NEC Wire Sizing

What Size Wire for a Dishwasher?

The breaker, copper and aluminum wire, and ground for a typical dishwasher circuit, with the NEC basis and the nameplate caveats that actually decide it.

Quick answer: A dishwasher typically needs a 20A / 120V circuit with #12 copper (or #10 aluminum) wire and a #12 copper ground. It must be GFCI protected.

Dishwasher Circuit Spec

Typical branch circuit for a dishwasher (NEC 210.8)
Voltage120V
Breaker20A GFCI
Copper wire#12
Aluminum wire#10
Equipment ground (Cu)#12

A built-in dishwasher uses a dedicated 120V 20A circuit. It must be GFCI protected (210.8) and, under the 2023 NEC, AFCI protected. Some compact units fit a 15A circuit; a hardwired unit still needs its own circuit. Wire sized at NEC Table 310.16 (copper lead at the 60°C column for NM-B); ground per NEC Table 250.122. The appliance nameplate lists the exact minimum circuit and maximum breaker; it always governs over a typical value.


Long Run? Size It Exactly

For a long run where voltage drop matters, or a nameplate that differs from the typical value, enter your exact load, distance, and conditions.

Loading calculator...

Frequently Asked Questions

What size wire do I need for a dishwasher?

A dishwasher typically uses a 20A / 120V circuit, which calls for #12 copper (or #10 aluminum) conductors and a #12 copper equipment ground per NEC Table 250.122. A built-in dishwasher uses a dedicated 120V 20A circuit. It must be GFCI protected (210.8) and, under the 2023 NEC, AFCI protected. Some compact units fit a 15A circuit; a hardwired unit still needs its own circuit.

What breaker size for a dishwasher?

A 20A single-pole breaker. The #12 copper conductors are matched to that 20A rating, and it must be a GFCI breaker (or GFCI protection ahead of the appliance). Always confirm against the appliance nameplate, which lists the exact minimum circuit and maximum breaker.

Does a dishwasher need GFCI protection?

Yes. Current NEC requires GFCI protection for this appliance (NEC 210.8 and 210.8). Use a GFCI breaker or a GFCI device ahead of it. For a hot tub or spa, a disconnect within sight and at least 5 feet away is also required (NEC 680).

Can I use aluminum wire for a dishwasher?

Yes. For the 20A circuit, aluminum needs #10 (versus #12 copper) at the 75C column. Aluminum is common on larger circuits and services to save cost; apply antioxidant to the terminations, torque to the listed spec, and remember aluminum drops slightly more voltage on long runs.


Wire Size for Other Appliances