NEC Chapter 9
Conduit Fill Chart (THHN in EMT)
Maximum number of THHN conductors per EMT trade size at the NEC fill limit for that count (40% for three or more). Read down your wire size, across to your conduit size.
THHN / THWN-2 Conductors in EMT by NEC Fill Limit
Maximum number of THHN or THWN-2 conductors per EMT trade size, each at Chapter 9 Table 1's limit for that count: 53% for one conductor, 31% for two, 40% for three or more. Source: NEC (NFPA 70-2023) Chapter 9, Tables 1, 4, and 5, and Note 7.
Swipe the table sideways to see the rest of its columns. →
| Wire (AWG/kcmil) | 1/2" | 3/4" | 1" | 1-1/4" | 1-1/2" | 2" | 2-1/2" | 3" | 3-1/2" | 4" |
|---|---|---|---|---|---|---|---|---|---|---|
| 14 | 12 | 22 | 35 | 61 | 84 | 138 | 241 | 364 | 476 | 608 |
| 12 | 9 | 16 | 26 | 45 | 61 | 101 | 176 | 266 | 347 | 443 |
| 10 | 5 | 10 | 16 | 28 | 38 | 63 | 111 | 167 | 219 | 279 |
| 8 | 3 | 6 | 9 | 16 | 22 | 36 | 64 | 96 | 126 | 161 |
| 6 | 2 | 4 | 7 | 12 | 16 | 26 | 46 | 69 | 91 | 116 |
| 4 | 1 | 2 | 4 | 7 | 10 | 16 | 28 | 43 | 56 | 71 |
| 3 | 1 | 1 | 3 | 6 | 8 | 13 | 24 | 36 | 47 | 60 |
| 2 | 1 | 1 | 3 | 5 | 7 | 11 | 20 | 30 | 40 | 51 |
| 1 | 1 | 1 | 1 | 4 | 5 | 8 | 15 | 22 | 29 | 37 |
| 1/0 | 1 | 1 | 1 | 3 | 4 | 7 | 12 | 19 | 25 | 32 |
| 2/0 | 0 | 1 | 1 | 2 | 3 | 6 | 10 | 16 | 20 | 26 |
| 3/0 | 0 | 1 | 1 | 1 | 3 | 5 | 8 | 13 | 17 | 22 |
| 4/0 | 0 | 1 | 1 | 1 | 2 | 4 | 7 | 11 | 14 | 18 |
| 250 | 0 | 0 | 1 | 1 | 1 | 3 | 6 | 9 | 11 | 15 |
| 350 | 0 | 0 | 1 | 1 | 1 | 2 | 4 | 6 | 9 | 11 |
| 500 | 0 | 0 | 0 | 1 | 1 | 1 | 3 | 5 | 6 | 8 |
THHN and THWN-2 share the same area, so counts are identical. A cell where only one conductor fits uses the 53% limit and one where two fit uses 31%; a nipple 24 inches or shorter is held to 60% (NEC Chapter 9, Table 1), which the conduit fill calculator applies. For IMC, RMC, or PVC, or mixed wire sizes, use the conduit fill calculator.
How the Count Is Calculated
Conduit fill is an area comparison. Max conductors = (conduit internal area × fill limit) / conductor area, rounded down. The conduit internal area comes from NEC Chapter 9, Table 4, the fill limit is 40% for three or more conductors from Table 1, and the conductor area comes from Table 5. For 3/4 inch EMT that is 0.533 sq in × 0.40 = 0.213 sq in of usable space, and each #12 THHN is 0.0133 sq in, so 0.213 / 0.0133 = 16.03, which gives 16 conductors. One rounding wrinkle from NEC Chapter 9, Note 7: you round up only when the decimal is 0.8 or larger, otherwise you round down. That is why #12 THHN in 1 inch EMT works out to 26 (25.98 rounds up) but in 3/4 inch EMT it is 16 (16.03 rounds down).
Every conductor in the raceway counts, including the equipment grounding conductor. The fill limit is about heat dissipation and pulling tension, not just physical space, which is why the limit is 40% rather than 100%.
Frequently Asked Questions
How many 12 AWG THHN wires fit in 3/4 inch EMT?
16 #12 THHN conductors fit in 3/4 inch EMT at the NEC 40% fill limit. The 3/4 inch EMT internal area is 0.533 sq in, so 0.533 x 0.40 = 0.213 sq in allowable, divided by 0.0133 sq in per #12 THHN = 16.
How many 12 AWG THHN wires fit in 1/2 inch EMT?
9 #12 THHN conductors fit in 1/2 inch EMT at 40% fill. The 1/2 inch EMT area is 0.304 sq in, so 0.304 x 0.40 = 0.122 sq in, divided by 0.0133 = 9.
How many 10 AWG THHN wires fit in 1/2 inch EMT?
5 #10 THHN conductors fit in 1/2 inch EMT at 40% fill (0.304 x 0.40 = 0.122 sq in, divided by 0.0211 sq in per #10 THHN = 5).
What is the fill limit for conduit?
The NEC Chapter 9, Table 1 fill limit is 40% for three or more conductors, 31% for exactly two, 53% for a single conductor, and 60% for a nipple 24 inches or shorter. This chart applies each count's own limit: 40% where three or more fit, and 31% or 53% where only two or one do.
Do ground wires count in conduit fill?
Yes. Every conductor in the raceway counts toward conduit fill, including the equipment grounding conductor, based on its own cross-sectional area from NEC Chapter 9, Table 5. Only bare grounds use the bare-conductor area; insulated grounds use the insulated area.
Is this chart the same for THWN-2 wire?
Yes. THHN and THWN-2 have identical cross-sectional areas in NEC Chapter 9, Table 5, so the conductor counts are the same. XHHW, RHH, RHW, TW, and THW are larger, so fewer fit. Use the conduit fill calculator for those insulations.
Related Calculators & Charts
Conduit Fill Calculator
Any mix of wire sizes and insulations in EMT, IMC, RMC, PVC, or ENT, with exact fill percentage and pass/fail.
Wire Ampacity Chart (310.16)
Once the wires fit, confirm the conductors already in the raceway can carry the load.
Box Fill Volume Chart (314.16)
The junction-box version: cubic inches per conductor with device, clamp, and ground rules.
Different conduit or a mix of wires?
This chart is THHN in EMT. For IMC, RMC, PVC, ENT, a short nipple, or any mix of sizes, the conduit fill calculator runs the exact NEC Chapter 9 math.
Keep going