HVAC Calculator

BTU / HVAC Load Calculator

The heating and cooling loads in BTU and the tonnage to order, computed by ACCA Manual J at your ZIP code's ASHRAE weather station, so the unit fits the house instead of short-cycling it.

Field brief
Zone 3B, 2,000 sqft DOE's 2021 reference house at EL PASO, Texas: 22,011 BTU/hr heating and 23,195 BTU/hr cooling, by our Manual J engine. 2 ton
Your ZIP, your station the load is worked at the ASHRAE design temperatures of the station nearest your ZIP code, from the answers you give, with the answers this page does not ask listed beside it. ACCA Manual J
Size to the window the nominal size is the rung closest to the load inside ACCA Manual S's 90 to 115 percent window, not the next one up out of habit. Oversizing short-cycles and leaves the humidity behind. 90–115%

Intry VerifiedA worked default reading, traceable end to end: what it was calculated from, what it was run with, how it was checked, and who has final say.

Enter a ZIP code for the Manual J load
Where this number comes fromIntry Verified
Calculated from
ACCA Manual J (abridged, on the server at your ZIP code's ASHRAE station) / Manual S fit. Computed by ACCA Manual J's abridged method at the ASHRAE weather station nearest your ZIP code, with the recommended tonnage judged against the 115 percent ACCA Manual S ceiling for SINGLE-SPEED cooling equipment. Manual S prints wider ceilings for multi-speed and variable-speed equipment. See the full receipt ↓
Run with
  • ZIP codenot entered
  • Floor area1,500 sqft, one storey
  • Weather stationnone yet
  • InsulationR-13 walls, R-30 attic
  • WindowsDouble pane
  • Air tightnessAverage
  • DuctsIn a vented attic
Checked
Every figure an Intry calculator computes comes from a locked source module, not hand-typed. 35,938 automated checks, one suite for the whole site rather than a per-tool count, re-derive the numbers before each deploy from the tables this site holds, read from the ACCA Manual J basis it came from. This is our own deterministic gate, not a third-party audit.
Final say
A full Manual J on the actual house has final say.
What Intry Verified means

Intry Verified · Build 525536D · 2026-11-13


Manual J Loads by Climate Zone

Our ACCA Manual J engine on DOE's 2021 reference house for each IECC zone (two storeys, built to that zone's 2021 energy code, low-e windows priced in Manual J's triple or double low-e column, ducts in a vented attic, on a slab), at the ASHRAE station nearest the model's own weather site, computed when this page is built. Each size is chosen by the same ACCA Manual S rule the calculator above uses. Your house at your ZIP code is the calculator's answer, and it is the one to use.

Swipe the table sideways to see the rest of its columns. →

Zone, ASHRAE stationHeating, 1,500 sqftHeating, 2,500 sqftCooling, 1,500 sqftCooling, 2,500 sqft
1AMIAMI NHC, Florida9,326 BTU/hr12,714 BTU/hr21,971 BTU/hr2 ton, 2 ton fits29,735 BTU/hr2.5 ton, 2.5 ton fits
2AMACDILL AFB, Florida14,285 BTU/hr19,410 BTU/hr23,456 BTU/hr2 ton, 2 ton fits31,674 BTU/hr2.5 ton, 2.5 ton fits
2BDAVIS-MONTHAN AFB, Arizona18,306 BTU/hr24,909 BTU/hrwithheldwithheld
3AATLANTA HARTSFIELD-JACKSON, Georgia19,639 BTU/hr27,296 BTU/hr18,955 BTU/hr1.5 ton, 1.5 ton fits26,022 BTU/hr2 ton, 2 ton fits
3BEL PASO, Texas18,299 BTU/hr25,424 BTU/hr19,459 BTU/hr1.5 ton, 1.5 ton fits26,922 BTU/hr2.5 ton, 2.5 ton fits
3CBROWN FIELD, California12,508 BTU/hr17,369 BTU/hr15,196 BTU/hr1.25 ton, 1.25 ton fits20,745 BTU/hr1.5 ton, Runs small at 1.5 ton
4ANEW YORK KENNEDY, New York17,080 BTU/hr24,317 BTU/hr16,650 BTU/hr1.5 ton, 1.5 ton fits22,782 BTU/hr2 ton, 2 ton fits
4BALBUQUERQUE INTL, New Mexico15,000 BTU/hr21,420 BTU/hr16,511 BTU/hr1.5 ton, 1.5 ton fits22,782 BTU/hr2 ton, 2 ton fits
4CSEATTLE TACOMA, Washington12,811 BTU/hr18,173 BTU/hr13,525 BTU/hr1.25 ton, 1.25 ton fits18,404 BTU/hr1.5 ton, 1.5 ton fits
5ABUFFALO NIAGARA, New York20,684 BTU/hr29,474 BTU/hr14,503 BTU/hr1.25 ton, 1.25 ton fits19,746 BTU/hr1.5 ton, 1.5 ton fits
5BBUCKLEY AFB, Colorado19,699 BTU/hr28,097 BTU/hr14,483 BTU/hr1.25 ton, 1.25 ton fits19,963 BTU/hr1.5 ton, 1.5 ton fits
5CBREMERTON, Washington13,925 BTU/hr19,785 BTU/hr13,501 BTU/hr1.25 ton, 1.25 ton fits18,370 BTU/hr1.5 ton, 1.5 ton fits
6AROCHESTER INTL, Minnesota25,824 BTU/hr37,095 BTU/hr14,927 BTU/hr1.25 ton, 1.25 ton fits20,345 BTU/hr1.5 ton, Runs small at 1.5 ton
6BGREAT FALLS, Montana25,782 BTU/hr37,075 BTU/hr14,529 BTU/hr1.25 ton, 1.25 ton fits20,040 BTU/hr1.5 ton, Runs small at 1.5 ton
7DULUTH INTL, Minnesota27,156 BTU/hr38,997 BTU/hr13,658 BTU/hr1.25 ton, 1.25 ton fits18,535 BTU/hr1.5 ton, 1.5 ton fits
8FAIRBANKS, Alaska35,817 BTU/hr51,395 BTU/hr12,179 BTU/hr1 ton, 1 ton fits16,481 BTU/hr1.25 ton, 1.25 ton fits

Cooling is the total, sensible plus latent. "Withheld" means Manual J's printed tables do not reach that station's cooling conditions at the daily range class its DOE design day reads, so the engine gives none rather than a guess. A ton is 12,000 BTU/hr by definition. The size shown is the nominal unit closest to the load whose capacity still falls between 90% and 115% of it, the acceptable range ACCA Manual S sets for single-speed cooling equipment (Table N2-1, printed page N12); where no nominal size falls inside that range, the nearest is shown with its verdict. Where a run's total latent load is negative (a dry design condition), Manual S sizes on the sensible total, as the calculator does. Manual S bounds the capacity, not the rounding: it says in the same section that equipment selection shall not be based on standard sizes, so treat the tonnage as a screening figure, and a real selection is made against the manufacturer’s performance data.


What Is a BTU?

A BTU (British Thermal Unit) is the amount of energy required to raise the temperature of one pound of water by one degree Fahrenheit. In HVAC, BTU measures the rate of heat transfer: how much heat an air conditioning system can remove from a space per hour (BTU/h). When someone says a system is "36,000 BTU," they mean it can remove 36,000 BTUs of heat energy from the indoor air every hour.

American HVAC equipment is rated in BTU/h. One ton of cooling is 12,000 BTU/h, 3,517 W (NIST's guide to the SI, SP 811, Appendix B.9).

Understanding BTU matters because every component in your HVAC system (the compressor, evaporator coil, condenser, and ductwork) must be matched to the building's load. An undersized system runs constantly without reaching setpoint. An oversized system short-cycles, wasting energy and failing to dehumidify. The goal is to calculate the exact thermal load your building produces and match equipment to that number.

Cooling vs Heating Load

Cooling load and heating load measure different things and need not be equal. Cooling load is the amount of heat that must be removed from a space to maintain the desired indoor temperature. It includes heat from the sun (solar gain through windows and roof), heat conducted through walls and ceiling, heat generated by people and appliances (internal gains), and moisture that must be condensed out of the air (latent load).

Heating load is simpler in concept: it is the amount of heat lost through the building envelope (walls, windows, roof, foundation) plus infiltration (cold air leaking in through gaps). There is no solar gain component and no latent load to worry about. The driving factor is the temperature difference between inside and outside. The colder it gets outside, the more heat escapes.

Where the winter design temperature difference is greater than the summer one, the heating load is larger than the cooling load. At Chicago O'Hare, ASHRAE's 99% heating design temperature is 3.3 °F and its 1% cooling design temperature 88.5 °F (Handbook of Fundamentals 2021, Chapter 14). Against Manual J's indoor design of 70 °F in winter and 75 °F in summer, that is a 66.7 degree difference in winter and 13.5 in summer, before the summer's solar and latent loads.

For heat pump systems, this distinction is critical. A heat pump sized for cooling may be undersized for heating in cold climates, requiring a backup heat source (electric resistance strips or a gas furnace). Modern cold-climate heat pumps have improved dramatically, but the fundamental physics remains: if your heating load is 60,000 BTU and your heat pump delivers 40,000 BTU at design temperature, you need supplemental heat.

The Danger of Oversizing

One HVAC sizing mistake is going too big, on the assumption that bigger is better. Some contractors upsize as insurance against callbacks. Manual S bounds both instincts: it sets the capacity window a unit must fall inside.

Short cycling. An oversized AC reaches the thermostat setpoint too quickly, so the compressor shuts off, the house warms up, and it kicks back on. Rapid on-off cycling is hard on a compressor: every start draws far more current than steady running, which stresses contacts and electrical components. We do not publish a cycle-length target or a startup-current multiple, because we have no source for either that we have checked ourselves.

Humidity problems. Air conditioning removes moisture by passing air over a cold evaporator coil. Moisture condenses on the coil and drains away. This process takes time. The coil needs to get cold and stay cold for the full cycle. When an oversized system short-cycles, the coil never reaches peak dehumidification. The house temperature drops, but the humidity stays high. Occupants feel cold and clammy, so they lower the setpoint, which makes the system run even shorter cycles. In a humid climate that leaves the indoor air damper than a unit sized to the load would.

Wasted energy, and the measured reason. One Department of Energy national laboratory study, NREL/TP-5500-60801 (November 2014), simulated a 1960s Houston house and found the oversizing energy penalty was -2% to 4% when the equipment drew no off-cycle standby power, and 10% to 21% when it drew standby power proportional to capacity. Its conclusion is that the penalty "is not due to unit cycling efficiency but rather to off-cycle parasitic power consumption": extra cycling by itself did not move the energy number much. Read it with its scope attached, because the scope is in the half of the title people drop: it is a simulation study of retrofit sequence impacts, where the oversized case is a unit replaced at its old capacity after the house was tightened, not a contractor upsizing at install. Other work disagrees and reports a larger cycling penalty, so treat the cause as contested. What is not contested is the comfort and humidity case made above, which is the more reliable reason not to oversize. One simulated house is not a national average, and we have not measured any of this ourselves.

Higher upfront cost. A larger system costs more in equipment alone, and the knock-on costs follow it: the ductwork may need to be larger and the electrical circuit may need to be upsized. You pay more for a system that performs worse. We publish no dollar figure here because we do not track equipment pricing.

The correct approach: calculate the load accurately, then select equipment that matches. If the calculation shows 30,000 BTU, the size inside the Manual S window is 2.5 ton, not a larger one "just in case." Variable-speed equipment offers some forgiveness because it can ramp down, but even variable-speed systems have a minimum output. Proper sizing remains essential.

Climate Zones Explained

The International Energy Conservation Code (IECC) divides the United States into climate zones based on temperature and moisture conditions, and the zones set insulation and air leakage requirements. This calculator does not price a zone: design load is an output of a Manual J calculation at a weather station, and no code or standard tabulates it per climate zone. The zone sets only the house the "built to the 2021 energy code" answers describe. The table above prints each zone's reference house as our engine computes it.

Zone 1: Very Hot-Humid

Southern tip of Florida, Hawaii, US territories. Cooling-dominated year-round with minimal heating needs. High latent (moisture) loads drive equipment selection. Dehumidification capacity is as important as sensible cooling capacity.

Zone 2: Hot-Humid

Gulf Coast, southern Texas, southern Arizona, much of Florida. Long cooling seasons with brief, mild winters. Humidity management remains critical. Ducts in a hot attic add to the cooling load, and this calculator prices them through Manual J's Table 7; a measured figure for your house comes from a duct-leakage test.

Zone 3: Warm-Humid / Warm-Dry

Mid-South, inland California, Kingman in Arizona, Las Cruces in New Mexico. Mixed needs with meaningful cooling and heating seasons. The humid vs dry subdivision affects latent load calculations. Humid areas need more dehumidification capacity.

Zone 4: Mixed-Humid / Mixed-Dry

Mid-Atlantic, lower Midwest, Albuquerque, Pacific Northwest coast. Balanced heating and cooling loads. A heat pump sized to the heating load can carry it here; check its capacity at your design temperature.

Zone 5: Cool-Humid

Upper Midwest, Great Lakes, New England, Pacific Northwest inland. Heating-dominant with moderate cooling needs. Insulation quality has a larger impact on heating load than cooling load. A cold-climate heat pump's capacity at your design temperature is in its maker's published table; compare it with the heating load before planning backup heat.

Zone 6: Cold

Northern tier states: Montana, Minnesota, northern New England, upstate New York. Long heating seasons. The heating load can be several times the cooling load, so size the heating side on its own.

Zone 7: Very Cold

Northern Minnesota, northern Maine, Anchorage. Extreme heating-dominant with minimal cooling needs. Some homes in Zone 7 do not have air conditioning at all, relying on natural ventilation for the brief summer. Where AC is installed, it is a relatively small system compared to the heating equipment.

Zone 8: Subarctic

Parts of Alaska, Fairbanks among them: DOE's climate zone guide places the only subarctic regions in the United States in Alaska. The table above prints the zone's reference house as our engine computes it.

How Insulation Affects Load

Insulation moves the load, and the engine's run below measures by how much on one house. The R-value (thermal resistance) of your walls, ceiling, and floor determines how fast heat moves through the building envelope. Higher R-values mean slower heat transfer and lower loads.

Our Manual J engine on the zone 3B reference house at 2,000 sqft, with each insulation answer this calculator offers and everything else held (computed when this page is built):

  • Built to the 2021 energy code for its zone: 22,011 BTU/hr heating, 23,195 BTU/hr cooling
  • R-13 walls, R-30 attic: 24,329 BTU/hr heating, 25,989 BTU/hr cooling
  • R-11 walls, R-19 attic: 25,574 BTU/hr heating, 28,083 BTU/hr cooling
  • No wall or attic insulation: 53,194 BTU/hr heating, 64,222 BTU/hr cooling

The difference translates directly into equipment size and into every energy bill for the life of the system.

The "built to the 2021 energy code" answer uses DOE/PNNL's 2021 reference house envelope for your zone; the BTU per square foot chart prints that envelope zone by zone, from the model files. A house built before those codes can hold less insulation and computes a higher load; choose the insulation answer that matches what is in the walls and the attic.

Air sealing matters as much as insulation. A home with R-38 attic insulation but unsealed can penetrations, recessed lights, and gaps around plumbing can lose as much heat through air leakage as through conduction. A blower door test quantifies infiltration in air changes per hour (ACH50). Older leaky homes test far higher than tight new construction, and the IECC sets a maximum by climate zone that a code-compliant new build has to meet. We do not publish the numbers here yet, because we have not read and re-derived that table ourselves. Each reduction in ACH directly reduces both heating and cooling loads.

When You Need a Full Manual J

This calculator provides a planning-level estimate. A full Manual J calculation is required or strongly recommended in several scenarios.

Permit requirements. A jurisdiction can require a Manual J calculation as part of the permit application for new HVAC installations, replacements, and major renovations. Building inspectors verify that equipment sizing matches the load calculation. An online calculator will not satisfy this requirement. You need a report generated by ACCA-approved software (Wrightsoft, HVAC-Calc, CoolCalc, or similar) signed by a licensed contractor.

Complex homes. Homes with unusual geometry, multiple stories with significantly different exposures, large window walls, cathedral ceilings, additions, or mixed construction types need room-by-room analysis that simplified calculators cannot provide. A full Manual J accounts for each room's unique characteristics and ensures ductwork distributes capacity where it is actually needed.

Equipment warranty. Some manufacturers require a Manual J calculation to validate warranty claims. If an improperly sized system fails prematurely, the manufacturer may deny the warranty claim if no load calculation was performed.

High-performance homes. Passive houses, net-zero homes, and deeply retrofitted buildings can have loads so low that rules of thumb oversize equipment. A detailed Manual J captures that.

Manual J vs Manual S

Manual J and Manual S are two separate ACCA standards that work together. Manual J calculates the load: how many BTU your building needs. Manual S selects the equipment: which specific make and model to install. They are sequential: you cannot do Manual S without completing Manual J first.

Manual J produces a load number (e.g., 36,000 BTU sensible cooling, 9,000 BTU latent cooling, 45,000 BTU total cooling). Manual S takes that number and matches it to manufacturer performance data at your specific design conditions. This matters because equipment capacity varies with outdoor temperature and indoor conditions. A unit delivers more than its nominal rating on a cooler day and less on a hotter one, and the maker's expanded performance table prints by how much at each outdoor temperature.

Manual S requires that a single-speed unit's total cooling capacity at design conditions falls between 90% and 115% of the Manual J total cooling load. Multi-speed equipment runs to 120% and variable-speed to 130%, and in a cold winter with no latent load a heat pump is capped by the Manual J load plus 15,000 BTU/hr rather than by a ratio at all. Latent capacity must be at least 100% of the latent load. This prevents both undersizing (comfort complaints on the hottest and coldest days) and oversizing (efficiency and humidity problems year-round).

A shortcut that causes problems: a contractor calculates a 36,000 BTU load and installs a "3-ton" system without checking Manual S. That 3-ton system might actually deliver 40,000 BTU at their design conditions, which is 11% over and within the 115% limit. Or it might deliver 44,000 BTU, which is 22% over, outside the limit, and a cause of short-cycling and humidity issues. Manual S closes this gap by verifying performance at your actual conditions.


Worked Examples

Zone 1A: 2,500 sqft reference house at MIAMI NHC, Florida

DOE's 2021 two-storey reference house built to zone 1A's 2021 energy code, at the ASHRAE station nearest the model's weather site. Our Manual J engine computes 12,714 BTU/hr of heating and 29,735 BTU/hr of total cooling. ACCA Manual S's selection gives 2.5 ton: 30,000 BTU/hr capacity is 100.9% of the calculated load, inside the 90-115% Manual S window for single-speed equipment (26,762-34,195 BTU/hr). Two-speed and variable-speed equipment are allowed more. Planning estimate, confirm with a Manual J before ordering.

Zone 3B: 2,500 sqft reference house at EL PASO, Texas

DOE's 2021 two-storey reference house built to zone 3B's 2021 energy code, at the ASHRAE station nearest the model's weather site. Our Manual J engine computes 25,424 BTU/hr of heating and 26,922 BTU/hr of total cooling. ACCA Manual S's selection gives 2.5 ton: 30,000 BTU/hr capacity is 111.4% of the calculated load, inside the 90-115% Manual S window for single-speed equipment (24,230-30,960 BTU/hr). Two-speed and variable-speed equipment are allowed more. Planning estimate, confirm with a Manual J before ordering.

Zone 8: 2,500 sqft reference house at FAIRBANKS, Alaska

DOE's 2021 two-storey reference house built to zone 8's 2021 energy code, at the ASHRAE station nearest the model's weather site. Our Manual J engine computes 51,395 BTU/hr of heating and 16,481 BTU/hr of total cooling. ACCA Manual S's selection gives 1.25 ton: 15,000 BTU/hr capacity is 91% of the calculated load, inside the 90-115% Manual S window for single-speed equipment (14,833-18,953 BTU/hr). Two-speed and variable-speed equipment are allowed more. Planning estimate, confirm with a Manual J before ordering.


Frequently Asked Questions

How many BTU do I need per square foot?

No code or standard prints one figure per square foot; the load is an output of Manual J for one house at one place. Our Manual J engine, run on DOE's 2021 reference house (1,500 sq ft, two storeys, built to the 2021 energy code) at each IECC zone's ASHRAE station, computes 8.1 to 15.6 BTU per square foot of cooling in the 15 of 16 zone runs where Manual J's printed tables reach the station, and 6.2 to 23.9 of heating. An older or leakier house computes higher. Enter your ZIP code and your house above for its own load.

What is the difference between BTU and tons?

One ton of cooling equals 12,000 BTU per hour. The term comes from the amount of heat needed to melt one ton of ice in 24 hours. To convert BTU to tons, divide by 12,000. A 36,000 BTU system is a 3-ton unit.

Why is oversizing an AC bad?

An oversized AC cools the air too quickly without running long enough to remove humidity. This causes short cycling (frequent on/off), which increases wear on the compressor and leaves your home feeling cold and clammy. Equipment sized to the load runs longer on each cycle, which gives the coil time to remove moisture. On energy specifically the evidence is mixed: a DOE national laboratory simulation (NREL/TP-5500-60801) found oversizing added little energy through cycling itself and mattered mainly where the equipment draws standby power between cycles, while older field work reports a larger cycling penalty. Comfort and humidity are the reliable reasons to size correctly.

How do I know if my AC is too big for my house?

Two signs point to an oversized system: short cycling and poor humidity control. If the AC runs for only a few minutes, shuts off, and restarts again soon after, and the house feels cold but damp or clammy, those are the signs of a unit larger than the load. Compare the installed tonnage to the house's Manual J cooling load: enter your ZIP code and the house on this page, and read the installed size against the ACCA Manual S window it prints. A single-speed unit whose capacity is above 115 percent of the load is past the Manual S ceiling for its class.

Is the heating load different from the cooling load?

Yes. Heating load depends on the temperature difference between indoor and outdoor design temperatures, insulation, and air infiltration. Where the winter design temperature difference is greater than the summer one, heating load is larger than cooling load. However, in hot-humid climates (Zones 1-2), cooling load dominates because you also need to remove moisture.

What is a Manual J calculation?

Manual J is the ACCA (Air Conditioning Contractors of America) standard method for calculating residential heating and cooling loads. It accounts for climate data, building orientation, window area and type, insulation levels, infiltration, duct losses, and internal heat gains. A jurisdiction can require a Manual J for a permit application on a new HVAC installation.

How do windows affect my BTU load?

Windows can be a large source of heat gain in a home. Single-pane glass admits substantially more solar heat than double-pane low-E, and south and west-facing windows contribute the most cooling load. This calculator prices the reference house's glass as single, double or triple pane through Manual J's window tables at your station. We do not publish a percentage for the single-pane penalty or for the saving from upgrading, because the honest answer depends on orientation, shading and glass coating, and ACCA Manual J Table 3 gives a heat-transfer multiplier per case rather than a single figure.

Does duct location matter for HVAC sizing?

Yes. Ducts running through a vented attic or an unconditioned basement or crawl space lose heat by conduction and air leakage, while ducts inside conditioned space lose far less. This calculator prices the duct location you choose through ACCA Manual J's Table 7 duct load factors and prints the line in its working; ducts inside the conditioned space or a ductless system carry no duct load. A measured duct-leakage figure for your house comes from a duct-leakage test.

How accurate is this calculator compared to a Manual J?

It runs ACCA Manual J's abridged method surface by surface on our server: your ZIP code finds the nearest ASHRAE weather station and its design temperatures, your answers compose a house on DOE's 2021 reference house plan, and the wall, ceiling, floor, window, door, infiltration, internal gain and duct lines are priced from the printed tables and shown in the working. What it does not know about your house it takes from that plan, and it lists those assumptions. Where your house differs from those assumptions (its window area, its orientation, its exact insulation), the load differs, which is what the Manual J load calculator's fuller questions are for. Where Manual J's printed tables do not reach a station's cooling conditions at the daily range class you set, it gives no cooling load rather than a guess, and says whether another class computes there. It is a whole-house block load: for permit applications and equipment selection you need a room-by-room Manual J from ACCA-approved software.


Related Calculators

Manual J Load Calculator

Every envelope question asked: ACCA Manual J Form J1 worked against the actual ASHRAE design temperatures for your ZIP's nearest weather station, component by component, with anything the printed method cannot price named instead of folded in.

CFM Calculator

The next step after the load: required airflow from tonnage (400 CFM/ton) or sensible load (CFM = BTU / (1.08 x deltaT)), which feeds the duct size calculator.

Gas Pipe Sizing Calculator

Gas appliance? The input Btu/h you set here is what the pipe has to carry. Sizes every section of the system, natural gas or propane, with the length method named and the code address for the book your jurisdiction adopted.

Combustion Air Calculator

Sizing a gas appliance? The input Btu/h you set here also decides the combustion air the space needs: the confined-vs-unconfined verdict and the required opening under IFGC 304.

Duct Size Calculator

Size the ducts for that airflow: round and rectangular duct size by the equal-friction method, with velocity and the rectangular equivalent.

Superheat & Subcooling Calculator

Check charge level with PT interpolation for 11 refrigerants including R-454B and R-32. Four-quadrant diagnostic decision tree.

Tonnage From Model Number

Compare the load result against the existing unit's nominal tonnage, decoded straight from its model number for 40+ brands.

HVAC Serial Number Lookup

Decode a unit's build date from its serial number for 54 brands (a furnace's for 34), with the refrigerant era, the maker's warranty term where its certificate is held here, and every valid reading shown when a format is ambiguous unless a held maker document about the typed model rules one out.

BTU Per Square Foot Chart

Heating and cooling BTU per square foot by IECC climate zone: Manual J computed on DOE's 2021 reference house at each zone's ASHRAE station, beside DOE's own sizing.

Sized the system? Verify the charge next.

A right-sized unit still underperforms if the charge is off. The superheat and subcooling calculator handles PT interpolation for 11 refrigerants, including R-454B and R-32, with a four-quadrant diagnostic to point you at the fault.