Heat Pump Water Heater Circuit

Rheem Performance Platinum ProTerra Hybrid (Low-Amp, 15A): Breaker & Wire Size

The circuit the Rheem Performance Platinum ProTerra Hybrid (Low-Amp, 15A) needs, read from the manufacturer's own spec sheet, with the conductor and ground derived for the stated breaker.

Quick answer: the Rheem Performance Platinum ProTerra Hybrid (Low-Amp, 15A) takes a 15A breaker on a dedicated 240V circuit with #14 copper conductors and a #14 copper equipment ground. Its 2,250W element draws 9.38A at 240V; sized at 125% per NEC 422.13, 11.72A.

Circuit Spec

Circuit specification for the Rheem Performance Platinum ProTerra Hybrid (Low-Amp, 15A) (240V dedicated)

Swipe the table sideways to see the rest of its columns. →

Voltage208/240V (240V dedicated)
Circuitdedicated 240V circuit
Nameplate element wattage2,250 W
Nameplate amps9.38 A
Design amps at 125% (NEC 422.13)11.72 A
Manufacturer-required breaker15 A
Conductor for that breaker#14 Cu
Equipment ground#14 Cu
Load-sized circuit (code minimum)15A on #14 Cu

The breaker is the manufacturer-stated value; the conductor and ground derive from that breaker. Under NEC 422.11(A) the overcurrent device must not exceed the rating marked on the appliance, so the nameplate on your unit always governs.

Models & Capacities

Representative models in this line: XE40T10H22U1, XE50T10H22U1, XE65T10H22U1, XE80T10H22U1. Capacities: 40, 50, 65, 80 gallons. The circuit spec above applies across the line as published by Rheem; confirm against the rating plate on the specific unit.

A Dedicated 240V Circuit

Rheem states a dedicated 15A / 240V circuit for this line, on #14 copper with a #14 ground.

Source

Circuit data read from the manufacturer: Rheem Performance Platinum ProTerra Hybrid (Low-Amp, 15A) specification, accessed 2026-07-11.

The 'H22' low-amp Rheem hybrid uses a 2,250W element instead of 4,500W, so it fits a 15A / 240V circuit. It is built for a retrofit into an existing 15A run or a service too small for a 30A branch, at the cost of slower resistance-mode recovery.

The documents behind these figures, and the code sections this page cites, are named in the source receipt.


Frequently Asked Questions

What size breaker does the Rheem Performance Platinum ProTerra Hybrid (Low-Amp, 15A) need?

Rheem specifies a 15A breaker on a dedicated 240V circuit for this line (models XE40T10H22U1, XE50T10H22U1, XE65T10H22U1, XE80T10H22U1). Under NEC 422.11(A) the overcurrent device must not exceed the rating marked on the appliance, so the nameplate governs. The conductor for a 15A breaker is #14 copper with a #14 copper equipment ground.

How many amps does the Rheem Performance Platinum ProTerra Hybrid (Low-Amp, 15A) draw?

With its 2,250W element on, it draws 9.38A at 240V (amps = watts / volts). NEC 422.13 requires the breaker and conductors for a fixed storage water heater 120 gallons or less to be rated at not less than 125% of it: 11.72A design. In heat-pump mode the draw is far lower; the circuit is sized for the element.

Does the Rheem Performance Platinum ProTerra Hybrid (Low-Amp, 15A) need a dedicated circuit?

Yes. Rheem states a dedicated 15A / 240V circuit for this line. For comparison, a standard 4,500W resistance tank draws 18.75A at 240V, 23.44A at the 125% sizing of NEC 422.13.

What wire size for the Rheem Performance Platinum ProTerra Hybrid (Low-Amp, 15A)?

#14 copper conductors for the manufacturer-required 15A breaker, with a #14 copper equipment ground sized to the breaker per NEC Table 250.122. Sized from the load alone: 2,250W / 240V = 9.38A, x1.25 = 11.72A (NEC 422.13), which lands on a 15A code-minimum breaker with #14 copper. The manufacturer's marked maximum governs the installed breaker (NEC 422.11(A)).


Compute Your Unit's Exact Amps

Read the watts off the rating plate and enter them below to get the exact draw at 120V or 240V. The rating plate governs over any typical value.

Solve for

Current
9.38 A
Show the math

Amps = Watts / (Volts) = 2250 / (240) = 9.38 A

Power factor (PF) applies to AC motor and reactive loads: real power W = V x A x PF. For resistive loads (heaters, incandescent, most 120V appliances) PF is 1.0. This calculator converts single-phase; for reference, three-phase uses W = V x A x PF x 1.732.