HVAC · Gas appliances

Combustion Air Calculator

Is the space confined, and what size combustion-air opening does the code require? IFGC 2021 Section 304, for every gas appliance in the room, with the exact subsection.

The short answer. A space is confined if it has less than 50 cubic feet of volume for every 1,000 Btu/h of total gas appliance input. A confined space needs combustion-air openings, sized by the method: outdoor air through two vertical openings is 1 square inch per 4,000 Btu/h each. An 80,000 Btu/h furnace plus a 40,000 water heater in a small closet is confined and takes 30 in² net per opening, or 80 in² gross once you account for a metal louver.

Two things decide the answer and both are easy to get wrong: the total must include every appliance in the space, the water heater as well as the furnace, and the required area is net free area, so the hole you cut is larger. The safety lane here is carbon monoxide, not fire, and this tool never certifies a space safe.

Loading calculator...

The two mistakes this catches

Sizing on the furnace alone

Combustion air is sized on the TOTAL of every appliance in the space. Leave out the co-located water heater and every number comes out too small, which starves combustion and makes carbon monoxide. The tool sums them for you and reminds you to include it.

Cutting the hole at the net size

The code area is net free area. A louver blocks part of the opening, so the gross hole is larger: 1.33 times for metal, 4 times for wood. Cut to the net size and the real opening is a quarter to three quarters short. The tool shows both.

Combustion-air methods and their divisors

Every value below is a locked IFGC 2021 Section 304 constant the calculator divides your total appliance input by. The required area is always net free area.

MethodRequired area / volumeSection
Confined-space threshold50 ft³ per 1,000 Btu/h of total input304.5.1
Known infiltration (KAIR)21 ft³/ACH draft-hood, 15 ft³/ACH fan-assisted (cap 0.60 ACH)304.5.2
All indoor, same story1 in² per 1,000 Btu/h each, min 100 in², min 3 in304.5.3.1
All indoor, different story2 in² per 1,000 Btu/h total304.5.3.2
Outdoor, two openings (direct/vertical)1 in² per 4,000 Btu/h each304.6.1
Outdoor, two openings (horizontal duct)1 in² per 2,000 Btu/h each304.6.1
Outdoor, one opening1 in² per 3,000 Btu/h, ≥ sum of vent areas304.6.2
Mechanical supply0.35 CFM per 1,000 Btu/h from outdoors304.9
Louver free areametal 75%, wood 25% of gross304.10

Branded to IFGC 2021, identical to IFGC 2024. NFPA 54 Section 9.3 uses different section numbers for the same rules; the values we cross-checked read identical, but confirm the exact code and edition your jurisdiction has adopted.

Questions

How much combustion air is needed for an 80,000 BTU furnace?

It depends on the room, and on every other gas appliance sharing it. The IFGC unconfined-space rule is 50 cubic feet of room volume per 1,000 Btu/h of total input, so an 80,000 Btu/h furnace alone needs a space of at least 4,000 cubic feet to draw its air from the room. If the space is smaller than that, it is confined and needs combustion-air openings sized by the method you choose. And if a water heater shares the space, its input adds to the furnace's before you size anything: the most common and most dangerous mistake here is sizing on the furnace alone and starving the water heater.

How many cubic feet per BTU for combustion air?

50 cubic feet per 1,000 Btu/h of aggregate appliance input, for the standard indoor-volume method (IFGC 304.5.1). That is the confined-versus-unconfined threshold: a room with at least that much volume can supply combustion air from the room itself, and a smaller room is confined. There is also a known-air-infiltration-rate method (IFGC 304.5.2) that can permit a smaller room when the building's tightness is known, using 21 cubic feet per air change for draft-hood appliances and 15 for fan-assisted, but it caps the infiltration rate at 0.60 air changes per hour.

How do you size a combustion air opening?

By the method and the appliance total. For outdoor air through two openings, each opening is 1 square inch per 4,000 Btu/h for a direct opening or a vertical duct, or 1 square inch per 2,000 Btu/h for a horizontal duct, which doubles it. A single outdoor opening is 1 square inch per 3,000 Btu/h and must also be at least the sum of the vent-connector areas. All-indoor openings are 1 square inch per 1,000 Btu/h with a 100 square inch minimum. In the 120,000 Btu/h example on this page, two vertical outdoor openings come out to 30 square inches of net free area each.

What is the difference between net free area and gross area?

Net free area is the actual open area air passes through. Gross area is the size of the hole you cut, and it is larger because the louver or screen blocks part of it. A metal louver passes about 75 percent of its gross area and a wood louver only 25 percent, so a required 30 square inch net opening through a metal louver becomes 80 square inches gross. Cutting the hole at the net size undersizes the opening by a quarter to three quarters, which starves combustion. Always cut to the gross size, and use the louver's actual marked free area if it has one.

What happens if there is not enough combustion air?

The appliance cannot get enough oxygen to burn cleanly. Incomplete combustion produces carbon monoxide, and in a tight space the appliance can backdraft, pulling its own flue gases back into the room instead of up the vent. That is the reason this is a code requirement and not a suggestion: it is a carbon-monoxide safety issue, not a fire one. A calculator sizes the code-required opening, but it cannot confirm the space is actually safe. That takes a draft, spillage, or CO test on the running appliances, and the authority having jurisdiction and the appliance instructions have the final say.

Does a high-efficiency or sealed-combustion furnace need combustion air openings?

A direct-vent, sealed-combustion appliance pulls its combustion air directly from outdoors through its own pipe, so it does not draw from the room and this room-air sizing does not apply to it. But it still matters on the same job: when a high-efficiency furnace replaces an old atmospheric one, an atmospheric water heater often stays behind in the same space, and now that water heater may be the only appliance left drawing combustion air from a room that used to share it. Re-run the space with only the remaining atmospheric appliances, because the answer changes when the furnace leaves.

Related tools