Electrical Calculator
MCA & MOCP Breaker and Wire Size Calculator
Wire, breaker, ground and voltage drop for an HVAC unit, read straight off its nameplate MCA and MOCP.
Intry VerifiedA worked default reading, traceable end to end: what it was calculated from, what it was run with, how it was checked, and who has final say.
Where this number comes fromIntry Verified
- Calculated from
- NEC 440.22, 310.16 with 310.15(B)(1) and Table 310.15(C)(1), 110.14(C), 240.6(A), 250.122. Computed from NEC 440.33/440.34/430.24 (MCA) and 440.22 (MOCP), with the 240.4(G) Article-440 conductor exemption, on NEC Table 310.16 ampacity corrected by 310.15(B)(1) and adjusted by Table 310.15(C)(1) and held to the 110.14(C) termination column, the 240.6(A) breaker, and the Table 250.122 ground. See the full receipt ↓
- Run with
- MCA19.9 A
- MOCP35 A
- Supply240 V, single phase
- MaterialCopper
- Terminals75°C
- Run50 ft one-way
- Checked
- Every figure an Intry calculator computes comes from a locked source module, not hand-typed. 35,938 automated checks, one suite for the whole site rather than a per-tool count, re-derive the numbers before each deploy from the tables this site holds, read from the cited NEC Article 440 section. This is our own deterministic gate, not a third-party audit.
- Final say
- The unit nameplate has final say. NEC Article 440 governs the sizing.
Intry Verified · NEC 2023 · Build 525536D · 2026-11-13
Values verified against NEC 2023 (NFPA 70-2023) Tables 310.16, 250.122, and 240.6(A). The nameplate and the manufacturer's installation instructions govern per NEC 110.3(B); local amendments and your AHJ have the final word.
Run this inside your AI assistant
Prefer to just ask? Add this to Claude.
Connect Intry to Claude once, then just say “use Intry to…” to run the mca & mocp breaker calculator from a plain-English question, on your phone, on the job. You get the number (computed live, not guessed), what it means, and the cited NEC Article 440 section. Works on every Claude plan.
MCA to Wire Size, 75 C Column
Minimum conductor for a given nameplate MCA, NEC Table 310.16, 75 C terminations, no more than 3 current-carrying conductors, 30 C ambient
Swipe the table sideways to see the rest of its columns. →
| Nameplate MCA up to | Copper | Aluminum |
|---|---|---|
| 15 A | #14 AWG (20 A) | #12 AWG (20 A) |
| 20 A | #14 AWG (20 A) | #12 AWG (20 A) |
| 25 A | #12 AWG (25 A) | #10 AWG (30 A) |
| 30 A | #10 AWG (35 A) | #10 AWG (30 A) |
| 35 A | #10 AWG (35 A) | #8 AWG (40 A) |
| 40 A | #8 AWG (50 A) | #8 AWG (40 A) |
| 45 A | #8 AWG (50 A) | #6 AWG (50 A) |
| 50 A | #8 AWG (50 A) | #6 AWG (50 A) |
| 55 A | #6 AWG (65 A) | #4 AWG (65 A) |
| 60 A | #6 AWG (65 A) | #4 AWG (65 A) |
| 65 A | #6 AWG (65 A) | #4 AWG (65 A) |
| 70 A | #4 AWG (85 A) | #3 AWG (75 A) |
For NM cable (Romex) use the 60 C column instead, per NEC 334.80: the calculator's 60 C termination toggle handles it. High ambient or more than three current-carrying conductors in a raceway require derating per NEC 310.15, and the calculator applies it: set the ambient, the roof mounting and the conductor count under “conditions on the run” and the size it returns is the one that passes after correction, not the flat table lookup.
Standard Breaker Sizes, NEC 240.6(A)
The standard ampere ratings for fuses and inverse-time breakers up to 125 A are:
15 • 20 • 25 • 30 • 35 • 40 • 45 • 50 • 60 • 70 • 80 • 90 • 100 • 110 • 125
Pick the largest one that does not exceed the nameplate MOCP. If the nameplate says MOCP 40 and no 40 exists in your panel lineup, go down to 35, never up to 45. When the MOCP is itself a standard rating, the breaker simply equals the MOCP.
Wire Sized to MCA, Breaker Sized to MOCP
Every air conditioner, heat pump, and mini split nameplate carries two circuit numbers, and each one answers exactly one question. MCA (Minimum Circuit Ampacity) answers "how big is the wire." The manufacturer computes it per NEC 440.4(B) and the listing standard as 125 percent of the largest motor's rated load amps plus the sum of the other loads (the same formula as NEC 440.33), then prints the finished answer. The conductor has to carry the MCA where it is actually installed. Take its NEC Table 310.16 ampacity in the column matching the terminations (NEC 110.14(C)), correct it for the ambient (NEC 310.15(B)(1), plus the rooftop adder of NEC 310.15(B)(2) where the raceway sits in direct sun), adjust it for more than three current-carrying conductors (NEC Table 310.15(C)(1)), and compare THAT figure to the MCA. A conductor that clears the MCA on the printed table can be well under it on a hot roof or in a crowded raceway.
MOCP (Maximum Overcurrent Protection) answers "how big can the breaker be." It is the ceiling the manufacturer established under NEC 440.22, up to 175 percent of the compressor RLA and as high as 225 percent where needed for starting (440.22(A)). Install the largest standard NEC 240.6(A) rating at or below it. The breaker does not need to round up from the MCA; if the MCA falls between standard sizes, MOCP still sets the maximum, and the smallest standard size at or above the MCA is simply the practical floor for reliable starting.
MCA and MOCP are Article 440 figures for a circuit with a compressor on it. A heating circuit with no compressor, such as the electric heat strips in an air handler, is sized under NEC Article 424 instead: use the heat strip wire and breaker calculator.
Why the Breaker Can Legally Exceed the Wire Ampacity
A 35 A breaker on a conductor rated 20 A looks wrong to anyone trained on ordinary branch circuits, and on any other circuit it would be. Hermetic compressor circuits split the protection job in two. The breaker or fuse handles short circuits and ground faults only. Running overload protection comes from the compressor's own overload devices per NEC 440.52, and those devices protect the branch-circuit conductors too. The manufacturer proved during UL listing that an MCA-sized conductor survives every fault the MOCP-rated device lets through, which is why NEC 240.4(G) exempts Article 440 circuits from the small-conductor breaker limits of 240.4(D). The oversized breaker exists for one reason: a compressor pulls locked-rotor current several times its running amps for a moment at every start, and a breaker sized to the wire would nuisance-trip on hot restarts.
The Two Mistakes That Cause Callbacks
Adding 125 percent twice. MCA already contains the 125 percent factor on the largest motor (NEC 440.4(B)). Treating the MCA like a continuous load and multiplying by 1.25 again per 210.20(A) lands one or two wire sizes heavy: wasted copper on every job, and an apprentice-exam trap question besides.
Sizing the breaker to the wire. Matching the breaker to the conductor ampacity the way you would on a receptacle circuit gives a breaker far below the MOCP, and the unit trips on hard starts, especially high-head restarts on hot days. The nameplate maximum exists because the manufacturer knows the inrush. Sizing up to the MOCP is not a shortcut; it is the design.
Worked Examples
Example 1: a nameplate reading MCA 19.9 / MOCP 35, 240 V
Wire: the conductor needs ampacity of at least 19.9 A. In NEC Table 310.16 at 75 C, 14 AWG copper carries 20 A, so 14 AWG THHN in conduit technically qualifies. Running NM cable instead? NEC 334.80 forces the 60 C column, where 14 AWG only carries 15 A, so NM needs 12 AWG copper (20 A at 60 C). 12 AWG copper serves either way.
Breaker: 35 A is a standard NEC 240.6(A) rating, so the answer is a 35 A HACR breaker, full stop. Yes, that is a 35 A breaker on a wire rated 20 A: NEC 240.4(G) exempts this Article 440 circuit from the small-conductor limits because the compressor overload protects the wire per NEC 440.52.
Ground: a 35 A device falls in Table 250.122's 60 A row, so the table size is 10 AWG copper, and 10 AWG is what this calculator gives. NEC 250.122(A) says an equipment grounding conductor is not required to be larger than the circuit conductors, which read strictly would allow 12 or 14 AWG here; whether that reaches a circuit whose breaker is deliberately oversized for compressor inrush is genuinely contested, so the tool holds the table size and tells you the relief exists rather than taking it for you. Pulling 10 AWG is never wrong.
Example 2: a nameplate reading MCA 26.4 / MOCP 45, 240 V, 80 ft run
Wire: 12 AWG copper tops out at 25 A in the 75 C column, short of 26.4 A, so the minimum is 10 AWG copper (35 A). In aluminum, 10 AWG carries 30 A at 75 C, which also clears 26.4 A.
Breaker: largest standard size at or below 45 A is 45 A. The smallest standard size at or above the 26.4 A MCA is 30 A, so any standard rating from 30 to 45 A is permitted; 45 A is a sound pick because it matches the nameplate maximum and rides through hard starts.
Voltage drop: at 26.4 A over 80 ft one way on 10 AWG copper, drop is about 2.2 percent of 240 V, inside the 3 percent guidance of NEC 210.19 Informational Note. Run the calculator with your exact distance to confirm.
Example 3: illegible nameplate, compressor RLA 21.0 / fan FLA 2.5
MCA: per NEC 440.33, take 125 percent of the largest motor plus the other loads: 1.25 × 21.0 + 2.5 = 28.75 A. The manufacturer's printed MCA governs when readable, since it may include a crankcase heater or control load you cannot see.
Wire: 28.75 A needs 10 AWG copper (35 A at 75 C in Table 310.16).
Breaker: with no readable MOCP, the conservative choice is the smallest standard size at or above the MCA, 30 A. The nameplate MOCP can be higher, on the order of 175 percent of the 21.0 A RLA per NEC 440.22(A), which is 36.75 A, pointing at a 35 A nameplate maximum. Pull the spec sheet by model number before finalizing.
Frequently Asked Questions
What does MCA mean on an HVAC nameplate?
MCA is Minimum Circuit Ampacity, the manufacturer's computed minimum conductor ampacity for the unit under NEC 440.4(B) and the UL 1995/UL 60335-2-40 listing standards: 125 percent of the largest motor's rated load amps plus the sum of all other concurrent loads. Its only job is to size the wire. Pick a conductor from NEC Table 310.16 whose ampacity meets or exceeds the MCA, using the column the terminations allow: on a circuit of 100 A or less NEC 110.14(C)(1)(a) holds it to the 60 C column unless the breaker and the equipment are listed and identified for 75 C conductors (110.14(C)(1)(a)(3)). MCA is not the running current and not the breaker size.
What does MOCP or Max Fuse/Ckt Bkr mean?
MOCP is Maximum Overcurrent Protection, the largest fuse or breaker the manufacturer permits for the unit, listed on the nameplate per NEC 440.4(B) and limited by NEC 440.22. Install the largest standard rating from NEC 240.6(A) that does not exceed the MOCP; going one size over it is a code violation and voids the listing per NEC 110.3(B). A smaller breaker is legal as long as the unit can start and run without nuisance trips, and the practical floor is the smallest standard size at or above the MCA.
Why can the breaker be bigger than the wire's ampacity on HVAC equipment?
Because on a hermetic refrigerant motor-compressor circuit the breaker only provides short-circuit and ground-fault protection. Running overload protection comes from the compressor's internal or external overload devices per NEC 440.52, and the manufacturer verified during listing that the MOCP-rated device still protects an MCA-sized conductor under fault conditions. NEC 240.4(G) explicitly exempts Article 440 circuits from the small-conductor breaker limits in 240.4(D), which is why a 14 or 12 AWG conductor on a 35 A breaker is legal here and nowhere else in a house.
Do I add 125 percent to the MCA for continuous load?
No. The 125 percent factor on the largest motor is already built into the MCA by the manufacturer per NEC 440.4(B) and 440.33. Applying NEC 210.20(A) continuous-load math on top of MCA double-counts the factor and lands you one or two wire sizes heavy. The conductor simply needs ampacity greater than or equal to the printed MCA.
What is an HACR breaker and do I need one?
HACR stands for Heating, Air Conditioning, and Refrigeration, a UL listing category confirming the breaker can handle the group locked-rotor and cycling profile of HVAC equipment. Where the equipment listing calls for HACR protection, NEC 110.3(B) makes it mandatory. Confirm the HACR marking on the breaker, older panels included.
The nameplate says Maximum Fuse only. Can I still use a breaker?
Not unless the manufacturer says so. If the nameplate specifies fuses without mentioning a circuit breaker or HACR breaker, the listing was established with fuses and NEC 110.3(B) requires following it, so install a fused disconnect at the unit. A nameplate that reads Max Fuse/Ckt Bkr or Max Fuse or HACR Breaker permits either device. When in doubt, the installation instructions for the model number control.
Can I run NM cable (Romex) to a condenser?
Indoors, yes, but with two catches. First, NEC 334.80 limits NM cable ampacity to the 60 C column of Table 310.16 no matter what the conductor insulation is rated, so an MCA of 19.9 A needs 12 AWG copper NM (20 A at 60 C) even though 14 AWG THHN in conduit would satisfy the 75 C column. Use this calculator's 60 C termination toggle for NM. Second, NM cannot be used in wet or damp locations (NEC 334.12), so the run transitions to THWN in a liquidtight whip or to UF cable for the final outdoor stretch to the disconnect and unit.
The MOCP is unreadable. How do I size the breaker?
First choice: look up the manufacturer spec sheet by model number, because the published MOCP governs. If the model tag is also gone, NEC 440.22(A) is the fallback the manufacturer used: the device is sized at up to 175 percent of the compressor rated load amps (plus other loads per 440.22(B)), and up to 225 percent where needed for starting. Switch this calculator to the From motor RLA/FLA mode to compute the MCA from the compressor RLA and fan FLA per NEC 440.33, and use the smallest standard breaker at or above that MCA as a conservative choice until the real MOCP is confirmed.
What breaker and wire do I need for MCA 19.9 and MOCP 35?
Breaker: 35 A, since 35 A is itself a standard rating in NEC 240.6(A) and may not be exceeded. Wire: with 75 C terminations and THHN/THWN-2 copper in conduit, 14 AWG (20 A at 75 C in Table 310.16) technically satisfies the 19.9 A MCA, and NEC 240.4(G) makes the 35 A breaker legal on it. With NM cable, or 60 C terminations, you need 12 AWG copper (20 A at 60 C). Running 12 AWG copper on either wiring method also buys voltage drop margin on longer runs.
Related Calculators
Three-Phase Motor Calculator
For a plain motor rather than nameplate-rated equipment: conductor and maximum breaker from horsepower per NEC Table 430.250, sized from the table current instead of a nameplate MCA.
A2L Changeout Circuit Check
Replacing R-410A with R-454B? Check whether the existing breaker and wire still pass the new nameplate, a lower new MOP can make the old breaker oversized (NEC 440.22).
EV Charger Circuit Calculator
Wire, breaker, panel capacity, and charging speed for Level 2 EVSE circuits, where the 125% continuous factor does apply.
Wire Size Calculator
General-purpose conductor sizing with ambient temperature correction, conduit bundling derates, and 240.4(D) limits.
Voltage Drop Calculator
Exact drop for any wire size, distance, and load, single or three phase, copper or aluminum, with the minimum size for 3 percent.
HVAC Serial Number Lookup
Decode the manufacture date from the serial number for 50+ HVAC brands, the other half of reading a nameplate.
Tonnage from Model Number
Decode nominal tonnage and BTU/h from the model number for 40+ brands, then size the circuit from the nameplate MCA and MOCP.
Electrical Load Calculator
The whole-house side of the job: NEC 220.82 service sizing and the 220.87 check for adding a heat pump or EV charger to an existing panel.
Long run to the condenser? Check the drop.
MCA sizing assumes the wire run is short. Past 60 or 80 feet, voltage drop starts costing compressor life. The voltage drop calculator gives the exact percentage and the wire size that keeps you inside 3 percent.