Electrical · Conductor sizing

Is the neutral a current-carrying conductor?

NEC 310.15(E) prints three conditions, and which one describes your circuit is the answer. Describe the system and what you are pulling, and this names the subdivision that decides it, counts the whole raceway, and carries the count through to a conductor size and a breaker.

Field brief
(1) own circuita neutral carrying only the unbalanced current of the other conductors of its own circuit. A 120/240 V three-wire circuit is this case, and it is the one people read as (2) because it looks the same at the panel.not counted
(2) wye, 3-wirethe neutral of a three-wire circuit taken from a 4-wire, 3-phase, wye-connected system. On its own it lands in 1-3, this tool's own no-adjustment key and not a row of the table, so it moves nothing until something else shares the raceway.counted
(3) wye, nonlinearthe neutral of a 4-wire 3-phase wye circuit where the major portion of the load is nonlinear. The same install goes 1-3 to 4-6 on that answer alone. The NEC prints no percentage for it.counted
Loading calculator...

The three branches, and the one that catches people

A 120/240 V three-wire circuit is not an (2) circuit, and it looks like one. (2) is scoped by its own printed words to a four-wire, three-phase, wye-connected system. A 120/240 volt service is supplied from a center-tapped single-phase transformer, so its neutral carries the difference between the two legs, which is the unbalanced current (1) describes. The two circuits are wired the same way at the panel and land in different subdivisions.

Counting the neutral under (2) does not move the adjustment by itself. Two phase conductors plus the counted neutral is three, and the table starts above three. It bites as soon as anything else is in the raceway, and one pulled spare is enough to do it.


The same conduit, answered two ways

A single four-wire wye circuit, with nothing else in the raceway, changes band on the load character alone. Both rows below are computed by the engine at build time, not typed.

The runNeutral counted?Lands in
One 4-wire wye circuit, load mostly linearNo1-3, this tool's own no-adjustment key and not a row of the table
The same circuit, load mostly nonlinearYesthe 4-6 row of Table 310.15(C)(1)
Four of those nonlinear circuits in one conduitYes, each of themthe 10-20 row of Table 310.15(C)(1)

The third row is the raceway point. The adjustment is per raceway, not per circuit, and the Table 310.15(C)(1) footnote is what says so: it counts the total number of conductors in the raceway or cable and says nothing about which circuit each conductor belongs to.


What this tool will not do

It will not put a number on “the major portion of the load”. (3) turns on that phrase and does not quantify it, and no percentage appears anywhere in 310.15(E) or in the Table 310.15(C)(1) footnote, which is the text this tool holds under receipt. There is no percentage to quote, and inventing one would put a fabricated number on a fire path. The tool asks you to characterise the load and says what each answer costs. That is the one place it declines because a question you can answer is unanswered. It also declines when a printed cap is asserted outside its own printed range, and when two answers cannot both be true of one run, and it names the provision when it does.

Where a run is described in parts, it takes the most restrictive part, and that rule is ours. 310.15(C)(1) prints no sentence about combining parts of a run. What it prints is that the ampacity of each conductor shall be reduced, and a conductor is one object passing through every part of its own run, so taking the worst part is the least restrictive composition that still cannot overstate what that conductor may carry.

It sizes the conductor. It does not approve the installation. Your AHJ decides what your job requires. (F) Grounding or Bonding Conductor. A grounding or bonding conductor shall not be counted when applying the provisions of 310.15(C)(1).


Common questions

Is the neutral a current-carrying conductor?

It depends on which of the three printed branches of NEC 310.15(E) describes your circuit, and 310.15(E) prints no general rule beyond those three: its own lead-in says neutral conductors are considered current carrying "in accordance with any of the following". Under (E)(1) a neutral that carries only the unbalanced current from the other conductors of the same circuit is not required to be counted. Under (E)(2) the neutral of a 3-wire circuit taken from a 4-wire 3-phase wye system is counted, because it carries approximately the same current as the line-to-neutral load currents of the other conductors. Under (E)(3) the neutral of a 4-wire 3-phase wye circuit is counted where the major portion of the load is nonlinear. The equipment grounding conductor is not counted when applying the adjustment, under 310.15(F).

How many current-carrying conductors are in my conduit?

The count is the total number of conductors in the raceway or cable, which is the Table 310.15(C)(1) footnote's own wording, so every circuit sharing the conduit is added together rather than counted separately. Pulled but unterminated spare conductors are included by that same footnote. Conductors connected to components that cannot be simultaneously energized, such as conductors on a mechanical interlock or a transfer switch, are excluded by it. Grounding and bonding conductors are excluded by 310.15(F). Then 310.15(E) decides, per circuit, whether that circuit's neutral is among them.

Is a 120/240V neutral counted as a current-carrying conductor?

No, and the reason is the part that gets misread. A 120/240 V three-wire circuit is supplied from a center-tapped single-phase transformer, not a wye, so NEC 310.15(E)(2) does not reach it: (E)(2) is scoped by its own printed words to "a 4-wire, 3-phase, wye-connected system". That neutral carries the difference between the two legs, which is the unbalanced current (E)(1) describes, so it is not required to be counted. A three-wire circuit of two hots and a neutral is therefore two current-carrying conductors. Harmonics do load a single-phase three-wire neutral in the real world, and (E)(3) is scoped to a 4-wire 3-phase wye circuit and does not reach that case either, so the code text as printed does not require counting it. Your AHJ may.

Does counting the neutral change the derating on its own?

Not on a single circuit taken from a wye. Two phase conductors plus a counted neutral is three current-carrying conductors, and Table 310.15(C)(1)'s own title is "Adjustment Factors for More Than Three Current-Carrying Conductors", so three or fewer is the absence of an adjustment rather than a row of the table. So a single (E)(2) circuit lands in 1-3, this tool's own no-adjustment key and not a row of the table. It starts to matter as soon as anything else is in the raceway, and a spare conductor is enough, because the count is the total in the raceway and spares are counted. A technician who learns "(E)(2) means count the neutral" and stops there will not understand why nothing changed.

What does a nonlinear load change on a 3-phase wye circuit?

The whole adjustment. Three phase conductors with a linear load is three current-carrying conductors, which lands in 1-3. The same physical install with the major portion of the load nonlinear counts the neutral under (E)(3), which makes it four, landing in 4-6. That is the first band the table prints an adjustment for, so the identical conduit is derated differently on the strength of what is plugged into it. Nonlinear load is switch-mode power supplies, LED drivers, variable-frequency drives, electronic ballasts, UPS and computing equipment.

What percentage of the load has to be nonlinear for the neutral to count?

310.15(E)(3) turns on the phrase "the major portion of the load" and does not quantify it, and no percentage appears in 310.15(E) or in the Table 310.15(C)(1) footnote, which is the text this tool holds under receipt. No number can be quoted for it, and this tool supplies none of its own. That judgement is yours and your AHJ's. If you cannot tell yet, answering that the load is mostly nonlinear counts the neutral, which raises the conductor count and so applies a smaller adjustment factor, and of the two answers it is the only one that cannot overstate what your conductor may carry.

Do spare conductors count toward the derating?

Yes. The Table 310.15(C)(1) footnote counts "the total number of conductors in the raceway or cable, including spare conductors", so a pulled but unterminated spare is in the count. Leaving spares out lowers the count, which raises the adjustment factor, which permits more ampacity on a conductor that is sharing the conduit with them. That is the direction that matters.

Does the equipment grounding conductor count?

No. NEC 310.15(F) excludes a grounding or bonding conductor when applying the provisions of 310.15(C)(1), and it applies whichever way 310.15(E) decides the neutral. Isolated and insulated grounding conductors are excluded on the same basis. Five wires in a conduit can be four current-carrying conductors plus one equipment ground.


Next in this job

Know the count? Size the conductor.

This tool carries a run to a conductor and a breaker on its own. The derating calculator takes the same count and shows the factor against the full ambient correction table.