Intry Verified receipt

Is the Intry Heat Strip Circuit Calculator accurate and NEC compliant?

The provenance receipt for the Intry Heat Strip Circuit Calculator: the exact authority its values derive from, the edition they are keyed to, who has final say, and what our automated checks hold them against, rebuilt from their cited source.

Short answer: It computes from the NEC sections named below (NEC 2023), and our automated checks hold its answers against values written from those sources for the cases the checks cover, not for every input you can enter. Whether an installation is NEC compliant is decided by the inspector, not by a calculator. The unit nameplate has the final say on the circuit where it prints a minimum circuit ampacity and maximum breaker; your AHJ and local amendments govern the install. Every figure an Intry calculator computes comes from a locked source module, not hand-typed. 35,006 automated checks, one suite for the whole site rather than a per-tool count, re-derive the numbers before each deploy from the tables this site holds, read from the cited NEC section. This is our own deterministic gate, not a third-party audit. The per-tool receipt is public at https://www.intrysys.com/verified.

The receipt

Calculated from
NEC 110.3(B) · NEC 424.4(B) · NEC 240.6(A) · NEC 240.4(B) and 240.4(D) · NEC Table 310.16 and 110.14(C)(1) · NEC 424.22(B) · NEC Table 250.122 (NEC 2023). Reused word for word from the locked engine, never re-written for this page. The documents it rests on are listed in the source receipt on the tool page.
Edition
NEC 2023
What it reads
  • NEC 110.3(B)
  • NEC 424.4(B)
  • NEC 240.6(A)
  • NEC 240.4(B) and 240.4(D)
  • NEC Table 310.16 and 110.14(C)(1)
  • NEC 424.22(B)
  • NEC Table 250.122

Its pages also cite NEC 2023 220.87, 422.34, 424.19, 424.19(A)(2), 424.19(B)(1).

Checked
Checked on every build, most recently on November 11, 2026. On every build, an automated check runs the locked engine that produces these figures and holds its answers against the values this site holds, written from the source it cites, so a checked number answers to its source and not merely to itself. The check covers the cases someone wrote a check for, not every input the tool accepts: it tells you where a number comes from, and it is not a proof of every value. As of the current build that suite holds 35,006 checks, and this page has to clear them too. This is our own deterministic gate, not a third-party audit.
Tested safeguards
The breaker and conductors it gives from the heater and blower, its subdivision answer where NEC 424.22(B) applies, the breaker and conductor it gives from a data plate's minimum circuit ampacity and maximum breaker, the two tables on its page, and the breaker its saved, sent and copied reading states, carry their own safeguards: when the code behind them is broken on purpose, the safeguards catch it.
Source changes
No source has been added to or removed from this tool since this record began on October 24, 2026.
Runnable
A reference engine behind the published numbers on this site. Runnable access is offered on the calculators exposed at the Intry MCP endpoint.
Final say
The unit nameplate has the final say on the circuit where it prints a minimum circuit ampacity and maximum breaker; your AHJ and local amendments govern the install.

Frequently Asked Questions

Is the Intry Heat Strip Circuit Calculator accurate and NEC compliant?

It computes from the NEC sections named below (NEC 2023), and our automated checks hold its answers against values written from those sources for the cases the checks cover, not for every input you can enter. Whether an installation is NEC compliant is decided by the inspector, not by a calculator. The unit nameplate has the final say on the circuit where it prints a minimum circuit ampacity and maximum breaker; your AHJ and local amendments govern the install. Every figure an Intry calculator computes comes from a locked source module, not hand-typed. 35,006 automated checks, one suite for the whole site rather than a per-tool count, re-derive the numbers before each deploy from the tables this site holds, read from the cited NEC section. This is our own deterministic gate, not a third-party audit. The per-tool receipt is public at https://www.intrysys.com/verified.