NEC 240.6 · 210.20 · 310.16
What Size Breaker Do I Need?
The standard breaker and copper wire for the loads people actually ask about, from a stove to an EV charger, plus the NEC method to size any breaker from watts.
Breaker Size by Load (Chart)
| Load | Volts | Breaker | Copper wire | NEC basis |
|---|---|---|---|---|
| General | ||||
| General lighting / receptacles (15A circuit) | 120V | 15A | #14 | NEC 210.23 |
| General receptacles (20A circuit) | 120V | 20A | #12 | NEC 210.23, 210.52(B) |
| Kitchen | ||||
| Electric range / stove (<= 12 kW) | 240V | 40A | #8 | NEC 210.19(A)(3), Table 220.55 |
| Electric wall oven | 240V | 40A | #8 | nameplate rating |
| Electric cooktop | 240V | 40A | #8 | nameplate rating |
| Dishwasher | 120V | 20A | #12 | NEC 210.8(A), 422.10 |
| Garbage disposal | 120V | 15A | #14 | nameplate rating |
| Microwave (built-in / OTR) | 120V | 20A | #12 | NEC 210.8(A), 210.23 |
| Refrigerator | 120V | 20A | #12 | NEC 210.52(B), 210.8(A) |
| Laundry | ||||
| Electric dryer | 240V | 30A | #10 | nameplate rating, NEC 210.23 |
| Washing machine | 120V | 20A | #12 | NEC 210.11(C)(2) |
| Water Heating | ||||
| Electric water heater (tank, 4500W) | 240V | 30A | #10 | NEC 422.13 |
| Tankless electric water heater | 240V | 60A | #6 | nameplate rating |
| HVAC | ||||
| Central air conditioner | 240V | 30A | #10 | NEC 440, nameplate MCA/MOCP |
| Electric furnace / air handler (10 kW) | 240V | 60A | #6 | NEC 424.3(B), nameplate |
| Baseboard heater | 240V | 20A | #12 | NEC 424.3(B) |
| Mini-split (ductless heat pump) | 240V | 20A | #12 | NEC 440, nameplate MCA/MOCP |
| Motors & Shop | ||||
| Well pump (1/2-1 HP, 230V) | 240V | 20A | #12 | NEC Article 430 |
| Air compressor (motor load) | 240V | 30A | #10 | NEC Article 430 |
| Welder | 240V | 50A | #6 | NEC 630.11, 630.12 |
| Hot tub / spa | 240V | 50A | #6 | NEC 680.44 |
| EV & Service | ||||
| EV charger (Level 2, 48A) | 240V | 60A | #6 | NEC 625.42, 625.41 |
| Main feeder / service (100A, whole dwelling) | 240V | 100A | #4 | NEC 310.12 |
| Dwelling service (200A) | 240V | 200A | #2/0 | NEC 230.42, 310.12 |
Copper conductor for each circuit. Sizes through 50A (#14 to #6) are valid on 60°C NM-B (Romex); a 60A circuit (#6) assumes 75°C conductors (THWN/THHN/SE), since NM-B at 60°C would need #4. Service and feeder rows use the 310.12 dwelling conductor, which applies only to conductors carrying the entire dwelling load. Motor and HVAC rows follow Articles 430 and 440 (size from the table FLC or the nameplate MCA/MOCP), not a flat rule. Always confirm against the nameplate and, for services and feeders, the load calculation.
Embed the Breaker Size by Load Chart on Your Site
Free for any website, blog, or training page. One line of code, always accurate, no login.
- Copy the code below.
- Paste it into any page, post, or CMS (WordPress, Squarespace, Webflow, raw HTML).
- Done. It stays accurate automatically. Keep the credit line so readers know where it comes from.
How Breaker Sizing Actually Works
Every breaker size traces back to one idea: the breaker protects the wire, and the wire has to carry the load. So you size in that order. First find the load current. For a resistive load it is watts divided by volts; for a motor it is the NEC table full-load current; for HVAC it is the nameplate Minimum Circuit Ampacity. Second, if the load runs for three hours or more it is continuous, and NEC 210.20(A) requires the breaker to be at least 125% of that current. Third, round up to the next standard breaker size in NEC 240.6(A) (15, 20, 25, 30, 35, 40, 50, 60…). Fourth, size the conductor so its ampacity from NEC Table 310.16 covers the breaker, honoring the 240.4(D) small-conductor rule.
A few load types break the flat pattern and are the ones people get wrong. Motors (well pumps, compressors) are sized from the table FLC under Article 430, with the breaker up to 250% of FLC so the motor can start, which is why they show a small wire under a big breaker. Air conditioners and heat pumps are sized from the nameplate MCA and MOCP under Article 440. Ranges use the demand factors of Table 220.55 rather than the full connected wattage. When in doubt, the nameplate and the load calculation govern, not a rule of thumb.
What Size Breaker for a Given Wattage
| Watts | Running amps | Min. breaker | If continuous (×1.25) |
|---|---|---|---|
| 3000W | 12.5A | 15A | 20A |
| 3500W | 14.6A | 15A | 20A |
| 4500W | 18.8A | 20A | 25A |
| 5000W | 20.8A | 25A | 30A |
| 5500W | 22.9A | 25A | 30A |
| 7500W | 31.3A | 35A | 40A |
| 9600W | 40A | 40A | 50A |
| 11500W | 47.9A | 50A | 60A |
| Watts | Running amps | Min. breaker | If continuous (×1.25) |
|---|---|---|---|
| 1000W | 8.3A | 15A | 15A |
| 1200W | 10A | 15A | 15A |
| 1500W | 12.5A | 15A | 20A |
| 1800W | 15A | 15A | 20A |
These are the code-minimum breaker sizes from the running current. A specific appliance may require the next common size (for example a 4500W water heater is installed on 30A with #10 copper, above its 25A minimum) or be sized directly to the nameplate. Never load a circuit past 80% continuously.
Frequently Asked Questions
What size breaker do I need for a stove?
The NEC minimum for a freestanding electric range or stove up to 12 kW is a 40A / 240V breaker with #8 copper: NEC Table 220.55 gives an 8 kW demand (about 33A) and NEC 210.19(A)(3) sets a 40A floor for ranges 8.75 kW and larger. In practice most ranges are installed on a 50A / 240V circuit with #6 copper and a NEMA 14-50 receptacle, which is also compliant and gives headroom. A range over 12 kW is sized up to its nameplate, and a gas stove needs only a 120V receptacle for its controls.
What size breaker for an electric water heater?
A standard 40-50 gallon, 4500W residential water heater is installed on a 30A / 240V breaker with #10 copper. It draws 18.75A, and NEC 422.13 treats a fixed water heater as a continuous load, so it is sized at 125% (23.4A); the code minimum is a 25A breaker, but 30A on #10 is the common install. A 5500W heater is also 30A. Tankless electric units are much larger and need 60-150A total.
What size breaker for a dryer?
An electric dryer uses a 30A / 240V breaker with #10 copper, per NEC 220.54. A gas dryer only needs a standard 120V 15A or 20A circuit for its motor and controls. Under the 2023 NEC, a dryer receptacle now requires GFCI protection, though adoption of that rule varies by jurisdiction.
What size breaker for a 48 amp EV charger?
A 48A EV charger needs a 60A breaker with #6 copper (75°C) wire. EV charging is a continuous load, so NEC 625.42 requires the circuit to be sized at 125% of the charger output: 48A x 1.25 = 60A. A 40A charger uses a 50A breaker, and a 32A charger uses a 40A breaker.
How do I figure out what size breaker I need from watts?
Divide watts by volts to get the running current, then choose the next standard breaker size (NEC 240.6) at or above it. For a continuous load (on 3 hours or more, such as a water heater, EV charger, or baseboard heat), size the breaker at 125% of that current first (NEC 210.20(A)). Example: a 3000W, 240V load draws 12.5A, so the minimum breaker is 15A (or 20A if continuous). Always size the wire to the breaker and confirm against the nameplate.
Does the wire size have to match the breaker?
Yes. The conductor must be able to carry the breaker's rating: 14 AWG copper for 15A, 12 AWG for 20A, 10 AWG for 30A, 8 AWG for 40A, and 6 AWG for 50A (and for 60A with 75°C wire). The NEC 240.4(D) small-conductor rule caps 14, 12, and 10 AWG copper at 15, 20, and 30A regardless of their higher table ampacity. Putting a larger breaker on undersized wire is the most dangerous wiring mistake because the breaker will not trip before the wire overheats.
What size breaker for a well pump or air compressor?
Motor loads follow NEC Article 430, not a flat rule. You size them from the table full-load current (NEC 430.248), not the nameplate: the conductor is 125% of FLC and the breaker can be up to 250% of FLC so the motor can start, which is why a motor circuit shows a small wire under a larger breaker. See the motor full-load current chart for the exact sizes by horsepower.
What size breaker for a central air conditioner?
Air conditioners and heat pumps are sized from the nameplate Minimum Circuit Ampacity (MCA) and Maximum Overcurrent Protection (MOCP) under NEC Article 440, not a flat rule. Use the MOCP printed on the unit as the maximum breaker and the MCA to size the wire. A typical 2-3 ton condenser lands on a 30A breaker, but always read the nameplate.
Related Calculators & Charts
Wire Size for Appliances
The matching conductor, ground, and full write-up for each specific appliance circuit.
Standard Breaker Sizes (240.6)
The complete list of standard breaker ampere ratings and the next-standard-size rule.
Motor Full-Load Current Chart
Breaker and wire for motor loads by horsepower, the one class that follows Article 430.
Have the breaker. Now size the wire and ground.
The wire size calculator takes any load and returns the conductor, the protecting breaker, and the equipment ground, with voltage drop checked on long runs.