NEC Wire Sizing

What Size Wire for a Garage Door Opener?

The breaker, copper and aluminum wire, and ground for the garage door opener circuit this page shows, with the NEC basis and the nameplate caveats that actually decide it.

Quick answer: This page shows a garage door opener on a 20A / 120V circuit with #12 copper (or #10 aluminum; aluminum on terminals identified for aluminum, NEC 2023, 110.14(A)) wire and a #12 copper ground. GFCI at a receptacle in a location under NEC 2023 210.8(A)(2).

Garage Door Opener Circuit Spec

Branch circuit shown for a garage door opener (NEC 210.11(C)(4), 210.8(A)(2), 210.52(G))

Swipe the table sideways to see the rest of its columns. →

Voltage120V
Breaker20A
Copper wire#12
Aluminum wire (75°C-marked terminations, SER or conduit)#10
Equipment ground (Cu)#12

A residential garage door opener plugs into a ceiling receptacle on the garage's 120V circuit. A receptacle is required in each vehicle bay (210.52(G)(1)). Under the 2023 and 2026 NEC it can share the 20A garage circuit (210.11(C)(4)), which supplies receptacle outlets including those 210.52(G)(1) requires; the 2020 text limits that circuit to the required ones and readily accessible outdoor receptacles. GFCI: plugged into a receptacle in a dwelling location NEC 2023 210.8(A) lists (210.8(A)(2) "Garages and also accessory buildings that have a floor located at or below grade level not intended as habitable rooms and limited to storage areas, work areas, and areas of similar use"), a garage door opener needs GFCI protection; 210.8(A) reaches 125-volt through 250-volt receptacles supplied by single-phase branch circuits rated 150 volts or less to ground. Which edition applies is the one your jurisdiction has adopted. Wire sized at NEC Table 310.16 (copper lead at the 60°C column for NM-B); ground per NEC Table 250.122. The appliance nameplate lists the exact minimum circuit and maximum breaker; it governs over the circuit shown here.

Aluminum branch conductors are 75°C-rated AA-8000 alloy (SER cable, or XHHW-2 / THWN-2 in conduit); there is no 60°C aluminum NM-B, so the aluminum row uses the 75°C column. Where the terminations are rated 60°C only, size aluminum from the 60°C column instead (#10 here). Aluminum: the terminals it lands on must be identified for aluminum conductors (NEC 2023, 110.14(A)).

Adding this as a new load? Check whether your panel can handle it (the NEC 220.87 service check), or compare it against the breaker size by load chart.


Size Your Exact Circuit

It opens on this page's 20 A circuit at the 60°C column. For a nameplate that differs from this page's circuit, enter your exact load and conditions. For a long run, the result links to the voltage drop calculator, which checks that wire over your run; this tool does not size for voltage drop.

Loading calculator...

The code sections this page cites are named in the source receipt.


Frequently Asked Questions

What size wire do I need for a garage door opener?

This page shows a garage door opener on a 20A / 120V circuit, which calls for #12 copper (or #10 aluminum; aluminum on terminals identified for aluminum, NEC 2023, 110.14(A)) conductors and a #12 copper equipment ground per NEC Table 250.122. A residential garage door opener plugs into a ceiling receptacle on the garage's 120V circuit. A receptacle is required in each vehicle bay (210.52(G)(1)). Under the 2023 and 2026 NEC it can share the 20A garage circuit (210.11(C)(4)), which supplies receptacle outlets including those 210.52(G)(1) requires; the 2020 text limits that circuit to the required ones and readily accessible outdoor receptacles. GFCI: plugged into a receptacle in a dwelling location NEC 2023 210.8(A) lists (210.8(A)(2) "Garages and also accessory buildings that have a floor located at or below grade level not intended as habitable rooms and limited to storage areas, work areas, and areas of similar use"), a garage door opener needs GFCI protection; 210.8(A) reaches 125-volt through 250-volt receptacles supplied by single-phase branch circuits rated 150 volts or less to ground. Which edition applies is the one your jurisdiction has adopted.

What size breaker for a garage door opener?

A 20A single-pole (120V) breaker. The #12 copper conductors are matched to that 20A rating. Do not oversize the breaker to a wire it does not protect: the breaker and the conductor go up together. Always confirm against the appliance nameplate, which lists the exact minimum circuit and maximum overcurrent device.

Does a garage door opener need GFCI protection?

It depends on where it is installed. GFCI: plugged into a receptacle in a dwelling location NEC 2023 210.8(A) lists (210.8(A)(2) "Garages and also accessory buildings that have a floor located at or below grade level not intended as habitable rooms and limited to storage areas, work areas, and areas of similar use"), a garage door opener needs GFCI protection; 210.8(A) reaches 125-volt through 250-volt receptacles supplied by single-phase branch circuits rated 150 volts or less to ground. Which edition applies is the one your jurisdiction has adopted.

Can I use aluminum wire for a garage door opener?

Yes. On the 75C column (the column this page reads for aluminum), a 20A circuit needs #10 aluminum, versus #12 copper. Aluminum: the terminals it lands on must be identified for aluminum conductors (NEC 2023, 110.14(A)). If you run aluminum, apply antioxidant to the terminations, torque to the listed spec, and remember aluminum drops slightly more voltage on long runs.

What size breaker for a garage opener?

Same answer: garage opener is another name for a garage door opener. It uses a 20A / 120V circuit with #12 copper wire and a #12 copper ground. A residential garage door opener plugs into a ceiling receptacle on the garage's 120V circuit. A receptacle is required in each vehicle bay (210.52(G)(1)). Under the 2023 and 2026 NEC it can share the 20A garage circuit (210.11(C)(4)), which supplies receptacle outlets including those 210.52(G)(1) requires; the 2020 text limits that circuit to the required ones and readily accessible outdoor receptacles. GFCI: plugged into a receptacle in a dwelling location NEC 2023 210.8(A) lists (210.8(A)(2) "Garages and also accessory buildings that have a floor located at or below grade level not intended as habitable rooms and limited to storage areas, work areas, and areas of similar use"), a garage door opener needs GFCI protection; 210.8(A) reaches 125-volt through 250-volt receptacles supplied by single-phase branch circuits rated 150 volts or less to ground. Which edition applies is the one your jurisdiction has adopted.


Wire Size for Other Appliances