Refrigerant Blends

Refrigerant Blend Top-Off Check

The leak is fixed and the machine is low. Can you top the blend off, or does a blend have to come out? The field calls it a gamble. The manufacturers have published the answer, in glide and in leak-and-recharge data, and this tool reads it for 15 blends.

Field brief
Azeotropes R-513A, R-514A, R-515B, R-507A: their makers print zero glide, so a leak takes the blend at its own composition and there is nothing to fractionate. Top off. 0 R glide
Zeotropes top off with the same blend, charged as liquid. The composition can shift only after a vapor leak from an idle or quiescent two-phase region, and Chemours' worst case for R-407C (50 percent lost, recharged four times, Table 3 of C-11107) bottoms out at 91 percent capacity with efficiency unchanged. under 11.5 F glide
Then a top-off is a refrigerant addition: The owner or operator must calculate the leak rate every time refrigerant is added to an appliance unless the addition is made immediately following a retrofit, installation of a new refrigerant-containing appliance, or qualifies as a seasonal variance. Leak rate on every addition

The Blends, With the Glide Their Makers Print

Every figure is the manufacturer's own print, quoted on the result and in the receipt below. A glide marked "at condition" or "average" is smaller than the total dew-minus-bubble glide; Chemours puts the effective evaporator glide at about 65 to 75 percent of the total.
BlendComposition (ASHRAE 34)GlideMaker says
R-513AR-1234yf/134a (56.0/44.0)0 (azeotrope)Azeotrope with zero glide; repeated top-offs keep the A1 rating (Chemours FAQ)
R-514AR-1336mzz(Z)/1130(E) (74.7/25.3)0 (azeotrope)Azeotrope with zero glide (B1, higher toxicity)
R-515BR-1234ze(E)/227ea (91.1/8.9)0 (azeotrope)Azeotropic blend, zero glide
R-507AR-125/143a (50.0/50.0)0 (azeotrope)Azeotropic mixture; no separation if leakage occurs
R-410AR-32/125 (50.0/50.0)<0.5 FTotal glide under 0.5 F; charge as liquid
R-404AR-125/143a/134a (44.0/52.0/4.0)<1.1 FTotal glide under 1.1 F (0.7 R average); one Chemours print disagrees
R-407CR-32/125/134a (23.0/25.0/52.0)<11.5 FExcellent behavior through vapor leaks and recharges; worst case 9 percent capacity after four 50 percent losses
R-407AR-32/125/134a (20.0/40.0/40.0)~8 R at conditionGlide about 8 F at cycle conditions; no leak-recharge statement on file
R-448AR-32/125/1234yf/134a/1234ze(E) (26.0/26.0/20.0/21.0/7.0)~10.4 R from PT tableZeotropic blend, 10.4 F glide off Honeywell's own PT table; no leak-recharge statement on file
R-449AR-32/125/1234yf/134a (24.3/24.7/25.3/25.7)~7.6 R at conditionFractionation not expected to cause problems; 10 percent loss and recharge, about 2 percent capacity
R-450AR-134a/1234ze(E) (42.0/58.0)~1.1 R from PT tableSlight glide, 1.1 F on Honeywell's own PT chart; liquid-charge only; no top-off statement printed
R-454BR-32/1234yf (68.9/31.1)~2 RVery low temperature glide, can be topped off after leaks
R-452BR-32/125/1234yf (67.0/7.0/26.0)~1.8 RVery low temperature glide (~1 K); no leak-recharge statement on file
R-454AR-32/1234yf (35.0/65.0)~9 RCan be topped off after leaks
R-454CR-32/1234yf (21.5/78.5)~10.8 RCan be topped-off after leaks

The Question, Verbatim, and the Answer

A technician asked, of an R-513A chiller: "being a refrigerant blend can the remaining refrigerant charge be topped off once the leak has been fixed? Or does the old refrigerant charge get scrapped since it's a blend?" The best answer offered was that it is a gamble. It is not. Top it off with R-513A. An azeotrope leaks at its own composition, so there is nothing to fractionate and the remaining charge stays in the machine.

The instinct behind the question is sound for a different case: a wide-glide zeotrope that leaked vapor while sitting idle. Even there the manufacturer's own study says top it off. Chemours ran R-407C through five cycles of losing half its charge as vapor with the unit off and recharging, and capacity settled at 91 percent of original with efficiency unchanged; the same document says a leak from a running unit leaves the composition essentially unchanged, and that in practice a heat pump held its loss to 4 percent after the second recharge. For R-454B, R-454A and R-454C Chemours prints "can be topped off after leaks" on the datasheet itself, at glides from 2 to 10.8 R. Glide tells you how far the composition can drift and under what kind of leak. It does not tell you to scrap a charge.

Two things this page will not do. It will not invent a glide cutoff between "near-azeotropic" and "zeotropic", because neither ASHRAE 34 nor either manufacturer prints one. And it will not print a capacity penalty for a blend whose maker has not published one: the published cases on file are for R-507A, R-407C, R-449A, and they are quoted only for those blends. Where the manufacturer's prints disagree with each other, as three Chemours documents do on R-404A's glide (under 1.1 F in one, 0.7 R average in another, about 4 F in the third), the disagreement is disclosed on the result rather than resolved by guessing.


Frequently Asked Questions

I have an R-513A leak on a chiller. Being a blend, can the remaining charge be topped off once the leak is fixed, or does it get scrapped?

Top it off. R-513A (Opteon XP10) is an azeotrope: its maker prints a temperature glide of 0 R. Its maker prints "azeotrope with zero glide"; property table "temperature glide 0 r (0 k)", and an azeotrope leaks at its own composition, so there is nothing to fractionate and the remaining charge stays. Chemours also addresses repeat top-offs in passing, answering a flammability question that presumes the practice: "If you top off Opteon XP40 (R-449A) or XP10 (R-513A) multiple times, will this impact its A1 nonflammable rating?" "No. As part of the ASHRAE Standard 34 listing process for an A1 rating, the refrigerant blend undergoes rigorous fractionation testing, including multiple leak recharge scenarios, in order to ensure that the blend will always maintain a nonflammable A1 rating." Charge it as liquid, and remember the top-off is a refrigerant addition under 40 CFR 84.106(b), so the leak rate is calculated on it.

What is temperature glide, and why does it decide whether a blend can be topped off?

Glide is the difference between the temperature at which a blend starts to boil (the bubble point) and the temperature at which the last liquid boils away (the dew point) at one pressure. A pure refrigerant and an azeotrope have none; a zeotropic blend's liquid and vapor have different compositions in the two-phase regions of the system, so a leak of vapor alone from a two-phase region takes more of the low-boiling components and leaves the charge richer in the high-boiling one. That is fractionation, and glide is the measure of how much of it is possible. In the single-phase regions it cannot happen at all: "In the single phase regions of a refrigeration system (superheated vapor and subcooled liquid), the composition of a refrigerant mixture is constant and behaves exactly like a single component refrigerant."

Does a zeotropic blend like R-407C, R-448A or R-449A have to be recovered and recharged after a leak?

Not according to the manufacturer documents that address it, which are Chemours' on R-507A, R-407C, R-449A, and the numbers are theirs; for the other zeotropes here no maker has published a leak-and-recharge statement either way. Chemours modelled the worst case for R-407C, a blend with total glide under 11.5 F: the unit off, 50 percent of the charge lost as vapor from a two-phase region, and recharged, five times over. Relative capacity went 100, 95, 93, 92, 91, 91 percent with efficiency unchanged, and Chemours' summary is that "capacity loss is limited to 9%, as the performance of Freon 407C levels out after four 50% leak/recharges", while a heat-pump experiment held the loss at 4 percent after the second recharge. For R-449A the Chemours FAQ says a 10 percent loss and recharge costs a theoretical 2 percent of capacity and no COP. And a leak from a running machine takes liquid and vapor together, leaving the composition "essentially unchanged". So the honest verdict is: top off with the same blend, charged as liquid, expect at most a small shift, and recover and recharge if the machine does not perform afterward or the charge has been mixed with something else.

Which blends are azeotropes, and which have glide?

Azeotropes, by their makers' own descriptions: R-513A, R-514A, R-515B, R-507A. Zeotropes with a printed glide: R-410A (under 0.5 F), R-404A (under 1.1 F), R-407C (under 11.5 F), R-407A (about 8 R), R-448A (about 10.4 R), R-449A (about 7.6 R), R-450A (about 1.1 R), R-454B (about 2 R), R-452B (about 1.8 R), R-454A (about 9 R), R-454C (about 10.8 R). Chemours prints "can be topped off after leaks" on R-454B, R-454A and R-454C, the last two at 9 to 10.8 R of glide, so glide alone does not forbid a top-off; it sets how much the composition can drift and under which kind of leak.

Why does it matter whether the machine was running when it leaked?

Because that decides whether the leak took vapor alone from a two-phase region. Chemours, on R-407C: "If there is a Freon 407C leak from an operating unit in a two-phase region where mixing occurs (heat exchangers or expansion device), both the vapor and liquid will leak from the unit. The composition of the refrigerant left in the system will remain essentially unchanged from the original composition." And: "if the unit is not operating and there is a vapor leak from a static two-phase region, the composition of the refrigerant that remains in the unit will change." A leak from a liquid line or the suction line is single-phase and changes nothing. If you do not know, this tool treats the leak as the idle case, which is the one where the shift is possible.

Why does the tool insist on charging liquid?

Because the vapor above the liquid in a blend cylinder is not the blend. "As with any other refrigerant blend, when charging equipment with Freon 407C, remove liquid refrigerant from the cylinder to charge the unit." Chemours says the same of R-410A ("To achieve optimum performance, remove as a liquid from the cylinder"), and it applies to every zeotrope here. Liquid goes into the high side or is throttled into the suction line through a metering device; it is never dumped into a running compressor.

Does a top-off count as a refrigerant addition for the EPA leak rate?

Yes. "The owner or operator must calculate the leak rate every time refrigerant is added to an appliance unless the addition is made immediately following a retrofit, installation of a new refrigerant-containing appliance, or qualifies as a seasonal variance." (40 CFR 84.106(b)). Every blend on this page that contains an HFC is covered by the AIM Act leak repair rule at a full charge of 15 lb or more, so the pounds you add to top off are the pounds the leak rate is computed from. The leak-rate calculator link on this page carries the blend, the appliance type, the charge and the pounds, and the calculator's own applicability verdict is shown beside it once the charge is entered.

Can I top a blend off with a different refrigerant?

No. "Can you top off Opteon XP40 (R-449A) with any other refrigerant?" "No, mixing refrigerants is not recommended. If Opteon XP40 (R-449A) were to be topped off with a different refrigerant, the resulting mixture would no longer be Opteon XP40. The pressure-temperature characteristics and performance would be impacted." A mixed charge also cannot be reclaimed, and it is one of the few cases where recovering and recharging with virgin refrigerant is the only honest answer, whatever the glide.


Related Calculators

Topped it off? The addition has a leak rate.

Under 40 CFR 84.106(b) the leak rate is calculated every time refrigerant is added. The leak-rate calculator applies the threshold for the appliance and lists the deadlines.