NEC Article 424 (Fixed Electric Space Heating)
What Size Wire for a Baseboard Heater?
Electric baseboard is sized at 125% of the wattage (NEC 424.4(B)). Here is how much heat each circuit carries, the wire by wattage, and the calculator.
How Much Heat Each Circuit Carries
The real baseboard question is “how many heaters can I put on one circuit,” and the answer is a wattage budget, not a count. Add up every heater on the circuit and keep the total at or below the figure here (80% of the breaker, the inverse of the 125% sizing).
Maximum total baseboard wattage per circuit (sized at 125%, copper).
Swipe the table sideways to see the rest of its columns. →
| Circuit | Copper Wire | Max Watts @ 240V | Max Watts @ 120V |
|---|---|---|---|
| 15A | #14 AWG | 2,880 W | 1,440 W |
| 20A | #12 AWG | 3,840 W | 1,920 W |
| 30A | #10 AWG | 5,760 W | 2,880 W |
A 240V heater draws half the current of a 120V unit of the same wattage, so a circuit carries twice the heat. A branch circuit that supplies two or more fixed heater outlets is rated not over 30A (NEC 424.4(A)), which is why this table stops at 30A.
These tables come from the same Article 424 heat-circuit engine as the heat strip calculator. Where these figures come from
Single Baseboard Heater Wire Size (240V)
One 240V heater per circuit, copper. Load x 1.25 (NEC 424.4(B)).
Swipe the table sideways to see the rest of its columns. →
| Heater Wattage | Load Amps | At 125% | Breaker | Copper Wire |
|---|---|---|---|---|
| 1,000 W | 4.2 A | 5.2 A | 15 A | #14 AWG |
| 1,500 W | 6.3 A | 7.8 A | 15 A | #14 AWG |
| 2,000 W | 8.3 A | 10.4 A | 15 A | #14 AWG |
| 2,500 W | 10.4 A | 13 A | 15 A | #14 AWG |
| 3,000 W | 12.5 A | 15.6 A | 20 A | #12 AWG |
| 4,000 W | 16.7 A | 20.8 A | 25 A | #10 AWG |
Copper at the 60°C column (NM-B / always-safe). Several small heaters can share one 20A circuit up to the 3,840W budget above.
Size Your Exact Heating Circuit
It opens on a full 20 A baseboard circuit, 3,840 W at 240 V. Enter your total heater load in amps (watts / volts) and leave Continuous load on: it applies the 125% NEC 424.4(B) requires, so do not add it yourself.
The code sections this page cites are named in the source receipt.
Frequently Asked Questions
What size wire for a baseboard heater?
Match the wire to the circuit breaker, and size the circuit for 125% of the heater wattage: NEC 424.4(B) requires the branch-circuit conductors to carry not less than 125 percent of the fixed heating load. A 20A circuit with #12 copper carries up to 3,840 watts of heat at 240V (16A x 240V), and a 15A circuit with #14 copper up to 2,880 watts. Convert watts to amps first (watts / volts), multiply by 1.25, then pick the breaker and the matching wire.
How many baseboard heaters can I put on one circuit?
As many as fit under 80% of the breaker, which is the same as sizing at 125%. A 20A/240V circuit carries 3,840 watts total, so that is roughly two 1,500W heaters or three 1,000W heaters wired together. A 15A/240V circuit carries 2,880 watts. Add up the wattage of every heater on the circuit; the sum, not the count, is what matters. A line-voltage thermostat controlling the group counts as part of the circuit.
Are baseboard heaters 120V or 240V?
Both exist. A 240V heater draws half the current of a 120V heater of the same wattage (resistance heat turns all of its input into heat at either voltage), so a single circuit carries twice the heat. On 120V, a 20A/#12 circuit tops out at 1,920 watts and a 15A/#14 at 1,440 watts, half the 240V figures.
Why is a baseboard heater sized at 125%?
Because NEC 424.4(B) says so for fixed electric space heating: the branch-circuit conductor ampacity shall not be less than 125 percent of the load of the heating equipment and any associated motor. That puts a 3,000W / 240V heater (12.5A) on at least 15.6A of conductor (12.5 x 1.25), so #12 rather than #14. The breaker follows the same 125%: a heater that runs three hours or more is a continuous load, and NEC 210.20(A) sizes its overcurrent device at not less than 125 percent of it, so 15.6A needs a 20A breaker rather than a 15A. Keeping the total heat at or under 80% of the breaker is the same rule read backwards.
Does a baseboard heater need a dedicated circuit?
Not necessarily its own circuit. A branch circuit that supplies two or more fixed heater outlets is rated not over 30A (NEC 424.4(A)), and a receptacle built into a baseboard heater must not be connected to the heater circuit (NEC 424.10). A 15 or 20A circuit that also supplies lighting or plug-in loads may carry fastened-in-place heat of no more than 50 percent of its rating (NEC 210.23(B)(2)); the watt budgets on this page are for a circuit that serves only heaters. A line-voltage thermostat is wired in series ahead of the heaters it controls. Each heater also needs a disconnecting means (NEC 424.19): for a heater with no motor over 1/8 hp and no supplementary overcurrent devices, the branch-circuit breaker satisfies it where it is within sight of the heater or capable of being locked open (424.19(B)(1)).
Related
Can My Panel Handle It?
Before you add this load, the NEC 220.87 check on whether the service can carry it.
Electric Furnace Wire Size
The big electric-heat load: by kW, on multiple circuits where the manual says so, sized to the nameplate.
Wire Size for Appliances
Dryer, range, water heater, AC, and more: the circuit for each.
Wire Size Calculator
Size any load per NEC 310.16 with derating, then check voltage drop.
Standard Breaker Sizes
The NEC 240.6(A) standard OCPD ratings a heating circuit rounds up to.