NEC Wire Sizing
What Size Wire for a Hot Tub?
The breaker, copper and aluminum wire, and ground for the hot tub circuit this page shows, with the NEC basis and the nameplate caveats that actually decide it.
Hot Tub Circuit Spec
Branch circuit shown for a hot tub (nameplate rating, GFCI per NEC 680.44)
Swipe the table sideways to see the rest of its columns. →
| Voltage | 240V |
| Breaker | 50A GFCI |
| Copper wire | #6 |
| Copper (75°C conduit) | Strong Spas: 60°C, #6 |
| Aluminum wire (75°C-marked terminations, SER or conduit) | Strong Spas: copper only |
| Equipment ground (insulated Cu, 680.7(A)) | #10 |
Size to the spa's nameplate and its maker's table: Strong Spas' manual for its 230/240V hardwired spas lists a 40A Class A GFCI breaker with #8 AWG copper for its 29A one-pump models, 50A with #6 AWG for its 33A pump-and-blower models (the 50A circuit this page shows), and 60A with #6 AWG for its 41A to 48A two- and three-pump models. NEC Article 680 also requires a disconnect within sight and at least 5 feet horizontally from the tub's inside walls. GFCI: NEC Article 680 requires GFCI protection for a hot tub's outlet (680.44). Wire sized at NEC Table 310.16 (copper lead at the 60°C column for NM-B); ground per NEC Table 250.122, as an insulated copper conductor not smaller than 12 AWG (NEC 680.7(A)). The appliance nameplate lists the exact minimum circuit and maximum breaker; it governs over the circuit shown here.
Strong Spas' manual for its 230/240V hardwired spas lists every wire as copper and footnotes "All wire is to be coded by 60C ampacity and Rated 90C.", and says "Use copper wire with THHN insulation. Do not use aluminum wire." The maker's instructions govern (NEC 110.3(B)), so this page offers #6 copper only for this circuit. Conductor rule: Strong Spas Owner's Manual, 230-240V Hardwired (pages 5 and 6), read 2026-11-12.
For a unit whose maker permits aluminum (not Strong Spas's): Aluminum branch conductors are 75°C-rated AA-8000 alloy (SER cable, or XHHW-2 / THWN-2 in conduit); there is no 60°C aluminum NM-B, so the aluminum row uses the 75°C column. Where the terminations are rated 60°C only, size aluminum from the 60°C column instead (#4 here). Aluminum: the terminals it lands on must be identified for aluminum conductors (NEC 2023, 110.14(A)).
Adding this as a new load? Check whether your panel can handle it (the NEC 220.87 service check), or compare it against the breaker size by load chart.
Size Your Exact Circuit
It opens on this page's 50 A circuit at the 60°C column. For a nameplate that differs from this page's circuit, enter your exact load and conditions. For a long run, the result links to the voltage drop calculator, which checks that wire over your run; this tool does not size for voltage drop. On this page the tool holds the maker's condition (Strong Spas): the 60°C column and copper only, and a saved or shared link keeps it.
The code sections this page cites are named in the source receipt.
Frequently Asked Questions
What size wire do I need for a hot tub?
This page shows a hot tub on a 50A / 240V circuit, which calls for #6 copper (copper only: Strong Spas forbids aluminum) conductors and a #10 copper equipment ground per NEC Table 250.122, as an insulated copper conductor not smaller than 12 AWG (NEC 680.7(A)). Strong Spas' manual for its 230/240V hardwired spas lists every wire as copper and footnotes "All wire is to be coded by 60C ampacity and Rated 90C.", and says "Use copper wire with THHN insulation. Do not use aluminum wire." Size to the spa's nameplate and its maker's table: Strong Spas' manual for its 230/240V hardwired spas lists a 40A Class A GFCI breaker with #8 AWG copper for its 29A one-pump models, 50A with #6 AWG for its 33A pump-and-blower models (the 50A circuit this page shows), and 60A with #6 AWG for its 41A to 48A two- and three-pump models. NEC Article 680 also requires a disconnect within sight and at least 5 feet horizontally from the tub's inside walls. GFCI: NEC Article 680 requires GFCI protection for a hot tub's outlet (680.44).
What size breaker for a hot tub?
A 50A double-pole (240V) breaker. The #6 copper conductors are matched to that 50A rating, and it must be a GFCI breaker (or GFCI protection ahead of the appliance). Do not oversize the breaker to a wire it does not protect: the breaker and the conductor go up together. Always confirm against the appliance nameplate, which lists the exact minimum circuit and maximum overcurrent device.
Does a hot tub need GFCI protection?
Yes. GFCI: NEC Article 680 requires GFCI protection for a hot tub's outlet (680.44). Use a GFCI breaker or a GFCI device ahead of it. For a hot tub or spa, a disconnect within sight and at least 5 feet horizontally from its inside walls is also required (NEC 680.13).
Can I use aluminum wire for a hot tub?
Not for the unit this page shows. Strong Spas' manual for its 230/240V hardwired spas lists every wire as copper and footnotes "All wire is to be coded by 60C ampacity and Rated 90C.", and says "Use copper wire with THHN insulation. Do not use aluminum wire." The maker's instructions govern (NEC 110.3(B)), so use #6 copper. Table 310.16 alone would allow #6 aluminum on the 75C column for a 50A circuit; that applies only to a unit whose maker permits aluminum.
Wire Size for Other Appliances
Electric Dryer
#10 copper on a 30A / 240V circuit.
Electric Range
#6 copper on a 50A / 240V circuit.
Electric Wall Oven
#8 copper on a 40A / 240V circuit.
Electric Cooktop
#8 copper on a 40A / 240V circuit.
Electric Water Heater
#10 copper on a 30A / 240V circuit.
Dishwasher
#12 copper on a 20A / 120V circuit.
Garbage Disposal
#14 copper on a 15A / 120V circuit.
Built-In Microwave
#12 copper on a 20A / 120V circuit.
Refrigerator
#12 copper on a 20A / 120V circuit.
Freezer
#12 copper on a 20A / 120V circuit.
Garage Door Opener
#12 copper on a 20A / 120V circuit.
Wire Size Calculator
Full NEC 310.16 sizing for any load, distance, and conditions.