NEC 310.16
Wire Size Calculator
Intry VerifiedA worked default reading, traceable end to end: what it was calculated from, what it was run with, how it was checked, and who has final say.
Where this number comes fromIntry Verified
- Calculated from
- NEC 310.16, 75°C terminations (110.14(C))
- Run with
- Load50 A continuous
- MaterialCopper
- InsulationTHHN (90°C)
- Ambient86°F
- In conduit1-3 conductors
- Checked
- Every figure an Intry calculator computes comes from a locked source module, not hand-typed. 21026 automated checks re-derive and source-check the numbers against the cited NEC section before each deploy. This is our own deterministic gate, not a third-party audit.
- Final say
- Your AHJ and local amendments have final say. Confirm before rough-in.
Intry Verified · NEC 2023 · Build AE2FC52 · 2026-08-21
New: run this inside your AI assistant
Prefer to just ask? Add this to Claude, free.
Connect Intry to Claude once, then just say “use Intry to…” to run the wire size calculator from a plain-English question, on your phone, on the job. You get the number, what it means, and the cited NEC section, computed live, not guessed. Works on every Claude plan.
Embed the Wire Size Calculator on Your Site
Add it to any website, blog, or training page. One line of code, always the deployed engine, no login, no API key.
- Copy the code below.
- Paste it into any page, post, or CMS (WordPress, Squarespace, Webflow, raw HTML).
- Done. It always runs the currently deployed engine. Keep the credit line so readers know where it comes from.
How to Use This Calculator
- Enter your circuit's load amperage. Use the nameplate rating or calculated load, not the breaker size.
- Check “Continuous load” if the load runs 3 or more hours without interruption (EV chargers, commercial lighting, electric baseboard heat).
- Select your system voltage and phase configuration.
- Enter the one-way wire run distance in feet, measured from the panel to the load, not round-trip.
- Choose copper or aluminum conductor material.
- Select the insulation type. THHN/THWN-2 is the most common for building wire in conduit.
- Adjust ambient temperature if the wire passes through spaces above 86°F (attics, rooftops, mechanical rooms).
- Select the number of current-carrying conductors sharing the same raceway or conduit.
- Read your results on the right. The calculator handles all NEC derating, terminal temperature capping, breaker sizing, and ground wire selection automatically.
How to Size Wire Per the National Electrical Code
Selecting the correct wire size is one of the most critical decisions in any electrical installation. An undersized conductor creates a fire hazard: the wire heats beyond its insulation rating under load, degrading the insulation over time and eventually creating conditions for an arc fault or direct short. An oversized conductor wastes material cost and may not physically fit in the conduit, junction box, or equipment terminations.
The National Electrical Code (NEC) provides a systematic process for determining the minimum conductor size that safely carries the required current under the specific installation conditions. This process accounts for the conductor material (copper or aluminum), insulation temperature rating, ambient temperature, number of conductors sharing a raceway, whether the load is continuous, and the temperature rating of the equipment terminals where the wire terminates.
The wire sizing process has five key steps: calculate the design amperage, look up the base ampacity from NEC Table 310.16, apply derating factors for temperature and bundling, enforce the terminal temperature limitation per NEC 110.14(C), and verify that the final ampacity meets or exceeds the design amperage. Each step is governed by a specific NEC section, and inspectors will check that every step was followed correctly. Understanding this process is what separates a compliant installation from a code violation.
Wire sizing also affects voltage drop, though the NEC treats voltage drop as a recommendation rather than a requirement for branch circuits. NEC 210.19 Informational Note suggests limiting voltage drop to 3% on branch circuits and 5% total (feeder plus branch circuit). While not mandatory for code compliance, excessive voltage drop causes equipment malfunction, dimming lights, motor overheating, and wasted energy. After sizing wire for ampacity, always check voltage drop separately, especially for long runs.
Step 1: Calculate Design Amperage
The design amperage is the current value you use to select the wire size. For non-continuous loads, this equals the actual load current. For continuous loads (any load expected to operate at maximum current for three hours or more), NEC 210.20(A) requires multiplying the load current by 125%. This ensures the conductor and overcurrent device operate within their thermal limits during extended operation.
Common continuous loads include EV chargers (Level 2 chargers typically draw 32–48A continuously), commercial lighting systems, electric baseboard heaters, and data center power feeds. A 40A EV charger, for example, becomes a 50A design load after the 125% continuous factor. Forgetting this multiplier is one of the most common reasons electrical installations fail inspection.
Step 2: Look Up Base Ampacity from NEC Table 310.16
NEC Table 310.16 is the fundamental ampacity table for conductors rated 0–2000V in raceway, cable, or directly buried, with not more than three current-carrying conductors, based on an ambient temperature of 30°C (86°F). The table has separate columns for 60°C, 75°C, and 90°C insulation ratings, and separate sections for copper and aluminum conductors.
When derating is required (for high ambient temperatures or bundled conductors), you start with the 90°C column regardless of your wire's actual insulation rating. The 90°C column gives you the highest starting ampacity, which provides the most room for derating. This is a deliberate NEC methodology: you use the 90°C column as your derating baseline, then apply the terminal temperature cap at the end.
For example, #6 AWG copper has ampacities of 55A at 60°C, 65A at 75°C, and 75A at 90°C. If you need to derate for a hot attic, starting from 75A gives you a higher result after derating than starting from 55A or 65A. But the final result is still capped by the terminal temperature. More on that in the critical section below.
Understanding the NEC 110.14(C) Terminal Temperature Limitation
This is the single most important concept in wire sizing and the one most frequently misunderstood. NEC 110.14(C) requires that the temperature rating of the conductor be considered in conjunction with the temperature rating of the equipment terminations. In practice, this means: even with 90°C wire (THHN), your final usable ampacity is capped at the equipment termination column. NEC 110.14(C)(1) sets that column from the circuit rating: 60°C at 100 amperes or less, 75°C above it, each one unless the equipment is listed and marked otherwise. The marking on your equipment is what decides it.
Here is why this matters. A #6 AWG copper THHN conductor has a 90°C ampacity of 75A per NEC 310.16. Many online calculators simply report 75A as the ampacity and call it done. But if that #6 THHN wire terminates on a breaker marked 75°C, the connection point can only handle the heat generated by 65A, the 75°C column value. Running 75A through a 75°C-rated terminal will overheat the connection, potentially causing thermal damage, increased resistance, and eventually failure.
The 90°C column value IS used, but only as the starting point for derating calculations. After applying temperature correction and bundling adjustment factors to the 90°C value, the result is compared to the straight 75°C column value. The final usable ampacity is the lesser of these two numbers. This means the 90°C rating provides benefit only when derating reduces the 90°C value below what the 75°C column allows. In effect, it gives you extra headroom for derating without needing to upsize the conductor.
When is the 90°C column value used directly without a 75°C cap? Only when both ends of the conductor terminate on equipment specifically listed and marked for 90°C terminations. This is uncommon in residential and light commercial work. Some industrial motor controllers, high-temperature-rated disconnects, and specialty equipment carry 90°C terminal ratings, but you must verify this on the equipment label. Never assume.
This calculator enforces NEC 110.14(C) automatically. The “Terminal Cap (75°C)” line in the results shows the final ampacity after applying this critical limitation. This is our key differentiator from calculators that simply report the 90°C ampacity without terminal temperature enforcement.
Temperature Derating per NEC Table 310.15(B)(1)(1)
NEC Table 310.16 assumes conductors operate in an ambient temperature of 30°C (86°F). When the ambient temperature exceeds this baseline, the conductor's ampacity must be reduced because the conductor cannot dissipate heat as effectively. The correction factors come from NEC Table 310.15(B)(1)(1), which provides multipliers for each temperature range and insulation rating.
Common scenarios requiring temperature derating include attics (which routinely reach 120–150°F in summer), rooftop conduit runs exposed to direct sunlight, mechanical rooms adjacent to boilers or furnaces, and conduit runs near steam pipes or hot water lines. Even a relatively moderate increase to 104°F (40°C) reduces 90°C wire ampacity by 9% (factor of 0.91).
To apply temperature derating, multiply the base ampacity from the 90°C column by the correction factor for your ambient temperature. For example, #6 THHN copper in a 122°F attic: 75A (90°C base) × 0.82 (correction factor) = 61.5A derated ampacity. Compare this to the 75°C column value of 65A. Since 61.5A is less than 65A, the terminal cap does not further reduce the ampacity. The final usable ampacity is 61.5A, which means #6 is only good for about 61A in that attic. For a 50A continuous load (62.5A design), you would need to upsize to #4 AWG.
This is exactly where the 90°C insulation rating provides its benefit. If you used the 75°C column as your derating starting point instead: 65A × 0.75 (75°C factor at 122°F) = 48.75A, well below the 61.5A you get starting from the 90°C column. The 90°C rating gives you both a higher base ampacity and a gentler correction factor, which is why THHN is the standard choice for hot locations. The 75°C terminal cap still applies at the end, but after real derating the corrected value usually governs.
Bundling Adjustment per NEC Table 310.15(C)(1)
When more than three current-carrying conductors share a raceway, cable, or conduit, each conductor's ability to dissipate heat is reduced because the adjacent conductors are also generating heat. NEC Table 310.15(C)(1) provides adjustment factors based on the number of current-carrying conductors in the raceway.
The adjustment factors are: 4–6 conductors at 80%, 7–9 at 70%, 10–20 at 50%, 21–30 at 45%, 31–40 at 40%, and 41 or more at 35%. These factors multiply with the temperature correction factor, so a conductor in a hot attic inside a conduit with six other current-carrying conductors gets hit with both derations.
An important nuance: the count of “current-carrying conductors” does not always include every wire in the conduit. Equipment grounding conductors are excluded. Neutral conductors that carry only unbalanced load in a balanced system are typically excluded. However, in a three-phase, four-wire wye system supplying nonlinear loads (like LED drivers or computer power supplies), the neutral carries harmonic currents and must be counted. When in doubt, count the neutral. Oversizing is safer than undersizing.
Both the temperature correction factor and bundling adjustment factor are applied to the 90°C base ampacity before the terminal temperature cap. The formula is: Derated Ampacity = Base Ampacity (90°C) × Temperature Factor × Bundling Factor. The final usable ampacity is then the lesser of this derated value and the 75°C column value.
Copper vs Aluminum: When to Use Each
Copper and aluminum are the two conductor materials used in building wiring, and each has distinct advantages. Aluminum has only about 61% of copper's conductivity, meaning a smaller copper wire carries the same current as a larger aluminum wire. Copper is also more ductile, easier to terminate, and resists oxidation better than aluminum.
Aluminum, however, is lighter and less expensive than copper for the same ampacity, and the cost gap widens on larger feeders. A 200A dwelling service entrance in copper requires #2/0 AWG under the NEC 310.12 dwelling rule (#3/0 where that rule does not apply); the equivalent aluminum installation uses #4/0 AWG. Conductor prices track a commodity market and move continuously, so price both materials at your own supplier on the day rather than working from a fixed percentage or a rule of thumb.
In practice, aluminum is the standard choice for service entrance conductors, large feeder runs (60A and above), and sub-panel feeders. Copper is the standard for branch circuits (15–50A), device connections, and smaller wire sizes where the cost difference is minimal and the superior workability of copper saves labor time.
The “aluminum wiring scare” of the 1960s and 1970s stemmed from a specific problem: solid aluminum branch circuit wiring (sizes #12 and #10) used with devices designed for copper only. Aluminum expands and contracts more than copper with temperature cycling, and it oxidizes when exposed to air. These properties caused loose connections at receptacles, switches, and splice points, leading to overheating and fires. The problem was never the aluminum conductor itself. It was the termination compatibility.
Modern aluminum installations use stranded aluminum conductors in larger sizes (#6 and above) with anti-oxidant compound (NoAlox or equivalent) on every termination, and all breakers and panel lugs carry AL/CU ratings. These practices eliminate the historical termination issues. For sub-panel feeders and service entrance conductors, aluminum remains a safe, code-compliant, and cost-effective choice when installed correctly.
5 Wire Sizing Mistakes That Fail Inspection
Electrical inspectors see the same wire sizing errors repeatedly. Understanding these common mistakes helps you avoid costly rework and failed inspections.
- Using the 90°C column without applying the terminal temperature cap. This is the most common error on online calculator results that homeowners bring to permit offices. A #8 THHN copper shows 55A in the 90°C column, but with standard 75°C equipment terminals, the usable ampacity is only 50A (the 75°C value). For a 50A continuous load (62.5A design), you need #6 AWG, not #8.
- Forgetting the 125% continuous load factor for EV chargers. A 48A EV charger is a continuous load. The design amperage is 48 × 1.25 = 60A. Many DIY installations are wired with #6 AWG (65A at 75°C) on a 50A breaker, but the breaker should be 60A, and some inspectors require the wire to support the full 60A design load. Always size for the continuous-adjusted amperage, then select the breaker.
- Ignoring temperature derating for attic runs. Wire routed through an attic must be derated for the elevated ambient temperature. An attic or rooftop run at 150°F reduces #12 THHN copper from 30A (90°C) to about 17A after derating (0.58 factor). This means a standard 20A circuit through a hot attic may require #10 AWG instead of #12.
- Using the wrong NEC table column for the insulation type. TW insulation is rated 60°C, THW and THWN are 75°C, and THHN and THWN-2 are 90°C. Using the 90°C column for TW wire overstates the ampacity by 50–70% and creates a direct fire hazard. Always verify the insulation marking on the conductor jacket.
- Undersizing the equipment grounding conductor. The EGC must be sized per NEC Table 250.122 based on the overcurrent protective device rating, not the wire size. A 100A sub-panel feeder requires a #8 AWG copper ground regardless of whether the hot conductors are #3 copper or #1 aluminum. Some installers mistakenly match the ground to two sizes below the hot conductors. This is not a valid method.
Common Wire Size Requirements
| Application | Typical Load | Wire Size | Breaker Size |
|---|---|---|---|
| EV Charger (Level 2) | 40–50A continuous | #6 AWG | 50A |
| Electric Dryer | 24–30A | #10 AWG | 30A |
| Hot Tub / Spa | 40–50A | #6 AWG | 50A |
| Central AC (3 ton) | 15–20A | #12 AWG | 20A |
| Electric Range | 40–50A | #6 AWG | 50A |
| Welder (240V) | 40–50A | #6 AWG | 50A |
| Sub-Panel 60A | 60A | #6 AWG | 60A |
| Sub-Panel 100A | 100A | #3 AWG | 100A |
| Pool Pump | 12–16A | #12 AWG | 20A |
| Water Heater (electric) | 18.75A continuous | #10 AWG | 30A |
| Well Pump | 10–20A | #12 AWG | 20A |
| Shop Air Compressor | 15–24A | #10 AWG | 30A |
These are typical values for standard conditions. Always verify with the actual nameplate amperage, wire run length, ambient temperature, and number of conductors in conduit.
NEC Table 310.16 Copper Ampacities
| Wire Size (AWG/kcmil) | 60°C (TW, UF) | 75°C (THW, THWN) | 90°C (THHN, THWN-2) |
|---|---|---|---|
| #14 | 15A | 20A | 25A |
| #12 | 20A | 25A | 30A |
| #10 | 30A | 35A | 40A |
| #8 | 40A | 50A | 55A |
| #6 | 55A | 65A | 75A |
| #4 | 70A | 85A | 95A |
| #3 | 85A | 100A | 115A |
| #2 | 95A | 115A | 130A |
| #1 | 110A | 130A | 145A |
| #1/0 | 125A | 150A | 170A |
| #2/0 | 145A | 175A | 195A |
| #3/0 | 165A | 200A | 225A |
| #4/0 | 195A | 230A | 260A |
Worked Examples
Example 1: EV Charger, 40A Continuous, 50 ft, Copper THHN
A Level 2 EV charger draws 40A continuously (charges for 8+ hours overnight). Per NEC 625.42, the branch circuit and OCPD must be sized at 125% of the continuous load. Design amps: 40A × 1.25 = 50A, so the breaker is 50A. Look up #8 THHN copper: 90°C ampacity = 55A. No derating needed (standard conditions). Apply terminal cap: min(55A, 50A at 75°C) = 50A. Since 50A ≥ the 50A design load, #8 AWG copper passes (many installers upsize to #6 for margin). A 48A charger steps up one size: 48 × 1.25 = 60A breaker with #6 AWG.
Example 2: Sub-Panel 100A, 75 ft, Copper THHN
A 100A sub-panel feeder is a non-continuous load (the diversified load rarely exceeds 80A in practice). Design amps: 100A. Look up wire sizes in the 90°C column: #3 copper = 115A, #4 copper = 95A. #4 is insufficient (95A < 100A after terminal cap of 85A). #3 THHN: 90°C ampacity = 115A. Terminal cap: min(115A, 100A at 75°C) = 100A. Since 100A ≥ 100A, #3 AWG copper passes. Breaker = 100A. Ground wire per NEC 250.122: #8 AWG.
Example 3: Kitchen Circuit 20A, 60 ft in Attic (150°F Ambient)
A 20A kitchen branch circuit routed through an attic that reaches 150°F under a summer roof deck. Design amps: 20A (non-continuous). At 150°F (150–158°F range), the 90°C correction factor is 0.58. Check #12 THHN copper: 90°C ampacity = 30A. Derated: 30A × 0.58 = 17.4A. Terminal cap: min(17.4A, 25A at 75°C) = 17.4A. Since 17.4A < 20A, #12 fails. Try #10 THHN: 40A × 0.58 = 23.2A. Terminal cap: min(23.2A, 35A) = 23.2A. Since 23.2A ≥ 20A, #10 AWG passes. The hot attic run requires upsizing from #12 to #10.
Wire Sizing FAQ
Is the Intry Wire Size Calculator accurate and NEC compliant?
Every figure an Intry calculator computes comes from a locked source module, not hand-typed. 21026 automated checks re-derive and source-check the numbers against the cited NEC section before each deploy. This is our own deterministic gate, not a third-party audit. The per-tool receipt is public at https://www.intrysys.com/verified.
What size wire do I need for a hot tub?
Most hot tubs and spas run on a 50A 240V circuit, which calls for #6 copper conductors on a 50A GFCI breaker with a #10 copper equipment ground; smaller 40A units take #8 copper (still with a #10 copper ground). Always size to the nameplate: match the breaker to the unit's listed maximum overcurrent rating, then pull copper THWN rated for that ampacity per NEC Table 310.16, where a 50A load lands on #6 (75C copper carries 65A) and a 40A load on #8. Spa and hot tub wiring falls under NEC Article 680 Part IV, so 680.42 (outdoor) or 680.43 (indoor) governs the install, 680.44 requires GFCI protection, and 680.13 requires a disconnecting means within sight of the spa and at least 5 feet from the water; the equipment ground is sized from Table 250.122 (#10 copper for a 40A or 50A circuit).
How many outlets can be on a 20 amp circuit?
There is no fixed NEC limit on receptacles for a 20-amp general-purpose circuit in a dwelling, because homes are sized by the general lighting and receptacle load calculation rather than a per-outlet count. In a non-dwelling occupancy the practical limit is 13 receptacles: NEC 220.14(I) assigns 180 VA per outlet, and 20A x 120V = 2400 VA divided by 180 VA = 13.3, rounded down to 13. The old 8-to-10 outlet rule of thumb is a design practice, not a code requirement for houses. Any circuit must still keep a continuous load at or below 80 percent, meaning 16 amps on a 20-amp circuit, per 210.19(A) and 210.20(A).
What is the 80% rule for a circuit breaker?
The 80% rule means a standard circuit breaker can carry a continuous load (one running 3 hours or more) at no more than 80% of its rating, so a 20A breaker is limited to 16A continuous and a 30A breaker to 24A. Stated as the sizing rule, the conductor and the overcurrent device must each be rated at least 125% of the continuous load, since 1 divided by 0.80 equals 1.25 (NEC 210.19(A) for the conductor, 210.20(A) for the breaker). Standard breakers are only listed for 100% of their rating on non-continuous loads; the 20% headroom covers heat buildup in the enclosure over long run times. For a load that never runs 3 hours straight, you can use the full 100% of the breaker rating.
Can you mix 12 and 14 gauge wire on the same circuit?
Yes on a 15A circuit, no on a 20A circuit. The breaker has to protect the smallest conductor, and NEC 240.4(D)(4) caps #14 copper at a 15A overcurrent device, so putting #14 alongside #12 on a 20A breaker is a violation even though the #12 alone could carry 20A. Mixing itself is fine; just keep the breaker at 15A or less so every conductor on the circuit stays protected.
Can I put a 20 amp breaker on 14 gauge wire?
No. NEC 240.4(D)(4) caps #14 copper at a 15-amp overcurrent device, so a 20A breaker on 14 gauge wire is a code violation and a fire hazard. The breaker protects the wire, not the load: 14 AWG copper is rated to carry only 15A safely, but a 20A breaker lets the circuit draw up to 20A without tripping, so the conductor can overheat before the breaker ever opens. Use 12 gauge copper for a 20A breaker, 14 gauge for 15A, and 10 gauge for 30A. The one common exception is a listed motor or air-conditioning circuit, where the nameplate maximum overcurrent protection can legally exceed the conductor rating by design (NEC 240.4(G)).
What happens if a circuit breaker is too big?
An oversized breaker stops protecting the wire. A breaker's job is to trip before the conductor overheats, so it has to match the wire's ampacity per NEC 240.4: 15A for #14 copper, 20A for #12, 30A for #10. Put a 30A breaker on a 20A (#12) circuit and the wire can carry 30A indefinitely without tripping, cooking the insulation and creating a fire risk long before the breaker opens. Bigger is only legal where the code specifically allows it, such as the next-standard-size rule in 240.4(B) when a calculated load lands between breaker sizes, or a motor and AC branch circuit sized to the nameplate MOCP (240.4(G)). If the breaker is larger than the wire it feeds, fix it: upsize the wire to match the breaker, or drop the breaker to match the wire.
What size wire for a well pump?
Size the branch-circuit conductor at the motor's full-load current times 125 percent (NEC 430.22), then upsize for voltage drop, which almost always governs on a well because the run is long. A 240V 1 to 2 HP single-phase submersible is 8 to 12 amps in NEC Table 430.248, so #12 or #10 copper covers ampacity, but past roughly 100 to 150 feet of drop plus lateral you step up to #10 or #8 to hold voltage drop near 3 percent. One code catch: per NEC 430.6(A)(1) you size the conductor off that table (horsepower-based) full-load current, not the nameplate amps; the nameplate running current is what sets the overload device (430.32). Always add the pump's drop-cable length to the horizontal run before you pick the gauge.
Is #6 copper wire safe for a 60 amp breaker?
Yes. #6 copper is rated 65A at the 75C column of NEC Table 310.16, which fully covers a standard 60A breaker (65A is not a standard breaker size, and 240.4(B) lets the 60A device protect it). For a continuous load (running three hours or more), the limiting factor is the breaker, not the wire: a 60A breaker caps continuous current at 48A (60 / 1.25), even though the #6 conductor itself could carry 52A continuous. Terminate on 75C-rated lugs and confirm no derating applies for ambient temperature above 30C or more than three current-carrying conductors in the raceway.
What size wire do I need for a 50 amp breaker?
For a 50A breaker with copper THHN at standard conditions (86°F, ≤3 conductors), you need #6 AWG copper. Even if the load is continuous (an EV charger, for example), the 125% rule increases design amps to 62.5A and #6 THHN still passes, because its 75°C terminal-capped ampacity is 65A. Always verify with your specific run length and ambient temperature.
What size wire for a 200 amp service?
A 200A residential service typically uses #4/0 AWG aluminum, or #2/0 AWG copper under the NEC 310.12 dwelling service rule (#3/0 copper where that rule does not apply). Aluminum is common for service entrance because the cost savings at this size are substantial. The service ground is the grounding electrode conductor (GEC), sized from the service conductor per NEC Table 250.66: #4 AWG copper to a water pipe or Ufer electrode, and need not exceed #6 copper where its only connection is to a ground rod (250.66(A)). That is a different table from the 250.122 equipment ground that runs with a feeder or branch circuit.
Can I use aluminum wire for a sub-panel?
Yes, aluminum is commonly used for sub-panel feeders, especially for 60A and larger circuits where the cost savings are significant. Use anti-oxidant compound on all aluminum terminations and ensure the breaker and panel lugs are rated AL/CU. Aluminum requires a larger wire size than copper for the same ampacity.
Which NEC rule actually decides my wire size?
Five can, and the code fixes the order they apply in. NEC 210.19(A) states the composition directly: branch-circuit conductors shall have an ampacity not less than the larger of the load-based minimums "and comply with 110.14(C) for equipment terminations" (215.2(A) says the same for feeders). So you take the largest requirement, you do not stop at the first one. In order: 210.19(A)(1) and 210.20(A) apply 125 percent to a continuous load; Table 310.15(B)(1)(1) corrects for ambient temperature; Table 310.15(C)(1) adjusts for the number of current-carrying conductors; 310.15(A) and 110.14(C) then cap the corrected value at the equipment termination column; and 240.4(D) limits the overcurrent device on 14, 12 and 10 AWG, expressly "after any correction factors for ambient temperature and number of conductors have been applied". Any one of them can be the rule that sets your size, and which one it is changes what you would have to change to use a smaller conductor. This calculator names the one that bound your result.
Do I size to the 60°C column or the 75°C column?
NEC 110.14(C)(1) decides it from the circuit rating, and then defers to the equipment marking: the determination applies "unless the equipment is listed and marked otherwise". For circuits rated 100 amperes or less, 110.14(C)(1)(a) permits only conductors rated 60°C, or higher-rated conductors used at their 60°C ampacity, or higher-rated conductors where the equipment is listed and identified for them. For circuits rated over 100 amperes, 110.14(C)(1)(b) makes 75°C the baseline. Which one applies to your job is a fact about your hardware, not something a calculator can infer, so read the breaker, the panelboard and the lugs. This calculator takes the termination rating as an input and shows you both answers whenever the marking would change the conductor.
My circuit is exactly 100 amperes. Which subdivision applies?
100 amperes falls under 110.14(C)(1)(a), which reads "circuits rated 100 amperes or less"; 110.14(C)(1)(b) begins at "over 100 amperes". The circuit rating is the overcurrent device rating per NEC 210.18: "where conductors of higher ampacity are used for any reason, the ampere rating or setting of the specified overcurrent device shall determine the circuit rating". One caution the rating alone does not settle: both subdivisions also key off what the equipment is MARKED for, (a) for 14 AWG through 1 AWG and (b) for conductors larger than 1 AWG, and no calculator can read that marking from your inputs. Where the two columns give different conductors, size to the marking on the equipment you are actually landing on.
Why is voltage drop not part of the code check?
Because it is not an enforceable requirement. The 3 percent branch-circuit and 5 percent total figures appear in an Informational Note under NEC 210.19, and NEC 90.5(C) states that such notes "are informational only and are not enforceable as requirements of this Code". Ampacity, the termination cap and the small-conductor overcurrent limit are mandatory rules, written with "shall", and voltage drop is a design recommendation. It still matters: a long run can need a larger conductor than ampacity alone, some local amendments adopt it, and NEC 250.122(B) requires the equipment grounding conductor to be increased proportionally if you upsize the ungrounded conductors for voltage drop. We keep it as a separate check so a recommendation is never presented to you as a code failure.
What's the difference between THHN and THWN-2?
THHN is rated 90°C in dry locations. THWN-2 is rated 90°C in both dry and wet locations. Most modern building wire is dual-rated THHN/THWN-2, meaning a single conductor carries both ratings. For conduit runs inside buildings, either designation applies. For wet locations, verify the THWN-2 rating on the jacket.
Why does my wire calculator show a different result than the 90°C column?
Per NEC 310.15(A) and 110.14(C), the final ampacity is capped by the equipment terminal temperature rating, and 110.14(C)(1) sets which column applies: 60°C for circuits rated 100 amperes or less, 75°C for circuits rated over 100 amperes, each of them unless the equipment is listed and marked otherwise. It is the marking that decides, not a default, so read the breaker, the panelboard and the lugs. Even with 90°C wire you cannot use the full 90°C ampacity unless the equipment is listed and identified for 90°C terminations; the 90°C rating only serves as the starting point for correction and adjustment.
Do I need to derate wire in an attic?
Yes. Attic temperatures commonly reach 120–150°F in summer. NEC 310.15(B)(1) requires temperature correction factors that reduce conductor ampacity. At 122°F, the correction factor for 90°C wire is 0.82, and at 150°F it drops to 0.58, which may require upsizing the conductor by one or two sizes compared to standard conditions.
What size ground wire do I need?
The equipment grounding conductor (EGC) is sized from the overcurrent protective device (breaker) rating per NEC Table 250.122, not from the circuit conductor. For copper: 20A breaker = #12 AWG, 50A breaker = #10 AWG, 100A breaker = #8 AWG, 200A breaker = #6 AWG. Table 250.122 prints separate copper and aluminum columns, so an aluminum EGC is larger at the same breaker rating: 20A breaker = #10 AWG, 50A breaker = #8 AWG, 100A breaker = #6 AWG, 200A breaker = #4 AWG. Run length does not change it. Two further rules apply: 250.122(A) says the EGC need not be larger than the circuit conductors supplying the equipment, and 250.122(B) requires the EGC to be increased proportionally to the circular-mil increase if the ungrounded conductors are upsized for any reason other than the corrections in 310.15, which is the case people miss after upsizing for voltage drop.
What is the maximum wire size for a residential panel?
Most residential panels accept conductors up to #4/0 AWG or 250 kcmil, depending on the lug size. A typical 200A residential panel has lugs rated for #4/0 AWG aluminum or #2/0 AWG copper. For services over 200A, parallel conductors or commercial-grade equipment is required. Check the panel label for specific lug ratings.
Wire Size for a Specific Breaker
Quick-answer pages for the most common breaker ratings, with the copper and aluminum conductor, ground wire, and code basis for each.
Three-Phase Motor Calculator
Sizing a motor? Use this instead. A motor branch circuit is sized from the NEC table full-load current, not the load, and its breaker is allowed to exceed the wire.
NEMA Plug & Receptacle Identifier
Identify the connector on the end of the run from what you can see, then size the conductors for it.
20 Amp Wire Size
#12 copper or #10 aluminum, #12 ground.
30 Amp Wire Size
#10 copper or #8 aluminum, #10 ground.
40 Amp Wire Size
#8 copper or #8 aluminum, #10 ground.
50 Amp Wire Size
#8 copper or #6 aluminum, #10 ground.
60 Amp Wire Size
#6 copper or #4 aluminum, #10 ground.
100 Amp Wire Size
#3 copper or #1 aluminum, #8 ground.
200 Amp Wire Size
#3/0 copper or 250 kcmil aluminum, #6 ground.
Related Calculators
Wire Size for Appliances
Dryer, range, water heater, hot tub, and more: the standard circuit and wire for each.
Voltage Drop Calculator
Verify voltage drop meets NEC recommendations for your wire run.
Conduit Fill Calculator
Check NEC conduit fill compliance for your wire selection.
Box Fill Calculator
Calculate junction box fill per NEC 314.16.
Wire Ampacity Chart (310.16)
The inverse of this tool: start from a conductor already in place at 60, 75, and 90°C and get the device, the ground wire and the size to pull.
Long run? Check voltage drop before you pull wire.
Ampacity is only half the sizing question. Past 100 feet, voltage drop often forces the gauge up before the ampacity table does. Run the numbers before you buy the wire, not after.