NEC Wire Sizing

What Size Wire for a Garbage Disposal?

The breaker, copper and aluminum wire, and ground for the garbage disposal circuit this page shows, with the NEC basis and the nameplate caveats that actually decide it.

Quick answer: This page shows a garbage disposal on a 15A / 120V circuit with #14 copper (or #12 aluminum; aluminum on terminals identified for aluminum, NEC 2023, 110.14(A)) wire and a #14 copper ground. GFCI at a receptacle in a location under NEC 2023 210.8(A)(6) and 210.8(A)(7).

Garbage Disposal Circuit Spec

Branch circuit shown for a garbage disposal (nameplate rating)

Swipe the table sideways to see the rest of its columns. →

Voltage120V
Breaker15A
Copper wire#14
Aluminum wire (75°C-marked terminations, SER or conduit)#12
Equipment ground (Cu)#14

A garbage disposal is sized to its nameplate on a dedicated 120V circuit: InSinkErator's 1/2 HP Badger 5 lists an average load of 6.3 amps at 120 volts, within the 15A circuit this page shows; a larger unit can take 20A. Confirm whether local practice lets it share the dishwasher circuit. GFCI: plugged into a receptacle in a dwelling location NEC 2023 210.8(A) lists (210.8(A)(6) "Kitchens", 210.8(A)(7) "Areas with sinks and permanent provisions for food preparation, beverage preparation, or cooking"), a garbage disposal needs GFCI protection; 210.8(A) reaches 125-volt through 250-volt receptacles supplied by single-phase branch circuits rated 150 volts or less to ground. Hardwired, it has no receptacle for 210.8(A) to reach, and 2023 210.8(D)'s list does not name it. Which edition applies is the one your jurisdiction has adopted. Wire sized at NEC Table 310.16 (copper lead at the 60°C column for NM-B); ground per NEC Table 250.122. The appliance nameplate lists the exact minimum circuit and maximum breaker; it governs over the circuit shown here.

Aluminum branch conductors are 75°C-rated AA-8000 alloy (SER cable, or XHHW-2 / THWN-2 in conduit); there is no 60°C aluminum NM-B, so the aluminum row uses the 75°C column. Where the terminations are rated 60°C only, size aluminum from the 60°C column instead (#12 here). Aluminum: the terminals it lands on must be identified for aluminum conductors (NEC 2023, 110.14(A)).

Adding this as a new load? Check whether your panel can handle it (the NEC 220.87 service check), or compare it against the breaker size by load chart.


Size Your Exact Circuit

It opens on this page's 15 A circuit at the 60°C column. For a nameplate that differs from this page's circuit, enter your exact load and conditions. For a long run, the result links to the voltage drop calculator, which checks that wire over your run; this tool does not size for voltage drop.

Loading calculator...

The code sections this page cites are named in the source receipt.


Frequently Asked Questions

What size wire do I need for a garbage disposal?

This page shows a garbage disposal on a 15A / 120V circuit, which calls for #14 copper (or #12 aluminum; aluminum on terminals identified for aluminum, NEC 2023, 110.14(A)) conductors and a #14 copper equipment ground per NEC Table 250.122. A garbage disposal is sized to its nameplate on a dedicated 120V circuit: InSinkErator's 1/2 HP Badger 5 lists an average load of 6.3 amps at 120 volts, within the 15A circuit this page shows; a larger unit can take 20A. Confirm whether local practice lets it share the dishwasher circuit. GFCI: plugged into a receptacle in a dwelling location NEC 2023 210.8(A) lists (210.8(A)(6) "Kitchens", 210.8(A)(7) "Areas with sinks and permanent provisions for food preparation, beverage preparation, or cooking"), a garbage disposal needs GFCI protection; 210.8(A) reaches 125-volt through 250-volt receptacles supplied by single-phase branch circuits rated 150 volts or less to ground. Hardwired, it has no receptacle for 210.8(A) to reach, and 2023 210.8(D)'s list does not name it. Which edition applies is the one your jurisdiction has adopted.

What size breaker for a garbage disposal?

A 15A single-pole (120V) breaker. The #14 copper conductors are matched to that 15A rating. Do not oversize the breaker to a wire it does not protect: the breaker and the conductor go up together. Always confirm against the appliance nameplate, which lists the exact minimum circuit and maximum overcurrent device.

Does a garbage disposal need GFCI protection?

It depends on where it is installed. GFCI: plugged into a receptacle in a dwelling location NEC 2023 210.8(A) lists (210.8(A)(6) "Kitchens", 210.8(A)(7) "Areas with sinks and permanent provisions for food preparation, beverage preparation, or cooking"), a garbage disposal needs GFCI protection; 210.8(A) reaches 125-volt through 250-volt receptacles supplied by single-phase branch circuits rated 150 volts or less to ground. Hardwired, it has no receptacle for 210.8(A) to reach, and 2023 210.8(D)'s list does not name it. Which edition applies is the one your jurisdiction has adopted.

Can I use aluminum wire for a garbage disposal?

Yes. On the 75C column (the column this page reads for aluminum), a 15A circuit needs #12 aluminum, versus #14 copper. Aluminum: the terminals it lands on must be identified for aluminum conductors (NEC 2023, 110.14(A)). If you run aluminum, apply antioxidant to the terminations, torque to the listed spec, and remember aluminum drops slightly more voltage on long runs.


Wire Size for Other Appliances