NEC Wire Sizing
What Size Wire for an Electric Dryer?
The breaker, copper and aluminum wire, and ground for the electric dryer circuit this page shows, with the NEC basis and the nameplate caveats that actually decide it.
Electric Dryer Circuit Spec
Branch circuit shown for an electric dryer (nameplate rating, load per NEC 220.54, GFCI per NEC 210.8(D))
Swipe the table sideways to see the rest of its columns. →
| Voltage | 240V |
| Breaker | 30A GFCI |
| Copper wire | #10 |
| Aluminum wire (75°C-marked terminations, SER or conduit) | #8 |
| Equipment ground (Cu) | #10 |
An electric dryer on a NEMA 14-30 receptacle takes a 30A / 240V circuit. A gas dryer needs only a 120V 15A outlet for its controls. On a 240V circuit, a 2-pole GFCI breaker is one way to provide GFCI protection. Where the 2023 NEC (210.8(D)) reaches the dryer itself, the 2020 NEC (210.8(A)(10)) reaches a dwelling's 125V through 250V receptacles in laundry areas. GFCI: NEC 2023 210.8(D) requires GFCI protection for the branch circuit or outlet supplying an electric dryer (210.8(D)(11) "Clothes dryers") rated 150 volts or less to ground and 60 amperes or less, hardwired or plugged in, wherever it is installed; which edition applies is the one your jurisdiction has adopted. Wire sized at NEC Table 310.16 (copper lead at the 60°C column for NM-B); ground per NEC Table 250.122. The appliance nameplate lists the exact minimum circuit and maximum breaker; it governs over the circuit shown here.
Maker's instruction: GE 7.2 cu. ft. Capacity Electric Dryer GTD38EASWWS, Quick Specs (Specification Revised 09/25), read 2026-11-13.
Aluminum branch conductors are 75°C-rated AA-8000 alloy (SER cable, or XHHW-2 / THWN-2 in conduit); there is no 60°C aluminum NM-B, so the aluminum row uses the 75°C column. Where the terminations are rated 60°C only, size aluminum from the 60°C column instead (#8 here). Aluminum: the terminals it lands on must be identified for aluminum conductors (NEC 2023, 110.14(A)).
Adding this as a new load? Check whether your panel can handle it (the NEC 220.87 service check), or compare it against the breaker size by load chart.
Size Your Exact Circuit
It opens on this page's 30 A circuit at the 60°C column. For a nameplate that differs from this page's circuit, enter your exact load and conditions. For a long run, the result links to the voltage drop calculator, which checks that wire over your run; this tool does not size for voltage drop.
The code sections this page cites are named in the source receipt.
Frequently Asked Questions
What size wire do I need for an electric dryer?
This page shows an electric dryer on a 30A / 240V circuit, which calls for #10 copper (or #8 aluminum; aluminum on terminals identified for aluminum, NEC 2023, 110.14(A)) conductors and a #10 copper equipment ground per NEC Table 250.122. GE's quick specs for the GTD38EASWWS electric dryer, rated "240V 5600W 24A 60Hz", read: "An individual, properly-grounded branch circuit, protected by a 30-amp circuit breaker or a time-delay fuse, is required." An electric dryer on a NEMA 14-30 receptacle takes a 30A / 240V circuit. A gas dryer needs only a 120V 15A outlet for its controls. On a 240V circuit, a 2-pole GFCI breaker is one way to provide GFCI protection. Where the 2023 NEC (210.8(D)) reaches the dryer itself, the 2020 NEC (210.8(A)(10)) reaches a dwelling's 125V through 250V receptacles in laundry areas. GFCI: NEC 2023 210.8(D) requires GFCI protection for the branch circuit or outlet supplying an electric dryer (210.8(D)(11) "Clothes dryers") rated 150 volts or less to ground and 60 amperes or less, hardwired or plugged in, wherever it is installed; which edition applies is the one your jurisdiction has adopted.
What size breaker for an electric dryer?
A 30A double-pole (240V) breaker. The #10 copper conductors are matched to that 30A rating, and it must be a GFCI breaker (or GFCI protection ahead of the appliance). Do not oversize the breaker to a wire it does not protect: the breaker and the conductor go up together. Always confirm against the appliance nameplate, which lists the exact minimum circuit and maximum overcurrent device.
Does an electric dryer need GFCI protection?
Yes. GFCI: NEC 2023 210.8(D) requires GFCI protection for the branch circuit or outlet supplying an electric dryer (210.8(D)(11) "Clothes dryers") rated 150 volts or less to ground and 60 amperes or less, hardwired or plugged in, wherever it is installed; which edition applies is the one your jurisdiction has adopted. Use a GFCI breaker or a GFCI device ahead of it.
Can I use aluminum wire for an electric dryer?
Yes. On the 75C column (the column this page reads for aluminum), a 30A circuit needs #8 aluminum, versus #10 copper. Aluminum: the terminals it lands on must be identified for aluminum conductors (NEC 2023, 110.14(A)). If you run aluminum, apply antioxidant to the terminations, torque to the listed spec, and remember aluminum drops slightly more voltage on long runs.
Wire Size for Other Appliances
Electric Range
#6 copper on a 50A / 240V circuit.
Electric Wall Oven
#8 copper on a 40A / 240V circuit.
Electric Cooktop
#8 copper on a 40A / 240V circuit.
Electric Water Heater
#10 copper on a 30A / 240V circuit.
Hot Tub
#6 copper on a 50A / 240V circuit.
Dishwasher
#12 copper on a 20A / 120V circuit.
Garbage Disposal
#14 copper on a 15A / 120V circuit.
Built-In Microwave
#12 copper on a 20A / 120V circuit.
Refrigerator
#12 copper on a 20A / 120V circuit.
Freezer
#12 copper on a 20A / 120V circuit.
Garage Door Opener
#12 copper on a 20A / 120V circuit.
Wire Size Calculator
Full NEC 310.16 sizing for any load, distance, and conditions.