower percentage, so applying this result to one would permit a larger branch-circuit device than the code allows. Size those directly from Table 430.52(C)(1). Table 430.250 covers a wound-rotor motor's current, and a DC motor's is in Table 430.247, which this tool does not read; the branch-circuit percentage covers neither. A three-phase synchronous motor's full-load current is in Table 430.250's own synchronous columns, which this tool does not read, so it does not size a three-phase synchronous motor either.

Does this calculator include voltage drop?

No. It returns the code-minimum conductor for ampacity under NEC 430.22 and the maximum branch-circuit protection under 430.52. A long run can require a larger conductor to hold voltage drop within the informational 3% branch-circuit recommendation, and motor starting makes drop more noticeable. Size the circuit here first, then check the run length in the voltage drop calculator.

Does this cover more than one motor on a circuit?

No. This sizes a single motor on its own branch circuit, which is the ordinary case. A feeder supplying several motors follows NEC 430.24 and 430.62, which size from 125% of the largest motor plus the sum of the rest, and that is a different calculation with a different result. Do not use a single-motor branch answer for a multi-motor feeder.

Related tools