HVAC Calculator
BTU / HVAC Load Calculator
Size your air conditioning system by climate zone, insulation level, window area, and duct location. Calculates cooling load in BTU and converts to tonnage so you order the right equipment, not one size too big.
Intry VerifiedA worked default reading, traceable end to end: what it was calculated from, what it was run with, how it was checked, and who has final say.
Where this number comes fromIntry Verified
- Calculated from
- ACCA Manual J (simplified) / Manual S fit
- Run with
- Total area1,500 sqft
- Climate zoneZone 4 (Baltimore, Nashville, St. Louis, Richmond)
- InsulationAverage: code-minimum (R-13 walls, R-30 attic)
- WindowsDouble-pane
- DuctsConditioned space
- Checked
- Every figure an Intry calculator computes comes from a locked source module, not hand-typed. 21026 automated checks re-derive and source-check the numbers against the ACCA Manual J basis it came from before each deploy. This is our own deterministic gate, not a third-party audit.
- Final say
- A full Manual J on the actual house has final say.
Intry Verified · Build AE2FC52 · 2026-08-21
Embed the BTU Load Calculator on Your Site
Add it to any website, blog, or training page. One line of code, always the deployed engine, no login, no API key.
- Copy the code below.
- Paste it into any page, post, or CMS (WordPress, Squarespace, Webflow, raw HTML).
- Done. It always runs the currently deployed engine. Keep the credit line so readers know where it comes from.
Cooling Tonnage by Climate Zone
| Zone | Description | BTU/sqft | 1,000 sqft | 1,500 sqft | 2,000 sqft | 2,500 sqft |
|---|---|---|---|---|---|---|
| 1 | Hot Humid | 25 | 2 ton96% of load | 3 ton96% of load | 4 ton96% of load | 5 ton96% of load |
| 2 | Hot | 22 | 2 ton109.1% of load | 3 ton109.1% of load | 3.5 ton95.5% of load | 5 ton109.1% of load |
| 3 | Warm | 20 | 1.5 ton90% of load | 2.5 ton100% of load | 3.5 ton105% of load | 4 ton96% of load |
| 4 | Mixed | 18 | 1.5 ton100% of load | 2.5 ton111.1% of load | 3 ton100% of load | 4 ton106.7% of load |
| 5 | Cool | 16 | 1.25 ton93.8% of load | 2 ton100% of load | 2.5 ton93.8% of load | 3.5 ton105% of load |
| 6 | Cold | 14 | 1.25 ton107.1% of load | 2 ton114.3% of load | 2.5 ton107.1% of load | 3 ton102.9% of load |
| 7 | Very Cold | 12 | 1 ton100% of load | 1.5 ton100% of load | 2 ton100% of load | 2.5 ton100% of load |
Load = sqft × BTU/sqft. A ton is 12,000 BTU/hr by definition. The size shown is the nominal unit closest to that load whose capacity still falls between 90% and 115% of it, the acceptable range ACCA Manual S sets for single-speed cooling equipment (Table N2-1, printed folio N12). Manual S bounds the capacity, not the rounding: it says in the same section that equipment selection shall not be based on standard sizes, so treat the tonnage as a screening figure and the percentage beside it as the number that matters. Actual sizing requires adjustments for insulation, windows, ceiling height, duct location and occupancy, and a real selection is made against the manufacturer’s performance data with a full Manual J.
What Is a BTU?
A BTU (British Thermal Unit) is the amount of energy required to raise the temperature of one pound of water by one degree Fahrenheit. In HVAC, BTU measures the rate of heat transfer: how much heat an air conditioning system can remove from a space per hour (BTU/h). When someone says a system is "36,000 BTU," they mean it can remove 36,000 BTUs of heat energy from the indoor air every hour.
The measurement dates back to the 1800s and remains the standard unit for heating and cooling capacity in the United States. While the rest of the world uses watts and kilowatts, American HVAC equipment is still rated in BTU/h. The conversion is straightforward: 1 ton of cooling = 12,000 BTU/h = 3.517 kW. A typical residential AC system moves between 18,000 and 60,000 BTU/h (1.5 to 5 tons).
Understanding BTU matters because every component in your HVAC system (the compressor, evaporator coil, condenser, and ductwork) must be matched to the building's load. An undersized system runs constantly without reaching setpoint. An oversized system short-cycles, wasting energy and failing to dehumidify. The goal is to calculate the exact thermal load your building produces and match equipment to that number.
Cooling vs Heating Load
Cooling load and heating load measure different things and are rarely equal. Cooling load is the amount of heat that must be removed from a space to maintain the desired indoor temperature. It includes heat from the sun (solar gain through windows and roof), heat conducted through walls and ceiling, heat generated by people and appliances (internal gains), and moisture that must be condensed out of the air (latent load).
Heating load is simpler in concept: it is the amount of heat lost through the building envelope (walls, windows, roof, foundation) plus infiltration (cold air leaking in through gaps). There is no solar gain component and no latent load to worry about. The driving factor is the temperature difference between inside and outside. The colder it gets outside, the more heat escapes.
In most of the continental US, the heating load is larger than the cooling load because the winter design temperature difference is greater than the summer one. A home in Zone 5 (Chicago) might have a 70-degree difference in winter (70°F indoor vs 0°F outdoor)but only a 20-degree difference in summer (75°F indoor vs 95°F outdoor, plus solar and latent loads). The exception is hot-humid climates (Zones 1-2), where the combination of high temperatures and humidity makes cooling the dominant load year-round.
For heat pump systems, this distinction is critical. A heat pump sized for cooling may be undersized for heating in cold climates, requiring a backup heat source (electric resistance strips or a gas furnace). Modern cold-climate heat pumps have improved dramatically, but the fundamental physics remains: if your heating load is 60,000 BTU and your heat pump delivers 40,000 BTU at design temperature, you need supplemental heat.
The Danger of Oversizing
The most common HVAC sizing mistake is going too big. Homeowners assume bigger is better. Some contractors upsize as insurance against callbacks. Both instincts are wrong, and the consequences are measurable and persistent.
Short cycling. An oversized AC reaches the thermostat setpoint too quickly, so the compressor shuts off, the house warms up, and it kicks back on. Rapid on-off cycling is hard on a compressor: every start draws far more current than steady running, which stresses contacts and electrical components. We do not publish a cycle-length target or a startup-current multiple, because we have no source for either that we have checked ourselves.
Humidity problems. Air conditioning removes moisture by passing air over a cold evaporator coil. Moisture condenses on the coil and drains away. This process takes time. The coil needs to get cold and stay cold for the full cycle. When an oversized system short-cycles, the coil never reaches peak dehumidification. The house temperature drops, but the humidity stays high. Occupants feel cold and clammy, so they lower the setpoint, which makes the system run even shorter cycles. In humid climates (Zones 1-3), oversizing can result in indoor humidity above 60%, creating conditions for mold growth.
Wasted energy, but not for the reason usually given. One Department of Energy national laboratory study, NREL/TP-5500-60801 (November 2014), simulated a 1960s Houston house and found the oversizing energy penalty was -2% to 4% when the equipment drew no off-cycle standby power, and 10% to 21% when it drew standby power proportional to capacity. Its conclusion is that the penalty "is not due to unit cycling efficiency but rather to off-cycle parasitic power consumption": extra cycling by itself did not move the energy number much. Read it with its scope attached, because the scope is in the half of the title people drop: it is a simulation study of retrofit sequence impacts, where the oversized case is a unit replaced at its old capacity after the house was tightened, not a contractor upsizing at install. Other work disagrees and reports a larger cycling penalty, so treat the cause as contested. What is not contested is the comfort and humidity case made above, which is the more reliable reason not to oversize. One simulated house is not a national average, and we have not measured any of this ourselves.
Higher upfront cost. A larger system costs more in equipment alone, and the knock-on costs follow it: the ductwork may need to be larger and the electrical circuit may need to be upsized. You pay more for a system that performs worse. We publish no dollar figure here because we do not track equipment pricing.
The correct approach: calculate the load accurately, then select equipment that matches. If the calculation shows 30,000 BTU, install a 2.5-ton system, not a 3.5-ton "just in case." Variable-speed equipment offers some forgiveness because it can ramp down, but even variable-speed systems have a minimum output. Proper sizing remains essential.
Climate Zones Explained
The International Energy Conservation Code (IECC) divides the United States into seven climate zones based on temperature and moisture conditions. These zones drive insulation requirements and building energy codes. The base BTU-per-square-foot values below are planning constants keyed to those zones, not values the IECC publishes: design load is an output of a Manual J calculation, and no code or standard tabulates it per climate zone. Each zone reflects distinct heating and cooling demands.
Zone 1: Very Hot-Humid
Southern tip of Florida, Hawaii, US territories. Cooling-dominated year-round with minimal heating needs. High latent (moisture) loads drive equipment selection. Base cooling load: 25 BTU/sqft. Most homes need AC running 8-10 months per year. Dehumidification capacity is as important as sensible cooling capacity.
Zone 2: Hot-Humid
Gulf Coast, southern Texas, southern Arizona, much of Florida. Long cooling seasons (6-8 months) with brief, mild winters. Base cooling load: 22 BTU/sqft. Humiditymanagement remains critical. Duct leakage in a hot attic adds to the cooling load, and this calculator applies its unconditioned-attic factor for it; a real figure for your house comes from a duct-leakage test.
Zone 3: Warm-Humid / Warm-Dry
Mid-South, inland California, northern Arizona, New Mexico. Mixed needs with meaningful cooling and heating seasons. Base cooling load: 20 BTU/sqft. The humid vs dry subdivision affects latent load calculations. Humid areas need more dehumidification capacity.
Zone 4: Mixed-Humid / Mixed-Dry
Mid-Atlantic, lower Midwest, central California, Pacific Northwest coast. Balanced heating and cooling loads. Base cooling load: 18 BTU/sqft. This is the most common zone for residential HVAC in the US. Heat pump systems work well here without supplemental heat in most cases.
Zone 5: Cool-Humid
Upper Midwest, Great Lakes, New England, Pacific Northwest inland. Heating-dominant with moderate cooling needs. Base cooling load: 16 BTU/sqft. Insulation quality has a larger impact on heating load than cooling load. Cold-climate heat pumps are increasingly viable but may still need backup heat below 5°F.
Zone 6: Cold
Northern tier states: Montana, Minnesota, northern New England, upstate New York. Long heating seasons (6-8 months). Base cooling load: 14 BTU/sqft. Heating load is typically 2-3 times the cooling load. High-performance insulation and air sealing have the biggest impact on total energy use. Many homes use furnaces with supplemental AC rather than heat pumps.
Zone 7: Very Cold
Northern Minnesota, northern Maine, Alaska interior. Extreme heating-dominant with minimal cooling needs. Base cooling load: 12 BTU/sqft. Some homes in Zone 7 do not have air conditioning at all, relying on natural ventilation for the brief summer. Where AC is installed, it is a relatively small system compared to the heating equipment.
How Insulation Affects Load
Insulation is the single largest variable in load calculations after climate zone and building size. The R-value (thermal resistance) of your walls, ceiling, and floor determines how fast heat moves through the building envelope. Higher R-values mean slower heat transfer and lower loads.
A poorly insulated home in Zone 4 (uninsulated or minimal) needs about 23.4 BTU/sqft against the 18 BTU/sqft base, and a well-insulated one (above-code (R-19 walls, R-49 attic)) about 15.3. Those come straight from this calculator's own zone base and insulation multipliers, not from a separate table. The difference translates directly into equipment size: at 2,000 sqft that is 4 tons of equipment against 2.5, which is a real difference in equipment cost and in every energy bill for the life of the system.
IECC 2021 minimum requirements by zone (Table R402.1.3): Zone 1 requires R-13 walls and an R-30 ceiling. Zone 2 requires R-13 walls and an R-49 ceiling. Zone 3 requires R-20 walls (or R-13 cavity plus R-5 continuous) and an R-49 ceiling. Zones 4-8 require R-30 walls (or R-20 cavity plus R-5 continuous, or R-13 plus R-10 continuous) and an R-60 ceiling. Homes built before these codes often have significantly less insulation, meaning their actual loads are higher than code-minimum calculations suggest. Always assess actual insulation levels, not assumed values.
Air sealing matters as much as insulation. A home with R-38 attic insulation but unsealed can penetrations, recessed lights, and gaps around plumbing can lose as much heat through air leakage as through conduction. A blower door test quantifies infiltrationin air changes per hour (ACH50). Older leaky homes test far higher than tight new construction, and the IECC sets a maximum by climate zone that a code-compliant new build has to meet. We do not publish the numbers here yet, because we have not fetched and re-derived that table ourselves. Each reduction in ACH directly reduces both heating and cooling loads.
When You Need a Full Manual J
This calculator provides a planning-level estimate. A full Manual J calculation is required or strongly recommended in several scenarios.
Permit requirements. Most jurisdictions require a Manual J calculation as part of the permit application for new HVAC installations, replacements, and major renovations. Building inspectors verify that equipment sizing matches the load calculation. An online calculator will not satisfy this requirement. You need a report generated by ACCA-approved software (Wrightsoft, HVAC-Calc, CoolCalc, or similar) signed by a licensed contractor.
Complex homes. Homes with unusual geometry, multiple stories with significantly different exposures, large window walls, cathedral ceilings, additions, or mixed construction types need room-by-room analysis that simplified calculators cannot provide. A full Manual J accounts for each room's unique characteristics and ensures ductwork distributes capacity where it is actually needed.
Equipment warranty. Some manufacturers require a Manual J calculation to validate warranty claims. If an improperly sized system fails prematurely, the manufacturer may deny the warranty claim if no load calculation was performed.
High-performance homes. Passive houses, net-zero homes, and deeply retrofitted buildings often have loads so low that standard rules of thumb dramatically oversize equipment. A tight, well-insulated 2,000 sqft home might need only 12,000 BTU of cooling (one ton) where a standard calculator would suggest 3 tons. Only a detailed Manual J captures these savings.
Manual J vs Manual S
Manual J and Manual S are two separate ACCA standards that work together. Manual J calculates the load: how many BTU your building needs. Manual S selects the equipment: which specific make and model to install. They are sequential: you cannot do Manual S without completing Manual J first.
Manual J produces a load number (e.g., 36,000 BTU sensible cooling, 9,000 BTU latent cooling, 45,000 BTU total cooling). Manual S takes that number and matches it to manufacturer performance data at your specific design conditions. This matters because equipment capacity varies with outdoor temperature and indoor conditions. A unit rated at 36,000 BTU at the AHRI test condition (95°F outdoor, 80°F indoor, 67°F wet bulb) might deliver 42,000 BTU at 85°F or only 30,000 BTU at 105°F.
Manual S requires that a single-speed unit's total cooling capacity at design conditions falls between 90% and 115% of the Manual J total cooling load. Multi-speed equipment runs to 120% and variable-speed to 130%, and in a cold winter with no latent load a heat pump is capped by the Manual J load plus 15,000 BTU/hr rather than by a ratio at all. Latent capacity must be at least 100% of the latent load. This prevents both undersizing (comfort complaints on the hottest and coldest days) and oversizing (efficiency and humidity problems year-round).
A common shortcut that causes problems: a contractor calculates a 36,000 BTU load and installs a "3-ton" system without checking Manual S. That 3-ton system might actually deliver 40,000 BTU at their design conditions, which is 11% over and within the 115% limit. Or it might deliver 44,000 BTU, which is 22% over, outside the limit, and likely to cause short-cycling and humidity issues. Manual S closes this gap by verifying performance at your actual conditions.
Worked Examples
Example 1: 1,500 sqft Ranch in Zone 4 (Virginia)
A single-story ranch home in Richmond, VA (Zone 4, Mixed-Humid). Average code-minimum insulation, double-pane windows covering 15% of wall area, 8-foot ceilings, ducts in the unconditioned attic, typical existing-home air sealing.
Step 1: Base load = 1,500 sqft × 18 BTU/sqft = 27,000 BTU. Step 2: Insulation: average code-minimum, no change (×1.0). Step 3: Windows: at 15% glazing the home is below the 20% double-pane baseline, so the windows trim the load about 5% (×0.95) = 25,650 BTU. Step 4: Duct location: unconditioned attic adds 15% (×1.15). Step 5: Infiltration: typical existing home adds 10% (×1.10). Combined: 27,000 × 0.95 × 1.15 × 1.10 = 32,447 BTU. Step 6: Convert to tonnage = 32,447 ÷ 12,000 = 2.70 tons. Result: A 2.5-ton system, which delivers 92% of this load. A 3-ton unit is 111% and is also inside the ACCA Manual S window, so either is defensible and the smaller one dehumidifies better. If the homeowner sealed the ductwork or air-sealed the envelope the load drops further; run the numbers before upsizing.
Example 2: 2,500 sqft Two-Story in Zone 2 (Houston)
A two-story home in Houston, TX (Zone 2, Hot-Humid). Average code-minimum insulation, 20% window area with double-pane low-E glass, 8-foot ceilings, ducts in the unconditioned attic, typical existing-home air sealing.
Step 1: Base load = 2,500 sqft × 22 BTU/sqft = 55,000 BTU. Step 2: Insulation: average code-minimum, no change (×1.0). Step 3: Windows: low-E glass trims load; at 20% window area the reduction is 3% = 55,000 × 0.97 = 53,350 BTU. Step 4: Duct location: unconditioned attic adds 15% = 53,350 × 1.15 ≈ 61,353 BTU. Step 5: Infiltration: typical existing home adds 10% = 61,353 × 1.10 ≈ 67,488 BTU. Step 6: Convert = 67,488 ÷ 12,000 = 5.6 tons. Result: This home needs a two-zone system, for example a 3-ton unit for downstairs and a 2.5-ton for upstairs. No single nominal size complies: the largest standard residential unit, 5 ton, delivers 88.9% of this load, below the 90% ACCA Manual S minimum that applies at every compressor speed. A single oversized unit would short-cycle on mild days. This is a case where a full Manual J is essential.
Example 3: 800 sqft Condo in Zone 6 (Minneapolis)
A second-floor condo unit in Minneapolis, MN (Zone 6, Cold). Good above-code insulation, double-pane low-E windows covering 12% of wall area, 8-foot ceilings, tight new construction, cooled by a ductless mini split.
Step 1: Base load = 800 sqft × 14 BTU/sqft = 11,200 BTU. Step 2: Insulation: good above-code insulation reduces load 15% = 11,200 × 0.85 = 9,520 BTU. Step 3: Windows: low-E at 12% window area trims about 2% = 9,520 × 0.982 ≈ 9,349 BTU. Step 4: No ducts: a mini split has zero duct losses, reduce 5% = 9,349 × 0.95 ≈ 8,881 BTU. Step 5: Infiltration: tight, air-sealed construction, no change (×1.0). Step 6: Convert = 8,881 ÷ 12,000 = 0.74 tons. Result: A 0.75-ton (9,000 BTU) mini split, which delivers 101% of this load and is the only nominal size inside the ACCA Manual S window for it. A 1-ton unit is 135% of the load, past the 115% single-speed ceiling. This is typical for well-insulated condos in cold climates. The cooling load is very small because the heating load dominates and the unit benefits from thermal buffering by adjacent units.
Frequently Asked Questions
How many BTU do I need per square foot?
Plan for about 18-20 BTU per square foot in a moderate climate (zones 3-4), 22-25 in hot climates (zones 1-2), and 12-16 in cold climates (zones 5-7). These are base values before adjustments for insulation, windows, ceiling height, and duct location, so a Manual J calculation is the accurate method.
What is the difference between BTU and tons?
One ton of cooling equals 12,000 BTU per hour. The term comes from the amount of heat needed to melt one ton of ice in 24 hours. Residential AC systems typically range from 1.5 to 5 tons. To convert BTU to tons, divide by 12,000. A 36,000 BTU system is a 3-ton unit.
Why is oversizing an AC bad?
An oversized AC cools the air too quickly without running long enough to remove humidity. This causes short cycling (frequent on/off), which increases wear on the compressor and leaves your home feeling cold and clammy. Properly sized equipment runs longer cycles and dehumidifies effectively. On energy specifically the evidence is mixed: a DOE national laboratory simulation (NREL/TP-5500-60801) found oversizing added little energy through cycling itself and mattered mainly where the equipment draws standby power between cycles, while older field work reports a larger cycling penalty. Comfort and humidity are the reliable reasons to size correctly.
How do I know if my AC is too big for my house?
Two signs point to an oversized system: short cycling and poor humidity control. If the AC runs for only a few minutes, shuts off, and restarts frequently, and the house feels cold but damp or clammy, the unit is almost certainly larger than the load. Compare the installed tonnage to a real load estimate: a right-sized system in a moderate climate runs close to 18-20 BTU per square foot, so a 2,000 sq ft house needs roughly 3 to 3.5 tons there, and a 5-ton unit on that house is oversized in nearly any climate. The definitive check is a Manual J load calculation. Run the numbers on this page by climate zone, and if the installed size is more than about half a ton above the calculated load, it is oversized.
Is the heating load different from the cooling load?
Yes. Heating load depends on the temperature difference between indoor and outdoor design temperatures, insulation, and air infiltration. In most of the US, heating load is larger than cooling load because winter temperature differences are greater. However, in hot-humid climates (Zones 1-2), cooling load dominates because you also need to remove moisture.
What is a Manual J calculation?
Manual J is the ACCA (Air Conditioning Contractors of America) standard method for calculating residential heating and cooling loads. It accounts for climate data, building orientation, window area and type, insulation levels, infiltration, duct losses, and internal heat gains. Most jurisdictions require a Manual J for permit applications on new HVAC installations.
How do windows affect my BTU load?
Windows are typically the largest source of heat gain in a home. Single-pane glass admits substantially more solar heat than double-pane low-E, and south and west-facing windows contribute the most cooling load. This calculator adjusts for window area percentage and type. We do not publish a percentage for the single-pane penalty or for the saving from upgrading, because the honest answer depends on orientation, shading and glass coating, and ACCA Manual J Table 3 gives a heat-transfer multiplier per case rather than a single figure.
Does duct location matter for HVAC sizing?
Significantly. Ducts running through an unconditioned attic or crawlspace lose heat by conduction and air leakage, while ducts inside conditioned space lose far less. This calculator applies +15% for ducts in an unconditioned attic, +5% for an unconditioned basement, no adjustment for ducts in conditioned space, and -5% for ductless mini splits. Those four are planning constants, not a measured duct-loss model, and a real duct-loss figure comes from a blower-door and duct-leakage test on the actual house.
How accurate is this calculator compared to a Manual J?
This calculator uses a simplified square-foot method on IECC 2021 climate zones. The base BTU-per-square-foot values are calibrated planning constants, not figures any standard publishes, and the calculator adjusts them for insulation, window area and type, orientation, ceiling height, duct location and infiltration. A detailed ACCA Manual J is a different procedure: it works surface by surface from printed tables against your actual construction, and it computes solar gain, internal gains and duct loads as their own terms rather than as multipliers. We do not publish an accuracy percentage for this estimate. We are building that surface-by-surface engine against the Manual J 8th Edition itself, and what it has measured so far is one-sided: on a partial reconstruction a small share of cases already come out low, worst in the hottest zones, and no case has yet been shown accurate. We will print a figure when we can show the working behind it. For permit applications, equipment selection, and warranty compliance, you need a full Manual J performed by an HVAC contractor using ACCA-approved software.
Related Calculators
Manual J Load Calculator
A worked load rather than a square-foot estimate: ACCA Manual J Form J1 worked against the actual ASHRAE design temperatures for your ZIP's nearest weather station, component by component, with anything the printed method cannot price named instead of folded in.
CFM Calculator
The next step after the load: required airflow from tonnage (400 CFM/ton) or sensible load (CFM = BTU / (1.08 x deltaT)), which feeds the duct size calculator.
Gas Pipe Sizing Calculator
Gas appliance? The input Btu/h you set here is what the pipe has to carry. Sizes every section of the system, natural gas or propane, with the length method named and the code address for the book your jurisdiction adopted.
Combustion Air Calculator
Sizing a gas appliance? The input Btu/h you set here also decides the combustion air the space needs: the confined-vs-unconfined verdict and the required opening under IFGC 304.
Duct Size Calculator
Size the ducts for that airflow: round and rectangular duct size by the equal-friction method, with velocity and the rectangular equivalent.
Superheat & Subcooling Calculator
Check charge level with PT interpolation for 10 refrigerants including R-454B and R-32. Four-quadrant diagnostic decision tree.
Tonnage From Model Number
Compare the load result against the existing unit's nominal tonnage, decoded straight from its model number for 40+ brands.
HVAC Serial Number Lookup
Decode any unit's age from its serial number: 50+ brands, refrigerant era, and warranty context, with every valid reading shown when a format is ambiguous.
BTU Per Square Foot Chart
The quick rule-of-thumb version: cooling and heating BTU per square foot by climate zone plus the tons-to-BTU conversion.
Sized the system? Verify the charge next.
A right-sized unit still underperforms if the charge is off. The superheat and subcooling calculator handles PT interpolation for 10 refrigerants, including R-454B and R-32, with a four-quadrant diagnostic to point you at the fault.