NEC Article 424 (Fixed Electric Space Heating)
What Size Wire for an Electric Furnace?
An electric furnace is a large resistance heat load, sized to the nameplate. Here is the current by kilowatt, when it needs multiple circuits, and the calculator.
Size to the Nameplate, Expect Multiple Circuits
An electric furnace is resistance heat, so the amps are watts divided by the voltage, and NEC 424.4(B) sizes the branch-circuit conductors at not less than 125 percent of the heating load and any associated motor (the blower). The catch is scale: NEC 424.22(B) requires equipment rated more than 48 A to have its elements subdivided at 48 A or less each, protected at 60 A or less by supplementary devices in, on or supplied with the unit, energized in stages by an internal sequencer; the listing brings them out as separate field circuits or through a single-point connection. A listed furnace's nameplate prints a minimum circuit ampacity and a maximum overcurrent protection for each connection, and NEC 110.3(B) makes those binding. Wire each circuit to its own listed ampacity and breaker; the table below is the Article 424 arithmetic, not a substitute for the data plate.
Electric Furnace Current by Size (240V)
| Furnace Size | Load Amps | At 125% | Circuit |
|---|---|---|---|
| 10 kW | 41.7 A | 52.1 A | 1 x 60A, #6 AWG copper (60 °C or 75 °C) |
| 15 kW | 62.5 A | 78.1 A | Over 48 A: subdivided (see nameplate) |
| 20 kW | 83.3 A | 104.2 A | Over 48 A: subdivided (see nameplate) |
| 25 kW | 104.2 A | 130.2 A | Over 48 A: subdivided (see nameplate) |
The 125% column is the minimum ampacity a single circuit would need for the elements, before the blower. On a circuit of 100 A or less the 60 °C size applies unless the unit is listed and identified for 75 °C conductors (NEC 110.14(C)(1)(a); such a unit is marked for them, 424.11). Over 48 A of load the elements are subdivided (NEC 424.22(B)): a 20 kW unit (83.3 A, or 104.2 A at 125%) wired as two field circuits needs, for the elements alone, two 60A circuits with #6 AWG copper (60 °C or 75 °C); the blower's circuit can need more. The nameplate's per-circuit minimum circuit ampacity and maximum breaker are the figures to wire to (NEC 110.3(B)).
Size a Single Circuit
Enter the nameplate's minimum circuit ampacity and maximum breaker for one field circuit, or, for a unit marked only in volts and watts, the heat at the voltage it runs on and the blower's amps. It opens on a 10 kW element bank at 240 V. For a unit that splits its heat, size each field circuit from its own nameplate figures; the heat strip page has the same tool and the table at 208 V.
Frequently Asked Questions
What size wire do I need for an electric furnace?
Size it from the furnace's nameplate: a listed furnace prints a minimum circuit ampacity and maximum breaker for each field circuit, and NEC 110.3(B) makes them binding. For a unit marked only in volts and watts, NEC 424.4(B) sizes the branch-circuit conductors at not less than 125 percent of the heating load and any associated motor. A 10 kW / 240 V element bank draws 41.7 A, 52.1 A at 125%, which lands on a 60 A circuit with #6 AWG copper (60 °C or 75 °C), before the blower's amps are added. At 15 kW (62.5 A, 78.1 A at 125%) the equipment is over 48 A. Over 48 A of equipment load, NEC 424.22(B) has the unit's heating elements subdivided at 48 A or less each, protected at 60 A or less by supplementary devices in, on or supplied with the unit (424.22(C)). Whether the unit then takes one field circuit or several is its listing: wire what the plate prints (110.3(B)).
Why can an electric furnace have more than one circuit?
Because NEC 424.22(B) requires resistance heating equipment rated more than 48 A to have its elements subdivided, each subdivided load not over 48 A and protected at not more than 60 A. A 20 kW / 240 V furnace draws 83.3 A (104.2 A at 125%), so an internal sequencer energizes the subdivided elements in stages, and the listing brings them out either as separate field-connected circuits or through a single-point connection; the nameplate says which (where it is two circuits, for the heating elements alone, a 20 kW furnace split in two needs two 60A circuits, since each 41.7A half is 52.1A at 125%; the subcircuit that also runs the blower adds that motor's load under NEC 424.4(B), so its nameplate figure can be larger). Each field circuit gets its own breaker and conductor sized to that circuit's nameplate ampacity.
What size breaker for an electric furnace?
Never larger than the maximum overcurrent protection printed on the nameplate for that circuit (NEC 110.3(B)). For a unit marked only in volts and watts, the arithmetic for the elements alone is a 60 A breaker at 10 kW / 240 V and 80 A at 15 kW as a single figure, before the blower; at 15 kW the unit is over 48 A, so its elements are subdivided (424.22(B)) and the nameplate gives the figures for each field connection. On a heating circuit NEC 240.4(D) holds #10 copper to 30 A: Table 240.4(G), which relaxes that for air conditioners, has no Article 424 row.
Is the electric furnace blower included in the wire size?
It must be. NEC 424.4(B) sizes the branch-circuit conductors at not less than 125 percent of the heating load and any associated motor, so the blower motor's amps go inside the 125% on the circuit that runs it. On a listed furnace, the nameplate's minimum circuit ampacity for that circuit is the figure to size to (110.3(B)); for a motor over 1/8 hp the plate also states its rating in volts, amperes and frequency (424.28(A)).
Does an electric furnace need a disconnect?
Yes. NEC 424.19 requires a means that disconnects the heater, the motor controller and any supplementary overcurrent devices from all ungrounded conductors at once, rated at least 125 percent of the motor and heater load and capable of being locked open. Where the unit has factory element fuses or breakers (424.19(A)) that means is within sight of them; with a blower over 1/8 hp it may also serve the motor controller where it is in sight from both and complies with Part IX of Article 430, or it may be out of sight from the motor controller where the motor and heater have a single unit switch that complies with 422.34 (424.19(A)(2)). A branch breaker that is merely lockable is the disconnect only for equipment with no supplementary devices and no motor over 1/8 hp (424.19(B)(1)). A unit fed by more than one circuit has its disconnects grouped and identified.
Related
Heat Strip Wire Size
Air handler strip heat at 208 V and 240 V, the plate first.
Can My Panel Handle It?
Before you add this load, the NEC 220.87 check on whether the service can carry it.
Baseboard Heater Wire Size
The smaller electric-heat load: watts-per-circuit budget and by-wattage wire.
Tankless Water Heater Wire Size
Another large multi-circuit load sized to the nameplate.
Wire Size for Appliances
Dryer, range, water heater, AC, and more: the circuit for each.