NEC Article 424 (Fixed Electric Space Heating)
Heat Strip Wire Size and Breaker
The circuit for the electric heat strips in an air handler, at 208 V and 240 V: the plate first, then the Article 424 arithmetic with the blower inside the 125%.
Size Your Heat Strip Circuit
Enter the plate's minimum circuit ampacity and maximum breaker, or, for a unit marked only in volts and watts, the strip heat at the voltage it runs on and the blower's amps. It opens on a 10 kW strip at 240 V.
The Plate First, Then Article 424
A listed air handler or electric furnace prints, for each field circuit, a minimum circuit ampacity and a maximum breaker, and NEC 110.3(B) makes the listing's instructions binding: the conductor carries at least that ampacity, and the breaker is never larger than that maximum. NEC 424.28(A) requires the plate to state volts and watts or amps (and a motor's rating where it is over 1/8 hp), not a minimum circuit ampacity or maximum breaker, so for a unit marked that way the rule is 424.4(B): the branch-circuit conductors carry not less than 125 percent of the heating load and any associated motor, which is the blower when it runs on that circuit. This tool picks the breaker as the next standard size at or above that 125% figure and the smallest conductor that breaker protects (240.4, with 240.4(B)'s next size up).
A heat strip circuit is not an air-conditioning circuit. Table 240.4(G), which lets a condenser's conductor sit on a larger breaker, has no Article 424 row, so NEC 240.4(D) holds #10 copper to 30 A, #12 to 20 A and #14 to 15 A here. A circuit that also supplies a compressor (a packaged heat pump) is also Article 440 (424.3); size it with the MCA and MOCP calculator for it.
Heat Strips at 208 V (elements only)
| Strip Heat | Load Amps | At 125% | Breaker | Copper 60 °C (governs to 100 A unless marked) | Copper 75 °C (governs over 100 A) |
|---|---|---|---|---|---|
| 2.5 kW | 12.02 A | 15.02 A | 20 A | #12 AWG | #12 AWG |
| 3 kW | 14.4 A | 18 A | 20 A | #12 AWG | #12 AWG |
| 4 kW | 19.2 A | 24 A | 25 A | #10 AWG | #10 AWG |
| 5 kW | 24.04 A | 30.05 A | 35 A | #8 AWG | #8 AWG |
| 6 kW | 28.8 A | 36.1 A | 40 A | #8 AWG | #8 AWG |
| 7.5 kW | 36.1 A | 45.1 A | 50 A | #6 AWG | #8 AWG |
| 8 kW | 38.5 A | 48.1 A | 50 A | #6 AWG | #8 AWG |
| 9 kW | 43.3 A | 54.1 A | 60 A | #6 AWG | #6 AWG |
| 10 kW * | 48.1 A | 60.1 A | 70 A | #4 AWG | #6 AWG |
| 12.5 kW * | 60.1 A | 75.1 A | 80 A | #3 AWG | #4 AWG |
| 15 kW * | 72.1 A | 90.1 A | 100 A | #2 AWG | #3 AWG |
| 18 kW * | 86.5 A | 108.2 A | 110 A | #1 AWG | #2 AWG |
| 20 kW * | 96.2 A | 120.2 A | 125 A | 1/0 AWG | #1 AWG |
| 25 kW * | 120.2 A | 150.2 A | 175 A | 3/0 AWG | 2/0 AWG |
* Over 48 A of equipment load, NEC 424.22(B) has the unit's heating elements subdivided at 48 A or less each, protected at 60 A or less by supplementary devices in, on or supplied with the unit (424.22(C)). Whether the unit then takes one field circuit or several is its listing: wire what the plate prints (110.3(B)). The single-circuit figures on that row apply only where the unit is listed for a single-point connection. The governing column is in bold: On a circuit of 100 A or less the 60 °C size applies unless the unit is listed and identified for 75 °C conductors (NEC 110.14(C)(1)(a); such a unit is marked for them, 424.11). Over 100 A the 75 °C column applies (NEC 110.14(C)(1)(b)).
Heat Strips at 240 V (elements only)
| Strip Heat | Load Amps | At 125% | Breaker | Copper 60 °C (governs to 100 A unless marked) | Copper 75 °C (governs over 100 A) |
|---|---|---|---|---|---|
| 2.5 kW | 10.4 A | 13 A | 15 A | #14 AWG | #14 AWG |
| 3 kW | 12.5 A | 15.6 A | 20 A | #12 AWG | #12 AWG |
| 4 kW | 16.7 A | 20.8 A | 25 A | #10 AWG | #10 AWG |
| 5 kW | 20.8 A | 26 A | 30 A | #10 AWG | #10 AWG |
| 6 kW | 25 A | 31.3 A | 35 A | #8 AWG | #8 AWG |
| 7.5 kW | 31.3 A | 39.1 A | 40 A | #8 AWG | #8 AWG |
| 8 kW | 33.3 A | 41.7 A | 45 A | #6 AWG | #8 AWG |
| 9 kW | 37.5 A | 46.9 A | 50 A | #6 AWG | #8 AWG |
| 10 kW | 41.7 A | 52.1 A | 60 A | #6 AWG | #6 AWG |
| 12.5 kW * | 52.1 A | 65.1 A | 70 A | #4 AWG | #4 AWG |
| 15 kW * | 62.5 A | 78.1 A | 80 A | #3 AWG | #4 AWG |
| 18 kW * | 75 A | 93.8 A | 100 A | #2 AWG | #3 AWG |
| 20 kW * | 83.3 A | 104.2 A | 110 A | #1 AWG | #2 AWG |
| 25 kW * | 104.2 A | 130.2 A | 150 A | 2/0 AWG | 1/0 AWG |
* Over 48 A of equipment load, NEC 424.22(B) has the unit's heating elements subdivided at 48 A or less each, protected at 60 A or less by supplementary devices in, on or supplied with the unit (424.22(C)). Whether the unit then takes one field circuit or several is its listing: wire what the plate prints (110.3(B)). The single-circuit figures on that row apply only where the unit is listed for a single-point connection. The governing column is in bold: On a circuit of 100 A or less the 60 °C size applies unless the unit is listed and identified for 75 °C conductors (NEC 110.14(C)(1)(a); such a unit is marked for them, 424.11). Over 100 A the 75 °C column applies (NEC 110.14(C)(1)(b)).
Frequently Asked Questions
What size wire and breaker for 10 kW heat strips?
If the air handler's plate prints a minimum circuit ampacity and maximum breaker, size to those (NEC 110.3(B)). For a unit marked only in volts and watts: a 10 kW strip at 240 V draws 41.7 A, and NEC 424.4(B) sizes the conductor at not less than 125 percent, 52.1 A; the next standard breaker is 60 A, and the smallest conductor it protects is #6 AWG copper (60 °C or 75 °C), before the blower. Add the blower motor's amps inside the 125% when it runs on the same circuit.
Why is a 208 V heat strip circuit different from 240 V?
Because the kW on the plate is a rating at a stated voltage, and the amps are that rating divided by the voltage. A 5 kW rating at 240 V is 20.8 A (26 A at 125%, a 30 A breaker); a 5 kW rating at 208 V is 24.04 A (30.05 A at 125%, over 30, so a 35 A breaker with #8 AWG copper (60 °C or 75 °C)). Use the rating the plate prints for 208 V; a strip rated at 240 V run on 208 V is not the 240 V row.
Is the blower included in the heat strip circuit?
Where the blower runs on the same circuit, yes: NEC 424.4(B) sizes the branch-circuit conductors at not less than 125 percent of the heating load and any associated motor. Read the blower motor's amps from the plate and add them to the heater amps before the 125%. On a listed unit, the plate's minimum circuit ampacity for that circuit is the figure to use (110.3(B)).
What happens to heat strips over 48 A?
Over 48 A of equipment load, NEC 424.22(B) has the unit's heating elements subdivided at 48 A or less each, protected at 60 A or less by supplementary devices in, on or supplied with the unit (424.22(C)). Whether the unit then takes one field circuit or several is its listing: wire what the plate prints (110.3(B)). A strip rated 10 kW at 208 V (48.1 A) is over that line; one rated 10 kW at 240 V (41.7 A) is not.
Can I use #10 wire on a 35 or 40 A heat strip breaker?
Not on a heating circuit. Table 240.4(G) lets an air-conditioning circuit's conductor sit on the plate's larger maximum breaker, but that table has no Article 424 row, so on heat strips NEC 240.4(D) holds #10 copper to 30 A, #12 to 20 A and #14 to 15 A. If the plate allows a larger breaker, the calculator gives the conductor that breaker needs.
Does a heat strip air handler need its own disconnect?
NEC 424.19 requires a means that disconnects the heater, the motor controller and any supplementary overcurrent devices from all ungrounded conductors at once, rated at least 125 percent of the motor and heater load and capable of being locked open. Where the unit has factory element fuses or breakers (424.19(A)) that means is within sight of them; with a blower over 1/8 hp it may also serve the motor controller where it is in sight from both and complies with Part IX of Article 430, or it may be out of sight from the motor controller where the motor and heater have a single unit switch that complies with 422.34 (424.19(A)(2)). A branch breaker that is merely lockable is the disconnect only for equipment with no supplementary devices and no motor over 1/8 hp (424.19(B)(1)). A unit fed by more than one circuit has its disconnects grouped and identified.
Related Calculators
Electric Furnace Wire Size
The same Article 424 rules for a furnace's element bank, by kW.
Can My Panel Handle a Heat Pump?
Strip heat adds to what the service has to carry: the NEC 220.87 check.
MCA and MOCP Calculator
For a circuit that supplies a compressor (Article 440).
Baseboard Heater Wire Size
Watts per circuit for baseboard heat.