NEC Wire Sizing

What Size Wire for a Built-In Microwave?

The breaker, copper and aluminum wire, and ground for a typical built-in microwave circuit, with the NEC basis and the nameplate caveats that actually decide it.

Quick answer: A built-in microwave typically needs a 20A / 120V circuit with #12 copper (or #10 aluminum) wire and a #12 copper ground. It must be GFCI protected.

Built-In Microwave Circuit Spec

Typical branch circuit for a built-in microwave (NEC 210.8(A), 210.23(B))
Voltage120V
Breaker20A GFCI
Copper wire#12
Aluminum wire (75°C, SER or conduit)#10
Equipment ground (Cu)#12

A built-in or over-the-range microwave should have its own dedicated 120V 20A circuit (sized to the nameplate per the manufacturer's instructions). Under the 2023 NEC, a microwave receptacle in the kitchen requires GFCI protection (210.8(A)), the same rule that covers the refrigerator. A countertop unit may share a small-appliance branch circuit, but a dedicated circuit avoids nuisance trips. Wire sized at NEC Table 310.16 (copper lead at the 60°C column for NM-B); ground per NEC Table 250.122. The appliance nameplate lists the exact minimum circuit and maximum breaker; it always governs over a typical value.

Aluminum branch conductors are 75°C-rated AA-8000 alloy (SER cable, or XHHW-2 / THWN-2 in conduit); there is no 60°C aluminum NM-B, so the aluminum row uses the 75°C column. Where the terminations are rated 60°C only, size aluminum from the 60°C column instead (#10 here).

Adding this as a new load? Check whether your panel can handle it (the NEC 220.87 service check), or compare it against the breaker size by load chart.


Long Run? Size It Exactly

For a long run where voltage drop matters, or a nameplate that differs from the typical value, enter your exact load, distance, and conditions.

Loading calculator...

Frequently Asked Questions

What size wire do I need for a built-in microwave?

A built-in microwave typically uses a 20A / 120V circuit, which calls for #12 copper (or #10 aluminum) conductors and a #12 copper equipment ground per NEC Table 250.122. A built-in or over-the-range microwave should have its own dedicated 120V 20A circuit (sized to the nameplate per the manufacturer's instructions). Under the 2023 NEC, a microwave receptacle in the kitchen requires GFCI protection (210.8(A)), the same rule that covers the refrigerator. A countertop unit may share a small-appliance branch circuit, but a dedicated circuit avoids nuisance trips.

What size breaker for a built-in microwave?

A 20A single-pole (120V) breaker. The #12 copper conductors are matched to that 20A rating, and it must be a GFCI breaker (or GFCI protection ahead of the appliance). Do not oversize the breaker to a wire it does not protect: the breaker and the conductor go up together. Always confirm against the appliance nameplate, which lists the exact minimum circuit and maximum overcurrent device.

Does a built-in microwave need GFCI protection?

Yes. Current NEC requires GFCI protection for this appliance (NEC 210.8(A), 210.23(B)). Use a GFCI breaker or a GFCI device ahead of it.

Can I use aluminum wire for a built-in microwave?

Yes. On the 75C column (the usual basis for aluminum), a 20A circuit needs #10 aluminum, versus #12 copper. Aluminum is common on larger circuits and services to save cost; apply antioxidant to the terminations, torque to the listed spec, and remember aluminum drops slightly more voltage on long runs.

What size breaker for a microwave?

Same answer: microwave is another name for a built-in microwave. It uses a 20A / 120V circuit with #12 copper wire and a #12 copper ground, GFCI protected. A built-in or over-the-range microwave should have its own dedicated 120V 20A circuit (sized to the nameplate per the manufacturer's instructions). Under the 2023 NEC, a microwave receptacle in the kitchen requires GFCI protection (210.8(A)), the same rule that covers the refrigerator. A countertop unit may share a small-appliance branch circuit, but a dedicated circuit avoids nuisance trips.


Wire Size for Other Appliances