NEC Wire Sizing

What Size Wire for a Hot Tub?

The breaker, copper and aluminum wire, and ground for a typical hot tub circuit, with the NEC basis and the nameplate caveats that actually decide it.

Quick answer: A hot tub typically needs a 50A / 240V circuit with #6 copper (or #6 aluminum) wire and a #10 copper ground. It must be GFCI protected. On 75°C terminals in conduit, #8 copper is permitted.

Hot Tub Circuit Spec

Typical branch circuit for a hot tub (NEC 680.44)
Voltage240V
Breaker50A GFCI
Copper wire#6
Copper (75°C conduit)#8
Aluminum wire (75°C, SER or conduit)#6
Equipment ground (Cu)#10

Portable spas and hot tubs are commonly on a 50A GFCI circuit, but the nameplate rules: some are 40A and some 60A. NEC Article 680 requires GFCI protection and a disconnect within sight and at least 5 feet from the tub. Wire sized at NEC Table 310.16 (copper lead at the 60°C column for NM-B); ground per NEC Table 250.122. The appliance nameplate lists the exact minimum circuit and maximum breaker; it always governs over a typical value.

Aluminum branch conductors are 75°C-rated AA-8000 alloy (SER cable, or XHHW-2 / THWN-2 in conduit); there is no 60°C aluminum NM-B, so the aluminum row uses the 75°C column. Where the terminations are rated 60°C only, size aluminum from the 60°C column instead (#4 here).

Adding this as a new load? Check whether your panel can handle it (the NEC 220.87 service check), or compare it against the breaker size by load chart.


Long Run? Size It Exactly

For a long run where voltage drop matters, or a nameplate that differs from the typical value, enter your exact load, distance, and conditions.

Loading calculator...

Frequently Asked Questions

What size wire do I need for a hot tub?

A hot tub typically uses a 50A / 240V circuit, which calls for #6 copper (or #6 aluminum) conductors and a #10 copper equipment ground per NEC Table 250.122. That is the 60C column, the NEC default for NM-B cable and terminations 100A and under; on 75C-rated terminals in conduit you may use #8 copper. Portable spas and hot tubs are commonly on a 50A GFCI circuit, but the nameplate rules: some are 40A and some 60A. NEC Article 680 requires GFCI protection and a disconnect within sight and at least 5 feet from the tub.

What size breaker for a hot tub?

A 50A double-pole (240V) breaker. The #6 copper conductors are matched to that 50A rating, and it must be a GFCI breaker (or GFCI protection ahead of the appliance). Do not oversize the breaker to a wire it does not protect: the breaker and the conductor go up together. Always confirm against the appliance nameplate, which lists the exact minimum circuit and maximum overcurrent device.

Does a hot tub need GFCI protection?

Yes. Current NEC requires GFCI protection for this appliance (NEC 680.44 and 210.8). Use a GFCI breaker or a GFCI device ahead of it. For a hot tub or spa, a disconnect within sight and at least 5 feet away is also required (NEC 680).

Can I use aluminum wire for a hot tub?

Yes. On the 75C column (the usual basis for aluminum), a 50A circuit needs #6 aluminum, versus #8 copper. Aluminum is common on larger circuits and services to save cost; apply antioxidant to the terminations, torque to the listed spec, and remember aluminum drops slightly more voltage on long runs.


Wire Size for Other Appliances