Put this calculator to work.Run it inside Claude, or embed it on your site. No login.Use this in ClaudeEmbed it

NEC 314.16

Box Fill Calculator

Field brief
NEC 314.16add the volume allowances for every conductor, device yoke, clamp, ground, and terminal block; over the box's rated volume means a bigger box.314.16(B)
Yoke = 2×each device yoke gets 2× the largest connected conductor volume; up to four grounds share one allowance, each beyond four adds a quarter.2× largest
Read itenter the box and its contents below for the fill total, the pass/fail, and the cited NEC subsection on every line.pass / fail

Intry VerifiedA worked default reading, traceable end to end: what it was calculated from, what it was run with, how it was checked, and who has final say.

Fits with room12 of 30.3 cu in, fits
Where this number comes fromIntry Verified
Calculated from
NEC 314.16(B), volumes per Table 314.16(A)
Run with
  • Box4x2-1/8 square
  • Conductors3 #14 AWG
  • Device yokes1
  • Grounds (EGC)1
Checked
Every figure an Intry calculator computes comes from a locked source module, not hand-typed. 21026 automated checks re-derive and source-check the numbers against the cited NEC section before each deploy. This is our own deterministic gate, not a third-party audit.
Final say
Your AHJ and local amendments have final say. Confirm before rough-in.
What Intry Verified means

Intry Verified · NEC 2023 · Build AE2FC52 · 2026-08-21

New: run this inside your AI assistant

Prefer to just ask? Add this to Claude, free.

Connect Intry to Claude once, then just say “use Intry to…” to run the box fill calculator from a plain-English question, on your phone, on the job. You get the number, what it means, and the cited NEC section, computed live, not guessed. Works on every Claude plan.

Use this in Claude

Embed the Box Fill Calculator on Your Site

Add it to any website, blog, or training page. One line of code, always the deployed engine, no login, no API key.

  1. Copy the code below.
  2. Paste it into any page, post, or CMS (WordPress, Squarespace, Webflow, raw HTML).
  3. Done. It always runs the currently deployed engine. Keep the credit line so readers know where it comes from.
Free. No login. No API key.

How to Use This Calculator

  1. Select a box type from the standard NEC 314.16(A) list, or toggle to “Enter custom volume” if your box has a manufacturer-stamped volume or you are using an extension ring. The dropdown shows each box type with its rated volume in cubic inches.
  2. Add your conductors by wire size and count. Count every conductor that enters the box: hot, neutral, travelers, and switch legs. If a wire passes through without termination, count it once. Do not count pigtails that originate inside the box.
  3. Enter device yokes, one for each switch, receptacle, or GFCI mounted in the box. Set the largest conductor size connected to any device.
  4. Check internal clamps if the box has built-in cable clamps. Select the largest conductor entering any clamp. All clamps share one volume allowance.
  5. Enter equipment grounding conductors. Count how many EGCs are present and select the largest. Up to four EGCs share a single volume allowance; each EGC beyond four adds a quarter allowance.
  6. Add terminal blocks if present (2023 NEC). Each block counts individually.
  7. Read your results. The fill bar shows percentage used. Green means compliant. If you exceed 100%, the calculator suggests the smallest standard box that would work.

NEC 314.16 Box Fill Rules Explained

NEC 314.16 governs the maximum number of conductors and devices permitted in outlet boxes, device boxes, and junction boxes. The rule exists for three critical safety reasons: preventing overheating from too many current-carrying conductors in a confined space, ensuring there is enough room to make reliable electrical connections without damaging wire insulation, and reducing the risk of wire damage during installation when conductors are forced into an overfilled box. Every electrician, from apprentice through master, encounters box fill calculations on the job and on licensing exams.

The calculation is straightforward in concept: add up the volume allowance for every item in the box, then verify the total does not exceed the box's rated volume in cubic inches. The complexity comes from knowing which items count, how they count, and which share allowances. NEC 314.16(B) breaks this into six subsections, each with its own counting rule.

Volume Allowance Rules per NEC 314.16(B)

314.16(B)(1), Conductors. Each conductor that originates outside the box and terminates or is spliced inside counts as one conductor volume. A conductor that passes through without splice counts once (not twice for entering and exiting). Equipment bonding jumpers, pigtails originating inside the box, and conductors that do not leave the box are not counted here. They fall under other subsections or are exempt. The volume per conductor depends on its wire gauge: #14 gets 2.00 cu in, #12 gets 2.25 cu in, and so on per NEC Table 314.16(B)(1).

314.16(B)(2), Clamps. If the box contains one or more internal cable clamps, all clamps together get a single volume allowance equal to the volume of the largest conductor entering any clamp. It does not matter whether the box has one clamp or four. The total is one volume. External clamps (those on the outside of the box) do not count.

314.16(B)(3), Support fittings. Each fixture stud, hickey, or similar support fitting inside the box counts as one conductor volume based on the largest conductor present. This calculator does not include support fittings as they are uncommon in standard device and junction boxes, but they must be counted when present.

314.16(B)(4), Device yokes. Each switch, receptacle, or device mounted on a yoke (strap) counts as two conductor volumes based on the largest conductor connected to that device. A single-gang receptacle is one yoke. A multi-gang device counts each gang. This is the rule that makes device boxes fill up fast. A single receptacle on #14 wire adds 4.00 cu in just for the yoke.

314.16(B)(5), Equipment grounding conductors. Up to four EGCs in the box share a single volume allowance based on the largest EGC present, and each EGC beyond four adds an additional quarter allowance (2020 and 2023 editions). Four #14 grounds count the same as one #14 ground: 2.00 cu in total. Six #14 grounds count 2.00 + 2 × 0.50 = 3.00 cu in. If one of those grounds is #12, every allowance is figured at 2.25 cu in.

314.16(B)(6), Terminal blocks (2023 NEC). Added in the 2023 edition, each terminal block, power distribution block, or similar wiring component installed inside the box counts individually. The volume allowance is the largest conductor connected to that terminal block. This closed a gap in previous editions where large terminal blocks could occupy significant space without any fill accounting.

Why Box Fill Matters

An overfilled box creates three distinct hazards. First, heat buildup: current-carrying conductors generate heat, and a cramped box prevents adequate heat dissipation. The insulation temperature ratings in NEC 310.16 assume adequate spacing and airflow. Pack too many conductors into a small box and the insulation runs hotter than its rating, accelerating degradation and increasing fire risk.

Second, connection reliability. Wire nuts, push-in connectors, and terminal screws need room to be properly installed and inspected. In an overfilled box, splices get jammed against the box walls, wire nuts back off under spring pressure from packed wires, and connections loosen over time. Loose connections arc, and arcing causes fires. Giving connections adequate space reduces callbacks and improves long-term reliability.

Third, installation damage. When an electrician pushes a device into an overfilled box, the conductors behind it get bent, compressed, and scraped against sharp box edges and device mounting screws. Nicked insulation creates potential short circuits and ground faults that may not present immediately but can fail months or years later. Proper box fill ensures conductors can be folded into the box without excessive force.

Understanding Box Fill Calculations Step by Step

The counting rules trip up apprentices and journeymen alike because different items in the box follow different rules. Here is the mental model: conductors count individually, devices count double, clamps count once regardless of quantity, and grounds count once for the first four plus a quarter each after that.

Start by counting conductors. Walk each cable into the box and count every individual conductor that crosses the box boundary. A 14/2 NM cable brings two insulated conductors (#14 hot and #14 neutral) plus one bare ground. The hot and neutral each count as one conductor for 314.16(B)(1). The bare ground goes into the EGC pool for 314.16(B)(5). A 14/3 NM cable adds three conductors plus one ground.

Next, count devices. Each receptacle, switch, dimmer, or GFCI mounted in the box is one device yoke. A duplex receptacle is one yoke. A two-gang box with two switches has two yokes. Each yoke gets two volume allowances at the size of the largest conductor connected to that device.

Then handle the shared items. If the box has internal clamps, add one volume at the largest clamped conductor size. Gather all equipment grounding conductors and add one volume at the largest EGC size, plus a quarter volume for each EGC beyond four. If there are terminal blocks (2023 NEC), add one volume per block at the largest conductor connected to each.

Finally, sum everything and compare to the box's rated volume. If the total exceeds the rated volume, you need a larger box. The fix is always to use a bigger box or reduce the number of items. Never ignore the calculation and force everything in.


NEC Table 314.16(B)(1) Volume Allowances

Each conductor size has a specific volume allowance in cubic inches. This table is the foundation of every box fill calculation.

NEC Table 314.16(B)(1): Volume allowance per conductor by wire size
Wire Size (AWG)Volume (cu in)
18 AWG1.50
16 AWG1.75
14 AWG2.00
12 AWG2.25
10 AWG2.50
8 AWG3.00
6 AWG5.00

NEC 314.16(A) Standard Metal Box Volumes

These are the NEC-listed standard box types with their rated volumes. If your box has a manufacturer-stamped volume, use that value instead, as it may differ slightly from these minimums.

NEC 314.16(A): Standard metal box volumes in cubic inches
Box TypeVolume (cu in)
4 x 1-1/4 round/octagonal12.5
4 x 1-1/2 round/octagonal15.5
4 x 2-1/8 round/octagonal21.5
4 x 1-1/4 square18.0
4 x 1-1/2 square21.0
4 x 2-1/8 square30.3
4-11/16 x 1-1/4 square25.5
4-11/16 x 1-1/2 square29.5
4-11/16 x 2-1/8 square42.0
3 x 2 x 1-1/2 device7.5
3 x 2 x 2 device10.0
3 x 2 x 2-1/4 device10.5
3 x 2 x 2-1/2 device12.5
3 x 2 x 2-3/4 device14.0
3 x 2 x 3-1/2 device18.0
4 x 2-1/8 x 1-1/210.3
4 x 2-1/8 x 1-7/813.0
4 x 2-1/8 x 2-1/814.5
Masonry 3-3/4 x 2 x 2-1/214.0
Masonry 3-3/4 x 2 x 3-1/221.0
FS single gang13.5
FD single gang18.0
FS double gang18.0
FD double gang24.0

Worked Examples

Example 1: Single-Gang Device Box with 4 #14 Conductors

A single-gang box with one 14/2 NM cable (feed) and one 14/2 NM cable (switch leg) feeding a single-pole switch. The box has internal clamps. Every insulated conductor entering the box is counted under 314.16(B)(1), so the two cables bring four #14 conductors, not three.

  • Conductors: 2 × 14/2 = 4 #14 insulated conductors × 2.00 = 8.00 cu in
  • Device yokes: 1 switch × (2 × 2.00) = 4.00 cu in
  • Internal clamps: 1 × 2.00 = 2.00 cu in
  • Equipment grounding: 1 × 2.00 = 2.00 cu in (2 grounds, but only 1 allowance)
  • Total: 16.00 cu in

A 3x2x2-3/4 device box provides only 14.0 cu in, so it fails. You need at least 16.0 cu in, so the next standard box up is a 3x2x3-1/2 device box (18.0 cu in), which also gives working room. This is why you count every conductor, device, clamp, and ground, not just the wires.

Example 2: 4-11/16 Square Box with Mixed Wire Sizes

A 4-11/16 x 2-1/8 square junction box with two 12/2 cables and one 14/3 cable, two device yokes (receptacles), internal clamps, and equipment grounding conductors.

  • #12 conductors: 4 (from two 12/2 cables) × 2.25 = 9.00 cu in
  • #14 conductors: 3 (from one 14/3 cable) × 2.00 = 6.00 cu in
  • Device yokes: 2 × (2 × 2.25) = 9.00 cu in (largest connected is #12)
  • Internal clamps: 1 × 2.25 = 2.25 cu in (largest conductor is #12)
  • Equipment grounding: 1 × 2.25 = 2.25 cu in (3 EGCs, largest is #12)
  • Total: 28.50 cu in

A 4-11/16 x 2-1/8 square box provides 42.0 cu in, compliant with 13.5 cu in to spare. A 4-11/16 x 1-1/4 at 25.5 cu in would fail. The mixed wire sizes require using the larger conductor volume for device yokes, clamps, and grounding calculations.

Example 3: Finding the Right Replacement for an Overfilled Box

A 3x2x2 device box (10.0 cu in) with one 12/2 cable and one 12/3 cable feeding a three-way switch, with internal clamps.

  • #12 conductors: 5 (2 from 12/2 + 3 from 12/3) × 2.25 = 11.25 cu in
  • Device yokes: 1 × (2 × 2.25) = 4.50 cu in
  • Internal clamps: 1 × 2.25 = 2.25 cu in
  • Equipment grounding: 1 × 2.25 = 2.25 cu in
  • Total: 20.25 cu in

The 3x2x2 box at 10.0 cu in is badly overfilled at 202% capacity. The minimum compliant standard box is a 4x1-1/2 square at 21.0 cu in. A 4x2-1/8 square at 30.3 cu in would provide comfortable working room. This is a common scenario in older homes where boxes were originally sized for fewer circuits and later had additional cables pulled in during renovations.


Frequently Asked Questions

Is the Intry Box Fill Calculator accurate and NEC compliant?

Every figure an Intry calculator computes comes from a locked source module, not hand-typed. 21026 automated checks re-derive and source-check the numbers against the cited NEC section before each deploy. This is our own deterministic gate, not a third-party audit. The per-tool receipt is public at https://www.intrysys.com/verified.

How do I calculate box fill in cubic inches per NEC?

Add up every volume allowance from NEC Table 314.16(B)(1), then compare the total to the box volume from Table 314.16(A). Each conductor counts by its size: #14 = 2.00 cu in, #12 = 2.25, #10 = 2.50, #8 = 3.00, #6 = 5.00. Each device yoke (receptacle or switch) counts as two allowances of the largest conductor connected to it. All internal cable clamps together count as one allowance of the largest conductor. All equipment grounds together count as one allowance of the largest ground. Sum every allowance in cubic inches, and the box volume must be equal or greater.

How many conductors are allowed in a 4 inch square junction box?

It depends on the box depth (NEC Table 314.16(A)). A 4 × 4 × 1-1/2 inch square box is 21.0 cu in, which holds 10 #14, 9 #12, or 8 #10 conductors when nothing else is in the box. A 4 × 4 × 2-1/8 inch box is 30.3 cu in: 15 #14, 13 #12, or 12 #10. Subtract two conductor allowances per device, one for clamps, and one for grounds before counting the remaining conductors.

What size box do I need for 4 receptacle wires?

You need at least an 18.0 cubic inch box, such as a 3x2x3-1/2 device box or a 4x1-1/4 square box. Four #14 conductors are 8.00 cu in, plus 4.00 for one device yoke, 2.00 for clamps, and 2.00 for a ground, totaling 16.00 cu in, and the next standard box up is 18.0 cu in. A 3x2x2-3/4 device box (14.0 cu in) fails. Always calculate the full fill including devices, clamps, and grounds, not just the wires.

Do ground wires count in box fill?

Yes, but not individually. Per NEC 314.16(B)(5) (2020 and 2023 editions), up to four equipment grounding conductors (EGCs) count as a single volume allowance based on the largest EGC present, and each EGC beyond four adds a quarter allowance. One to four #14 grounds consume 2.00 cu in together, but six #14 EGCs consume 2.00 + 2 x 0.50 = 3.00 cu in.

How do I count wires that pass through a box?

A conductor that passes through a box without splice, tap, or termination counts once for box fill purposes per NEC 314.16(B)(1). It enters and exits, but you only count it as one conductor. However, if that same conductor is spliced or terminated inside the box, it still counts the same way: once. The key distinction is that a pigtail (short wire connected from a device to a splice) originating inside the box does not count, because it does not enter the box from outside.

What changed in the 2023 NEC for box fill?

The 2023 NEC added section 314.16(B)(6) covering terminal blocks and similar components. Each terminal block, power distribution block, or similar device installed in a box now requires a volume allowance equal to the largest conductor connected to it. Before 2023, these components had no explicit volume allowance, which led to dangerously overfilled boxes in panel feedthrough and junction applications. If your jurisdiction has adopted the 2023 NEC, you must account for terminal blocks in every calculation.

Can I use an extension ring to add volume?

Yes, but only when the piece carries a marked cubic-inch capacity. A marked extension adds its marked volume to the base box volume. Read the marking on the ring in your hand rather than working from a typical figure: capacity varies with size and depth, and a published example is easy to misapply to a different part. Note that not every accessory of this shape counts. Plaster rings (mud rings) and levelling-type box extenders frequently carry no marked cubic-inch capacity at all, and a piece with no marking cannot be counted toward box fill. When using this calculator with a marked extension, select 'Enter custom volume' and enter the base box volume plus the marked ring volume.


How Many Wires in a Specific Box

Dedicated fill answers for the boxes you actually install, with the bare maximum and the realistic count once a device, clamps, and a ground are in the box.


Related Calculators

Box is legal, but what about the raceway feeding it?

Box fill and conduit fill get cited together on inspections. Run the conduit fill calculator against NEC Chapter 9 for the same conductors, or check the rest of the electrical tools.