HVAC · Gas appliances

Combustion Air Calculator

Is the space confined, and what size combustion-air opening does the code require? IFGC 2021 Section 304, for every gas appliance in the room, with the exact subsection.

Field brief
Confined space less than 50 cubic feet of volume for every 1,000 Btu/h of total gas appliance input (IFGC 304.5.1, the standard method). An 80,000 Btu/h furnace alone needs 4,000 ft³ to be unconfined by that method, unless the house is known to be tighter than 0.40 ACH, where IFGC 304.5 requires the known-air-infiltration-rate method (304.5.2) instead. 4,000 ft³
Opening size outdoor air through two horizontal ducts is 1 in² per 2,000 Btu/h each. An 80,000 furnace plus a 40,000 water heater in a small closet takes 60 in² net per opening, 80 in² gross each behind a metal louver. Through two direct openings or vertical ducts it is 1 in² per 4,000 Btu/h: 30 in² net per opening, 40 in² gross each. 60 in² net
Count every appliance the water heater as well as the furnace, and the required area is net free area, so the hole you cut is larger. The safety lane is carbon monoxide, not fire, and this tool never certifies a space safe. net, not gross
Every gas appliance in the space (include the water heater)

Include every appliance that draws its combustion air from this room. Leave OUT a direct-vent or sealed-combustion appliance that pipes its own air from outdoors, since it does not use room air. When in doubt, include it: the safe error is a larger opening, not a smaller one.

Leave 0 for the standard 50 ft3/1,000 method, except in a house known to be tighter than 0.40 ACH: there IFGC 304.5 requires the known-infiltration method, so enter the house's measured air infiltration rate and say what it is below (a blower-door ACH50 is a different number, and this tool gives no verdict on one). If set, that method is used (capped at 0.60 ACH).

Space verdict
CONFINED
required 6,000 ft3, you have 72 ft3
Total appliance input120,000 Btu/h
Required volume6,000 ft3
Required opening (net free area)120 in2 (2 x 60)
Gross opening to cutlouver 75%160 in2
Code sectionIFGC 2021 Section 304.6.1
Safety: this does not certify the space safe. This computes the code-required opening only. It does NOT certify the space safe. The authority having jurisdiction (AHJ) and the appliance manufacturer's installation instructions have final say, and a real combustion-air problem is confirmed by a draft, spillage, or CO test, never by a calculation.
Show the arithmetic
Total appliance input = 120,000 Btu/h (2 appliances)
Standard required volume = 50 x (120,000/1000) = 6000 ft3; appliance space 72 ft3 -> CONFINED
Outdoor, two openings, horizontal: 1 in2 per 2,000 Btu/h = 60.0 in2 net each
Where this number comes fromIntry Verified
Calculated from
IFGC 2021 Section 304 combustion-air provisions. Computed by the combustion-air engine from IFGC 2021 Section 304: the total appliance input sets the required volume against the 50 ft3 per 1,000 Btu/h threshold, and each opening is that input divided by the locked divisor for the chosen method, corrected for the louver free area. See the full receipt ↓
Run with
  • Total input120,000 Btu/h
  • Space72 ft3
  • Required volume6,000 ft3
  • Verdictconfined
  • Opening120 in2 net / 160 in2 gross
Checked
Every figure an Intry calculator computes comes from a locked source module, not hand-typed. 31163 automated checks, one suite for the whole site rather than a per-tool count, re-derive the numbers before each deploy from the tables this site transcribed from the IFGC 2021 Section 304 / NFPA 54 §9.3 combustion-air provisions it was computed from. This is our own deterministic gate, not a third-party audit.
Final say
The authority having jurisdiction and the appliance manufacturer's instructions have final say. This never certifies a space safe: a real combustion-air problem is confirmed by a draft, spillage, or CO test.
What Intry Verified means

Intry Verified · Build 2731D30 · 2026-10-15

What this does not decide for you

This opening depends on the duct type. A direct opening or a VERTICAL duct is 1 in2 per 4,000 Btu/h (the smaller opening); a HORIZONTAL duct is 1 in2 per 2,000, which DOUBLES it. This result assumes a horizontal duct (the larger, conservative opening). Confirm the routing before you cut. (IFGC 2021 Section 304.6.1)

The required area above is NET free area. Cut the GROSS opening larger to account for the louver or screen: 120.0 in2 net becomes 160.0 in2 gross through a metal louver (75% free area). Publishing the net area as the hole to cut undersizes it. (IFGC 2021 Section 304.10)

Each opening must be at least 3 in in its least dimension ("The minimum dimension of air openings shall be not less than 3 inches"): a 60 in2 opening only 1 in tall does not qualify. (IFGC 2021 Section 304.6)

Any screen over an opening must have a mesh size not smaller than 1/4 in ("Screens shall have a mesh size not smaller than 1/4 inch"). (IFGC 2021 Section 304.10)

The total input must include EVERY gas appliance drawing combustion air from this space, including a co-located water heater. Confirm none was left out. (IFGC 2021 Section 304.5)

160 in2 gross openingCONFINED

The two mistakes this catches

Sizing on the furnace alone

Combustion air is sized on the TOTAL of every appliance in the space. Leave out the co-located water heater and every number comes out too small, which starves combustion and makes carbon monoxide. The tool sums them for you and reminds you to include it.

Cutting the hole at the net size

The code area is net free area. A louver blocks part of the opening, so the gross hole is larger: 1.33 times for metal, 4 times for wood. Cut to the net size and the real opening is a quarter to three quarters short. The tool shows both.

Combustion-air methods and their divisors

Every value below is a locked IFGC 2021 Section 304 constant the calculator divides your total appliance input by. The required area is always net free area.

MethodRequired area / volumeSection
Confined-space threshold50 ft³ per 1,000 Btu/h of total input304.5.1
Known infiltration (KAIR)21 ft³/ACH draft-hood, 15 ft³/ACH fan-assisted (cap 0.60 ACH); required where ACH is known to be below 0.40 (304.5)304.5.2
All indoor, same story1 in² per 1,000 Btu/h each, min 100 in², min 3 in304.5.3.1
All indoor, different story2 in² per 1,000 Btu/h total304.5.3.2
All indoor, when it appliesonly if both spaces together meet the required volume; if not, outdoor air304.1
Outdoor, two openings (direct/vertical)1 in² per 4,000 Btu/h each304.6.1
Outdoor, two openings (horizontal duct)1 in² per 2,000 Btu/h each304.6.1
Outdoor, one opening1 in² per 3,000 Btu/h, ≥ sum of vent areas304.6.2
Mechanical supply0.35 CFM per 1,000 Btu/h from outdoors304.9
Louver free areametal 75%, wood 25% of gross304.10

Branded to IFGC 2021, identical to IFGC 2024. NFPA 54 Section 9.3 uses different section numbers for the same rules; the values we cross-checked read identical, but confirm the exact code and edition your jurisdiction has adopted.

Questions

How much combustion air is needed for an 80,000 BTU furnace?

It depends on the room, and on every other gas appliance sharing it. The IFGC unconfined-space rule is 50 cubic feet of room volume per 1,000 Btu/h of total input, so an 80,000 Btu/h furnace alone needs a space of at least 4,000 cubic feet to draw its air from the room by that standard method. Where the house's air infiltration rate is known to be less than 0.40 air changes per hour, IFGC 304.5 requires the known-air-infiltration-rate method instead, and in a tight house that method can require more room than the standard one. If the space is smaller than that, it is confined and needs combustion-air openings sized by the method you choose. And if a water heater shares the space, its input adds to the furnace's before you size anything: the most common and most dangerous mistake here is sizing on the furnace alone and starving the water heater.

How many cubic feet per BTU for combustion air?

50 cubic feet per 1,000 Btu/h of aggregate appliance input, for the standard indoor-volume method (IFGC 304.5.1). That is the confined-versus-unconfined threshold for that method: a room with at least that much volume can supply combustion air from the room itself, and a smaller room is confined. The exception is a tight house. IFGC 304.5 reads: "where the air infiltration rate is known to be less than 0.40 air changes per hour (ACH), Section 304.5.2 shall be used." The known-air-infiltration-rate method (IFGC 304.5.2) uses 21 cubic feet per air change for draft-hood appliances and 15 for fan-assisted, and an infiltration rate above 0.60 air changes per hour may not be used. It can permit a smaller room in a leakier house and require a larger one in a tight house: it needs more volume than the standard method below 0.42 ACH for draft-hood appliances and below 0.30 ACH for fan-assisted ones.

How do you size a combustion air opening?

By the method and the appliance total. For outdoor air through two openings, each opening is 1 square inch per 4,000 Btu/h for a direct opening or a vertical duct, or 1 square inch per 2,000 Btu/h for a horizontal duct, which doubles it. A single outdoor opening is 1 square inch per 3,000 Btu/h and must also be at least the sum of the vent-connector areas. All-indoor openings are 1 square inch per 1,000 Btu/h with a 100 square inch minimum, and that method applies only where the appliance space and the communicating space together meet the required volume: where they do not, IFGC 304.1 requires outdoor air, and this calculator sizes no all-indoor opening. In the 120,000 Btu/h example on this page, two horizontal outdoor ducts come out to 60 square inches of net free area each, and two direct openings or vertical ducts come out to 30 square inches each (40 square inches gross each behind a metal louver).

What is the difference between net free area and gross area?

Net free area is the actual open area air passes through. Gross area is the size of the hole you cut, and it is larger because the louver or screen blocks part of it. A metal louver passes about 75 percent of its gross area and a wood louver only 25 percent, so a required 60 square inch net opening through a metal louver becomes 80 square inches gross. Cutting the hole at the net size undersizes the opening by a quarter to three quarters, which starves combustion. Always cut to the gross size, and use the louver's actual marked free area if it has one.

What happens if there is not enough combustion air?

The appliance cannot get enough oxygen to burn cleanly. Incomplete combustion produces carbon monoxide, and in a tight space the appliance can backdraft, pulling its own flue gases back into the room instead of up the vent. That is the reason this is a code requirement and not a suggestion: it is a carbon-monoxide safety issue, not a fire one. A calculator sizes the code-required opening, but it cannot confirm the space is actually safe. That takes a draft, spillage, or CO test on the running appliances, and the authority having jurisdiction and the appliance instructions have the final say.

Does a high-efficiency or sealed-combustion furnace need combustion air openings?

A direct-vent, sealed-combustion appliance pulls its combustion air directly from outdoors through its own pipe, so it does not draw from the room and this room-air sizing does not apply to it. But it still matters on the same job: when a high-efficiency furnace replaces an old atmospheric one, an atmospheric water heater often stays behind in the same space, and now that water heater may be the only appliance left drawing combustion air from a room that used to share it. Re-run the space with only the remaining atmospheric appliances, because the answer changes when the furnace leaves.

Related tools