NEC Wire Sizing

What Size Wire for a Freezer?

The breaker, copper and aluminum wire, and ground for a typical freezer circuit, with the NEC basis and the nameplate caveats that actually decide it.

Quick answer: A freezer typically needs a 20A / 120V circuit with #12 copper (or #10 aluminum) wire and a #12 copper ground. It must be GFCI protected.

Freezer Circuit Spec

Typical branch circuit for a freezer (NEC 210.8(A), 422.10)
Voltage120V
Breaker20A GFCI
Copper wire#12
Aluminum wire#10
Equipment ground (Cu)#12

A standalone chest or upright freezer draws about 5-6A running and belongs on its own 120V circuit (a 15A circuit is compliant; 20A is common). Freezers usually sit in a garage, basement, or utility space where the 2023 NEC requires GFCI protection (210.8(A)). Nuisance tripping is a real concern for freezers, so use a high-quality GFCI and check it periodically. Wire sized at NEC Table 310.16 (copper lead at the 60°C column for NM-B); ground per NEC Table 250.122. The appliance nameplate lists the exact minimum circuit and maximum breaker; it always governs over a typical value.


Long Run? Size It Exactly

For a long run where voltage drop matters, or a nameplate that differs from the typical value, enter your exact load, distance, and conditions.

Loading calculator...

Frequently Asked Questions

What size wire do I need for a freezer?

A freezer typically uses a 20A / 120V circuit, which calls for #12 copper (or #10 aluminum) conductors and a #12 copper equipment ground per NEC Table 250.122. A standalone chest or upright freezer draws about 5-6A running and belongs on its own 120V circuit (a 15A circuit is compliant; 20A is common). Freezers usually sit in a garage, basement, or utility space where the 2023 NEC requires GFCI protection (210.8(A)). Nuisance tripping is a real concern for freezers, so use a high-quality GFCI and check it periodically.

What size breaker for a freezer?

A 20A single-pole (120V) breaker. The #12 copper conductors are matched to that 20A rating, and it must be a GFCI breaker (or GFCI protection ahead of the appliance). Do not oversize the breaker to a wire it does not protect: the breaker and the conductor go up together. Always confirm against the appliance nameplate, which lists the exact minimum circuit and maximum overcurrent device.

Does a freezer need GFCI protection?

Yes. Current NEC requires GFCI protection for this appliance (NEC 210.8(A), 422.10). Use a GFCI breaker or a GFCI device ahead of it.

Can I use aluminum wire for a freezer?

Yes. On the 75C column (the usual basis for aluminum), a 20A circuit needs #10 aluminum, versus #12 copper. Aluminum is common on larger circuits and services to save cost; apply antioxidant to the terminations, torque to the listed spec, and remember aluminum drops slightly more voltage on long runs.

What size breaker for a chest freezer?

Same answer: chest freezer is another name for a freezer. It uses a 20A / 120V circuit with #12 copper wire and a #12 copper ground, GFCI protected. A standalone chest or upright freezer draws about 5-6A running and belongs on its own 120V circuit (a 15A circuit is compliant; 20A is common). Freezers usually sit in a garage, basement, or utility space where the 2023 NEC requires GFCI protection (210.8(A)). Nuisance tripping is a real concern for freezers, so use a high-quality GFCI and check it periodically.


Wire Size for Other Appliances