Electrical · Transformers
Transformer OCPD Calculator
NEC Table 450.3(B) overcurrent protection for transformers 1000 volts and less. Shows the cell that applies, the percentage ceiling it sets, and which way that cell rounds.
Three-phase divides by 1.732. Leaving it out overstates rated current by about 73 percent.
This picks the row of Table 450.3(B), and the two rows do not use the same percentages.
240.6(A) gives fuses four ratings a breaker cannot use: 1, 3, 6 and 601 A. On a small transformer that is often the difference between an answer and none.
Note 3 raises the primary ceiling to 6 times rated current at 6 percent impedance or less, and 4 times over 6 through 10 percent. Above 10 percent it does not apply.
Show the arithmetic
Where this number comes fromIntry Verified
- Calculated from
- NEC 2023 Table 450.3(B) and the standard ratings of NEC 240.6(A). Computed by the transformer OCPD engine from NEC 2023 Table 450.3(B) and the standard ratings in 240.6(A): rated current is derived from kVA and voltage with the phase factor, the table cell sets a percentage ceiling, and the device is the standard rating that cell's own rounding direction selects. See the full receipt ↓
- Run with
- Transformer45 kVA 480/208 V 3ph
- Primary rated54.13 A
- Cell250% (note 3)
- Roundingdown, it is a maximum
- Primary device125 A
- Checked
- Every figure an Intry calculator computes comes from a locked source module, not hand-typed. 31163 automated checks, one suite for the whole site rather than a per-tool count, re-derive the numbers before each deploy from the tables this site transcribed from the cited cell of NEC Table 450.3(B) and the standard ratings in 240.6(A). This is our own deterministic gate, not a third-party audit.
- Final say
- Your AHJ has final say. Table 450.3(B) gives maximums, so a smaller device is usually permitted and often required by the load, the conductors or the transformer inrush.
Intry Verified · NEC 2023 · Build 2731D30 · 2026-10-15
Where secondary protection is required it may be up to six circuit breakers or six sets of fuses grouped in one location, and the sum of their ratings must not exceed the value allowed for a single device. (NEC Table 450.3(B) Note 2)
Table 450.3(B) does not apply where the transformer is installed as a motor control circuit transformer in accordance with 430.72(C)(1) through (C)(5). The small control transformers that land in the under-9 A columns are exactly the ones most likely to fall under that exclusion, so check it before relying on this result. (NEC 450.3(B))
Article 450 does not cover every transformer. 450.1 excludes current transformers, dry-type transformers that are a component part of other apparatus, X-ray, high-frequency and electrostatic-coating apparatus, transformers used with Class 2 and Class 3 circuits, sign and outline lighting, electric-discharge lighting, power-limited fire alarm circuits, and research and testing transformers. Table 450.3(B) does not size protection for any of those. (NEC 450.1)
This engine sizes the transformer overcurrent protection only. Conductors on both sides are sized separately, and transformer secondary conductors follow 240.21(C), which takes its ratios from the device protecting the transformer PRIMARY, not from the feeder device used by 240.21(B)(3). (NEC 240.21(C))
This breaker is NONADJUSTABLE. Table 450.3(B) Note 1 scopes its round-up to a fuse or a nonadjustable circuit breaker, so on an adjustable-trip breaker Note 1 does not apply and the cell percentage stays a hard maximum: the device would round DOWN instead, to a smaller rating. (NEC Table 450.3(B) Note 1)
Common dry-type transformers, 480 to 208Y/120, protected on both sides
The transformer sizes are a chosen list; every other value in each row is computed by the same engine the calculator above runs, from NEC Table 450.3(B) and the standard ratings in 240.6(A). These are code maximums on a three-phase transformer with protection on both sides. The device you install is often smaller, because the load, the conductors and the inrush all push the other way.
| Transformer | Primary current | 250% ceiling | Max primary device | Secondary current | 125% target | Max secondary device |
|---|---|---|---|---|---|---|
| 15 kVA | 18 A | 45.1 A | 45 A | 41.6 A | 52 A | 60 A |
| 30 kVA | 36.1 A | 90.2 A | 90 A | 83.3 A | 104.1 A | 110 A |
| 45 kVA | 54.1 A | 135.3 A | 125 A | 124.9 A | 156.1 A | 175 A |
| 75 kVA | 90.2 A | 225.5 A | 225 A | 208.2 A | 260.2 A | 300 A |
| 112.5 kVA | 135.3 A | 338.3 A | 300 A | 312.3 A | 390.3 A | 400 A |
| 150 kVA | 180.4 A | 451.1 A | 450 A | 416.4 A | 520.4 A | 600 A |
| 225 kVA | 270.6 A | 676.6 A | 600 A | 624.5 A | 780.7 A | 800 A |
| 300 kVA | 360.8 A | 902.1 A | 800 A | 832.7 A | 1040.9 A | 1200 A |
The primary column rounds down from the ceiling beside it. The secondary column rounds up from the target beside it, because the 125 percent cell is the one Note 1 marks. Two adjacent columns of the same table, rounding in opposite directions.
Where the small transformers go wrong
A 1 kVA 480 volt control transformer draws 2.08 A on the primary. That is under 9 A, so on the primary only row the ceiling is 167 percent, or 3.48 A, and the cell has no Note 1 marker, so it rounds down. The largest standard rating at or below 3.48 A is a 3 A fuse.
The answer is a fuse for a reason. NEC 240.6(A) gives fuses four ratings a circuit breaker cannot use, 1, 3, 6 and 601 A. Below the 167 percent ceiling on a transformer this small there is no standard circuit breaker small enough, and this calculator says so rather than rounding up to the smallest breaker it knows. A tool that reaches for a 15 A breaker here returns a device at several times the code maximum, which is the opposite of protection.
Primary-only protection is a legality question, not just a sizing one
Satisfying the primary only row of Table 450.3(B) protects the transformer. It does not protect the secondary conductors. NEC 240.4(F) permits the primary device to be considered the protection for secondary conductors only on a single-phase transformer with a 2-wire single-voltage secondary, or a three-phase delta-delta transformer with a 3-wire single-voltage secondary, and only where that device also does not exceed the secondary conductor ampacity times the secondary-to-primary voltage ratio. 240.21(C)(1) says the same thing.
On a 480 to 208Y/120 wye secondary, the most common dry-type step-down in a commercial building, that permission does not apply. The calculator stops and names 240.4(F) as the rule, because treating the primary device as the conductors protection there is the failure this section exists to prevent. Note what it is not saying: primary-only protection of the transformer is still permitted by Table 450.3(B), and 240.21(C) separately permits secondary conductors to run without a device at the transformer where they meet one of its rules. What is not permitted is calling the primary device their protection.
Questions
What size breaker does a 45 kVA 480 to 208Y/120 transformer need?
Protected on both the primary and the secondary, a 45 kVA 480 to 208Y/120 three-phase transformer takes a maximum 125 amp primary device and a maximum 175 amp secondary device. The primary rated current is 54.1 amps, and the primary and secondary row of NEC Table 450.3(B) allows 250 percent of that, which is 135.3 amps. That is a maximum with no Note 1 marker on it, so it rounds DOWN to the next standard rating at or below it, giving 125 amps. The secondary rated current is 124.9 amps, and the 125 percent cell gives 156.1 amps. That cell does carry the Note 1 marker, so where the result is not a standard rating the next higher standard rating is permitted, giving 175 amps.
Does the 250 percent primary round up or down?
Down. This is the error that matters most on this table. Note 1 is the only note that grants a round-up, and its own text scopes it twice over: where 125 percent of the current does not correspond to a standard rating of a fuse or a nonadjustable circuit breaker, a higher rating not exceeding the next higher standard rating is permitted. Both limits bind. On an adjustable-trip breaker the setting is not a standard rating to miss, so Note 1 never engages and the cell percentage stays a hard maximum. Its superscript appears on the 125 percent cells and nowhere else. The 250 percent cells carry marker 3 instead, and Note 3 is the coordinated thermal overload permission of six times and four times rated current. It says nothing at all about rounding. Under a table titled Maximum Rating or Setting of Overcurrent Protection, a cell Note 1 does not reach is a ceiling, and rounding a ceiling up oversizes the device and defeats the protection the table exists to require. On the 45 kVA example the ceiling is 135.3 amps: rounding down gives 125 amps, and rounding up would give a device above the code maximum.
When is primary-only protection allowed?
Table 450.3(B) has a primary only row, and satisfying it protects the transformer. That is not the whole question, because it does not protect the secondary conductors. NEC 240.4(F) states that single-phase transformers other than 2-wire, and multiphase transformers other than 3-wire delta-delta, do not have their secondary conductors protected by the primary device. Conductors fed by a single-phase transformer with a 2-wire single-voltage secondary, or by a three-phase delta-delta transformer with a 3-wire single-voltage secondary, may be protected by the primary device, provided that protection also does not exceed the secondary conductor ampacity multiplied by the secondary-to-primary voltage ratio. 240.21(C)(1) carries the same rule. So on a 480 to 208Y/120 wye secondary, which is the most common dry-type step-down in a commercial building, the primary device cannot be counted as the secondary conductors protection, so those conductors need their own protection under 240.21(C). Primary-only protection of the transformer itself is still permitted by Table 450.3(B).
What are the 9 amp and 2 amp columns for?
Table 450.3(B) does not use one percentage for every transformer. On the primary only row, a primary of 9 amps or more takes 125 percent, a primary under 9 amps takes 167 percent, and a primary under 2 amps takes 300 percent. Small control transformers land in those columns constantly. A 1 kVA 480 volt control transformer draws 2.08 amps on the primary, which is under 9, so the ceiling is 167 percent, or 3.48 amps. That cell has no Note 1 marker, so it rounds down, and the largest standard rating at or below 3.48 amps is a 3 amp fuse. Note that the answer is a fuse: NEC 240.6(A) gives fuses four ratings a circuit breaker cannot use, 1, 3, 6 and 601 amps, and on a transformer this small there is no standard circuit breaker small enough to satisfy the ceiling at all. On the primary and secondary row the primary stays at 250 percent across all three primary columns, including under 9 and under 2 amps.
How do you calculate transformer rated current?
Rated current is the kVA rating times 1000, divided by the voltage on that side, and for a three-phase transformer divided again by 1.732. Compute it separately for each side, because the two sides have different currents and Table 450.3(B) reads each against its own column. On the 45 kVA 480 to 208Y/120 example the primary is 45 times 1000 divided by 480 and by 1.732, which is 54.1 amps, and the secondary is 45 times 1000 divided by 208 and by 1.732, which is 124.9 amps. Leaving the 1.732 out is a common and expensive slip: the same 45 kVA at 480 volts single-phase draws 93.75 amps, about 73 percent higher, and every device chosen from that number comes out oversized.
What does Note 3 do?
Note 3 applies to the 250 percent cells, the primary side of the primary and secondary row. Where the transformer is equipped with coordinated thermal overload protection provided by the manufacturer and arranged to interrupt the primary current, the primary device may instead be rated or set at not more than six times rated current for a transformer of 6 percent impedance or less, and not more than four times rated current for a transformer over 6 percent through 10 percent impedance. Above 10 percent impedance Note 3 does not reach the transformer and the 250 percent cell stands. Note 3 grants a larger multiplier. It does not grant a round-up: those cells are still maximums and still round down.
Is this the same as sizing the transformer secondary conductors?
No, and they are easy to confuse. This tool sizes the overcurrent protection for the transformer under 450.3(B). Sizing the conductors on the secondary is 240.21(C), and its ratios are taken against the device protecting the transformer primary. That is a different reference device from 240.21(B)(3), the feeder tap rule that happens to supply a transformer, whose ratios are taken against the device protecting the feeder. Same-looking arithmetic, different reference device, different conductor. Table 450.3(B) also gives maximums, so the device you actually install is often smaller: the load, the conductors, and the inrush the transformer needs to survive all push the other way.