Put this calculator to work.Run it inside Claude, or embed it on your site. No login.Use this in ClaudeEmbed it

NEC 314.16

Box Fill Calculator

Whether your conductors, devices, clamps and grounds fit the box, and which box to use if they do not.

Field brief
NEC 314.16add the volume allowances for every conductor, device yoke, clamp, ground, and terminal block; over the box's rated volume means a bigger box or fewer items in it.314.16(B)
Yoke = 2×each device yoke gets 2× the largest connected conductor volume; up to four grounds share one allowance, each beyond four adds a quarter.2× largest
Read itenter the box and its contents for the fill total, the pass/fail, and the cited NEC subsection on every line.pass / fail

Box Type

The standard boxes are the metal boxes of NEC Table 314.16(A). A nonmetallic box, or any box marked with its own volume, uses the marked volume (314.16(A)(2)): enter it as a custom volume. A box with a barrier is figured one space at a time (314.16(B)): enter each space's own volume, its share of the box less the space the barrier takes (314.16(A)).

Conductors

Count a conductor that passes through once, and a loop or coil of unbroken conductor at least twice the free length 300.14 requires as two (314.16(B)(1)).

Device Yokes

A device wider than a single 2 in. device box counts as one yoke for each gang it needs (314.16(B)(4)).

Internal Clamps

Support Fittings

Each type adds one allowance at the largest conductor present (NEC 314.16(B)(3)).

Equipment Grounding

Terminal Blocks

One allowance for each terminal block, NEC 314.16(B)(6)

Box Fill Volume
12 / 30.3 cu in
NEC 314.16 PASS
#14 conductors3 × 2.00 = 6.00
Device yokes1 × 4.00 = 4.00
Equipment grounding (all)1 × 2.00 = 2.00
Total Required12 cu in
Show the math
  1. TABLEThe box: 4x2-1/8 square, 30.3 cu in (Table 314.16(A), metal boxes)NEC Table 314.16(A)
  2. MATH#14 conductors: 3 × 2.00 = 6.00 cu inNEC 314.16(B)(1), Table 314.16(B)(1)
  3. MATHDevice yokes: 1 × 4.00 = 4.00 cu inNEC 314.16(B)(4)
  4. MATHEquipment grounding (all): 1 × 2.00 = 2.00 cu inNEC 314.16(B)(5)
  5. RESULTTotal required: 12 cu inNEC 314.16(B)
  6. RESULT12 cu in ≤ 30.3 cu in = PASSNEC 314.16

Each conductor that starts outside the box and ends or is spliced in it counts once, and one that passes through without a splice counts once. A loop or coil of unbroken conductor at least twice the free length 300.14 requires counts twice, so enter it as two. A conductor that never leaves the box, such as a pigtail, does not count. NEC 314.16(B)(1)
Internal cable clamps: one allowance for all of them, at the largest conductor in the box. A connector whose clamp sits outside the box takes none. NEC 314.16(B)(2)

Luminaire studs and hickeys: one allowance for each type present, at the largest conductor in the box. NEC 314.16(B)(3)

Each yoke or strap: two allowances at the largest conductor connected to its device. A device wider than a single 2 in. device box takes two for each gang it needs, so enter one yoke for each gang. NEC 314.16(B)(4)

Ground wires: one allowance for up to four, at the largest ground wire, and a quarter allowance for each one after four. NEC 314.16(B)(5)

Terminal blocks: one allowance for each block, at the largest conductor terminated on it. This tool takes the largest conductor you entered, which covers every conductor that enters the box; a pigtail that never leaves the box is not entered, so where one larger than every entered conductor lands on a block, that block's allowance is at the pigtail's size: add the difference. NEC 314.16(B)(6)

Where this number comes fromIntry Verified
Calculated from
NEC 314.16(B), volumes per Table 314.16(A). Computed from NEC Table 314.16(B)(1) per-conductor volumes and the 314.16(B)(1)-(6) counting rules, against the Table 314.16(A) box volume. See the full receipt ↓
Run with
  • Box4x2-1/8 square
  • Conductors3 #14 AWG
  • Device yokes1
  • Grounds (EGC)1
Checked
Every figure an Intry calculator computes comes from a locked source module, not hand-typed. 35,938 automated checks, one suite for the whole site rather than a per-tool count, re-derive the numbers before each deploy from the tables this site holds, read from the cited NEC section. This is our own deterministic gate, not a third-party audit.
Final say
Your AHJ and local amendments have final say. Confirm before rough-in.
What Intry Verified means

Intry Verified · NEC 2023 · Build 525536D · 2026-11-13

12 / 30.3 cu inPASS

Run this inside your AI assistant

Prefer to just ask? Add this to Claude.

Connect Intry to Claude once, then just say “use Intry to…” to run the box fill calculator from a plain-English question, on your phone, on the job. You get the number (computed live, not guessed), what it means, and the cited NEC section. Works on every Claude plan.

Use this in Claude

How to Use This Calculator

  1. Select a box type from the standard NEC 314.16(A) list, or toggle to “Enter custom volume” if your box has a manufacturer-stamped volume or you are using an extension ring. The dropdown shows each box type with its rated volume in cubic inches.
  2. Add your conductors by wire size and count. Count every conductor that enters the box: hot, neutral, travelers, and switch legs. If a wire passes through without termination, count it once; a loop or coil of unbroken conductor at least twice the free length 300.14 requires counts twice. Do not count pigtails that originate inside the box.
  3. Enter device yokes, one for each switch, receptacle, or GFCI mounted in the box. Set the largest conductor size connected to any device.
  4. Check internal clamps if the box has built-in cable clamps. All clamps share one volume allowance, at the largest conductor present in the box.
  5. Enter equipment grounding conductors. Count how many EGCs are present and select the largest. Up to four EGCs share a single volume allowance; each EGC beyond four adds a quarter allowance.
  6. Add terminal blocks if present (314.16(B)(6)). Each block counts individually.
  7. Read your results. The fill bar shows percentage used. Green means compliant. If you exceed 100%, the calculator suggests the smallest standard box that would work.

NEC 314.16 Box Fill Rules Explained

NEC 314.16 governs the maximum number of conductors and devices permitted in outlet boxes, device boxes, and junction boxes. The rule exists for three critical safety reasons: preventing overheating from too many current-carrying conductors in a confined space, ensuring there is enough room to make reliable electrical connections without damaging wire insulation, and reducing the risk of wire damage during installation when conductors are forced into an overfilled box. Every electrician, from apprentice through master, encounters box fill calculations on the job and on licensing exams.

The calculation is straightforward in concept: add up the volume allowance for every item in the box, then verify the total does not exceed the box's rated volume in cubic inches. The complexity comes from knowing which items count, how they count, and which share allowances. NEC 314.16(B) breaks this into six subsections, each with its own counting rule.

Volume Allowance Rules per NEC 314.16(B)

314.16(B)(1), Conductors. Each conductor that originates outside the box and terminates or is spliced inside counts as one conductor volume. A conductor that passes through without splice counts once (not twice for entering and exiting), and a loop or coil of unbroken conductor at least twice the free length 300.14 requires counts twice. Equipment bonding jumpers, pigtails originating inside the box, and conductors that do not leave the box are not counted here. They fall under other subsections or are exempt. The volume per conductor depends on its wire gauge: #14 gets 2.00 cu in, #12 gets 2.25 cu in, and so on per NEC Table 314.16(B)(1).

314.16(B)(2), Clamps. If the box contains one or more internal cable clamps, all clamps together get a single volume allowance equal to the volume of the largest conductor present in the box, whichever cable it is in. It does not matter whether the box has one clamp or four. The total is one volume. A cable connector whose clamp sits outside the box does not count.

314.16(B)(3), Support fittings. Luminaire studs and hickeys take one conductor volume for each type present, based on the largest conductor present: a stud alone is one, a stud and a hickey are two. The calculator asks for each.

314.16(B)(4), Device yokes. Each switch, receptacle, or device mounted on a yoke (strap) counts as two conductor volumes based on the largest conductor connected to that device. A single-gang receptacle is one yoke. A device wider than a single 2 in. device box counts two volumes for each gang it needs, so enter it as one yoke per gang. This is the rule that makes device boxes fill up fast. A single receptacle on #14 wire adds 4.00 cu in just for the yoke.

314.16(B)(5), Equipment grounding conductors. Up to four EGCs in the box share a single volume allowance based on the largest EGC present, and each EGC beyond four adds an additional quarter allowance. Four #14 grounds count the same as one #14 ground: 2.00 cu in total. Six #14 grounds count 2.00 + 2 × 0.50 = 3.00 cu in. If one of those grounds is #12, every allowance is figured at 2.25 cu in.

314.16(B)(6), Terminal blocks. Each terminal block assembly in the box takes one volume, based on the largest conductor terminated to that assembly. This calculator charges each block at the largest conductor you enter for the box; a pigtail larger than every entered conductor that lands on a block sets that block's allowance instead.

Why Box Fill Matters

An overfilled box creates three distinct hazards. First, heat buildup: current-carrying conductors generate heat, and a cramped box prevents adequate heat dissipation. The insulation temperature ratings in NEC 310.16 assume adequate spacing and airflow. Pack too many conductors into a small box and the insulation runs hotter than its rating, accelerating degradation and increasing fire risk.

Second, connection reliability. Wire nuts, push-in connectors, and terminal screws need room to be properly installed and inspected. In an overfilled box, splices get jammed against the box walls, wire nuts back off under spring pressure from packed wires, and connections loosen over time. Loose connections arc, and arcing causes fires. Giving connections adequate space reduces callbacks and improves long-term reliability.

Third, installation damage. When an electrician pushes a device into an overfilled box, the conductors behind it get bent, compressed, and scraped against sharp box edges and device mounting screws. Nicked insulation creates potential short circuits and ground faults that may not present immediately but can fail months or years later. Proper box fill ensures conductors can be folded into the box without excessive force.

Understanding Box Fill Calculations Step by Step

The counting rules trip up apprentices and journeymen alike because different items in the box follow different rules. Here is the mental model: conductors count individually, devices count double, clamps count once regardless of quantity, and grounds count once for the first four plus a quarter each after that.

Start by counting conductors. Walk each cable into the box and count every individual conductor that crosses the box boundary. A 14/2 NM cable brings two insulated conductors (#14 hot and #14 neutral) plus one bare ground. The hot and neutral each count as one conductor for 314.16(B)(1). The bare ground goes into the EGC pool for 314.16(B)(5). A 14/3 NM cable adds three conductors plus one ground.

Next, count devices. Each receptacle, switch, dimmer, or GFCI mounted in the box is one device yoke. A duplex receptacle is one yoke. A two-gang box with two switches has two yokes. Each yoke gets two volume allowances at the size of the largest conductor connected to that device.

Then handle the shared items. If the box has internal clamps, add one volume at the largest conductor present in the box. Gather all equipment grounding conductors and add one volume at the largest EGC size, plus a quarter volume for each EGC beyond four. If there are terminal blocks, add one volume per block at the largest conductor terminated on it.

Finally, sum everything and compare to the box's rated volume. If the total exceeds the rated volume, you need a larger box or fewer items in this one. Never ignore the calculation and force everything in.


NEC Table 314.16(B)(1) Volume Allowances

Each conductor size has a specific volume allowance in cubic inches. This table is the foundation of every box fill calculation.

NEC Table 314.16(B)(1): Volume allowance per conductor by wire size

Swipe the table sideways to see the rest of its columns. →

Wire Size (AWG)Volume (cu in)
18 AWG1.50
16 AWG1.75
14 AWG2.00
12 AWG2.25
10 AWG2.50
8 AWG3.00
6 AWG5.00

NEC 314.16(A) Standard Metal Box Volumes

These are the NEC-listed standard box types with their rated volumes. If your box has a manufacturer-stamped volume, use that value instead, as it may differ slightly from these minimums.

NEC 314.16(A): Standard metal box volumes in cubic inches

Swipe the table sideways to see the rest of its columns. →

Box TypeVolume (cu in)
4 x 1-1/4 round/octagonal12.5
4 x 1-1/2 round/octagonal15.5
4 x 2-1/8 round/octagonal21.5
4 x 1-1/4 square18.0
4 x 1-1/2 square21.0
4 x 2-1/8 square30.3
4-11/16 x 1-1/4 square25.5
4-11/16 x 1-1/2 square29.5
4-11/16 x 2-1/8 square42.0
3 x 2 x 1-1/2 device7.5
3 x 2 x 2 device10.0
3 x 2 x 2-1/4 device10.5
3 x 2 x 2-1/2 device12.5
3 x 2 x 2-3/4 device14.0
3 x 2 x 3-1/2 device18.0
4 x 2-1/8 x 1-1/210.3
4 x 2-1/8 x 1-7/813.0
4 x 2-1/8 x 2-1/814.5
Masonry 3-3/4 x 2 x 2-1/214.0
Masonry 3-3/4 x 2 x 3-1/221.0
FS single gang13.5
FD single gang18.0
FS double gang18.0
FD double gang24.0

Worked Examples

Example 1: Single-Gang Device Box with 4 #14 Conductors

A single-gang box with one 14/2 NM cable (feed) and one 14/2 NM cable (switch leg) feeding a single-pole switch. The box has internal clamps. Every insulated conductor entering the box is counted under 314.16(B)(1), so the two cables bring four #14 conductors, not three.

  • Conductors: 2 × 14/2 = 4 #14 insulated conductors × 2.00 = 8.00 cu in
  • Device yokes: 1 switch × (2 × 2.00) = 4.00 cu in
  • Internal clamps: 1 × 2.00 = 2.00 cu in
  • Equipment grounding: 1 × 2.00 = 2.00 cu in (2 grounds, but only 1 allowance)
  • Total: 16.00 cu in

A 3x2x2-3/4 device box provides only 14.0 cu in, so it fails. You need at least 16.0 cu in, so the next standard box up is a 3x2x3-1/2 device box (18.0 cu in), which also gives working room. This is why you count every conductor, device, clamp, and ground, not just the wires.

Example 2: 4-11/16 Square Box with Mixed Wire Sizes

A 4-11/16 x 2-1/8 square junction box with two 12/2 cables and one 14/3 cable, two device yokes (receptacles), internal clamps, and equipment grounding conductors.

  • #12 conductors: 4 (from two 12/2 cables) × 2.25 = 9.00 cu in
  • #14 conductors: 3 (from one 14/3 cable) × 2.00 = 6.00 cu in
  • Device yokes: 2 × (2 × 2.25) = 9.00 cu in (largest connected is #12)
  • Internal clamps: 1 × 2.25 = 2.25 cu in (largest conductor is #12)
  • Equipment grounding: 1 × 2.25 = 2.25 cu in (3 EGCs, largest is #12)
  • Total: 28.50 cu in

A 4-11/16 x 2-1/8 square box provides 42.0 cu in, compliant with 13.5 cu in to spare. A 4-11/16 x 1-1/4 at 25.5 cu in would fail. The mixed wire sizes require using the larger conductor volume for device yokes, clamps, and grounding calculations.

Example 3: Finding the Right Replacement for an Overfilled Box

A 3x2x2 device box (10.0 cu in) with one 12/2 cable and one 12/3 cable feeding a three-way switch, with internal clamps.

  • #12 conductors: 5 (2 from 12/2 + 3 from 12/3) × 2.25 = 11.25 cu in
  • Device yokes: 1 × (2 × 2.25) = 4.50 cu in
  • Internal clamps: 1 × 2.25 = 2.25 cu in
  • Equipment grounding: 1 × 2.25 = 2.25 cu in
  • Total: 20.25 cu in

The 3x2x2 box at 10.0 cu in is badly overfilled at 202% capacity. The minimum compliant standard box is a 4x1-1/2 square at 21.0 cu in. A 4x2-1/8 square at 30.3 cu in would provide comfortable working room. This is a common scenario in older homes where boxes were originally sized for fewer circuits and later had additional cables pulled in during renovations.


Frequently Asked Questions

Is the Intry Box Fill Calculator accurate and NEC compliant?

Every figure an Intry calculator computes comes from a locked source module, not hand-typed. 35,938 automated checks, one suite for the whole site rather than a per-tool count, re-derive the numbers before each deploy from the tables this site holds, read from the cited NEC section. This is our own deterministic gate, not a third-party audit. The per-tool receipt is public at https://www.intrysys.com/verified.

How do I calculate box fill in cubic inches per NEC?

Add up every volume allowance from NEC Table 314.16(B)(1), then compare the total to the box volume from Table 314.16(A). Each conductor counts by its size: #14 = 2.00 cu in, #12 = 2.25, #10 = 2.50, #8 = 3.00, #6 = 5.00. Each device yoke (receptacle or switch) counts as two allowances of the largest conductor connected to it. All internal cable clamps together count as one allowance of the largest conductor in the box. Up to four equipment grounds count as one allowance of the largest ground, plus a quarter allowance for each ground beyond four. Sum every allowance in cubic inches, and the box volume must be equal or greater.

How many conductors are allowed in a 4 inch square junction box?

It depends on the box depth (NEC Table 314.16(A)). A 4 × 4 × 1-1/2 inch square box is 21.0 cu in, which holds 10 #14, 9 #12, or 8 #10 conductors when nothing else is in the box. A 4 × 4 × 2-1/8 inch box is 30.3 cu in: 15 #14, 13 #12, or 12 #10. Subtract two conductor allowances per device, one for clamps, and one for up to four grounds (a quarter more for each ground beyond four) before counting the remaining conductors.

What size box do I need for 4 receptacle wires?

You need at least an 18.0 cubic inch box, such as a 3x2x3-1/2 device box or a 4x1-1/4 square box. Four #14 conductors are 8.00 cu in, plus 4.00 for one device yoke, 2.00 for clamps, and 2.00 for a ground, totaling 16.00 cu in, and the next standard box up is 18.0 cu in. A 3x2x2-3/4 device box (14.0 cu in) fails. Always calculate the full fill including devices, clamps, and grounds, not just the wires.

Do ground wires count in box fill?

Yes, but not individually. Per NEC 314.16(B)(5), up to four equipment grounding conductors (EGCs) count as a single volume allowance based on the largest EGC present, and each EGC beyond four adds a quarter allowance. One to four #14 grounds consume 2.00 cu in together, but six #14 EGCs consume 2.00 + 2 x 0.50 = 3.00 cu in.

How do I count wires that pass through a box?

A conductor that passes through a box without splice, tap, or termination counts once for box fill purposes per NEC 314.16(B)(1). It enters and exits, but you only count it as one conductor. However, if that same conductor is spliced or terminated inside the box, it still counts the same way: once. The key distinction is that a pigtail (short wire connected from a device to a splice) originating inside the box does not count, because it does not enter the box from outside. One exception runs the other way: a loop or coil of unbroken conductor at least twice the free length 300.14 requires counts twice, so enter it as two.

How do terminal blocks count in box fill?

NEC 314.16(B)(6) in the 2023 NEC gives each terminal block assembly in a box one volume allowance, based on the largest conductor terminated to that assembly. This calculator charges each block at the largest conductor you enter for the box, which covers every conductor that enters it. A pigtail never leaves the box and is not entered, so where a pigtail larger than every entered conductor lands on a block, that block's allowance is at the pigtail's size: add the difference.

Can I use an extension ring to add volume?

Yes, when the piece is marked with its volume or is made from boxes whose dimensions Table 314.16(A) lists (314.16(A)). A marked extension adds its marked volume to the base box volume. Read the marking on the ring in your hand rather than working from a typical figure: capacity varies with size and depth, and a published example is easy to misapply to a different part. Note that not every accessory of this shape counts. An unmarked plaster ring (mud ring) or levelling-type box extender adds nothing unless it is made from boxes whose dimensions Table 314.16(A) lists. When using this calculator with a marked extension, select 'Enter custom volume' and enter the base box volume plus the marked ring volume.


How Many Wires in a Specific Box

Dedicated fill answers for the boxes you actually install, with the bare maximum and the realistic count once a device, clamps, and a ground are in the box.


Related Calculators

Box is legal, but what about the raceway feeding it?

Box fill and conduit fill get cited together on inspections. Run the conduit fill calculator against NEC Chapter 9 for the same conductors, or check the rest of the electrical tools.