Heat Pump Water Heater Circuit

GE Profile GeoSpring 240V (FlexCapacity): Breaker & Wire Size

The circuit the GE Profile GeoSpring 240V (FlexCapacity) needs, read from the manufacturer's own spec sheet, with the conductor and ground derived for the stated breaker.

Quick answer: the GE Profile GeoSpring 240V (FlexCapacity) takes a 30A breaker on a dedicated 240V circuit with #10 copper conductors and a #10 copper equipment ground. The manufacturer does not print an element wattage for this line; the stated 30A breaker governs (NEC 422.11(A)).

Circuit Spec

Circuit specification for the GE Profile GeoSpring 240V (FlexCapacity) (240V dedicated)

Swipe the table sideways to see the rest of its columns. →

Voltage240V (240V dedicated)
Circuitdedicated 240V circuit
Nameplate element wattageNot printed by the manufacturer
Nameplate ampsNot derived (no printed wattage)
Manufacturer-required breaker30 A
Conductor for that breaker#10 Cu
Equipment ground#10 Cu

The breaker is the manufacturer-stated value; the conductor and ground derive from that breaker. Under NEC 422.11(A) the overcurrent device must not exceed the rating marked on the appliance, so the nameplate on your unit always governs.

Models & Capacities

Representative models in this line: PH50S10BNY, PH50S10BPY. Capacities: 50 gallons. The circuit spec above applies across the line as published by GE Profile; confirm against the rating plate on the specific unit.

A Dedicated 240V Circuit

GE Profile states a dedicated 30A / 240V circuit for this line, on #10 copper with a #10 ground.

Source

Circuit data read from the manufacturer: GE Profile GeoSpring 240V (FlexCapacity) specification, accessed 2026-08-12.

GE Profile's 240V GeoSpring takes a 30A / 240V dedicated circuit and, being FlexCapacity, can also be reconfigured to run as a 120V, 15A shared plug-in. GE does not print an element wattage, so the 30A dedicated circuit follows the manufacturer's stated breaker, not a derived load.

The documents behind these figures, and the code sections this page cites, are named in the source receipt.


Frequently Asked Questions

What size breaker does the GE Profile GeoSpring 240V (FlexCapacity) need?

GE Profile specifies a 30A breaker on a dedicated 240V circuit for this line (models PH50S10BNY, PH50S10BPY). Under NEC 422.11(A) the overcurrent device must not exceed the rating marked on the appliance, so the nameplate governs. The conductor for a 30A breaker is #10 copper with a #10 copper equipment ground.

How many amps does the GE Profile GeoSpring 240V (FlexCapacity) draw?

GE Profile does not print a wattage for this line, so no amp figure is derived here. The manufacturer-stated 30A breaker governs the circuit (NEC 422.11(A)); read the rating plate on the unit for its exact draw.

Does the GE Profile GeoSpring 240V (FlexCapacity) need a dedicated circuit?

Yes. GE Profile states a dedicated 30A / 240V circuit for this line. For comparison, a standard 4,500W resistance tank draws 18.75A at 240V, 23.44A at the 125% sizing of NEC 422.13.

What wire size for the GE Profile GeoSpring 240V (FlexCapacity)?

#10 copper conductors for the manufacturer-required 30A breaker, with a #10 copper equipment ground sized to the breaker per NEC Table 250.122.


Compute Your Unit's Exact Amps

Read the watts off the rating plate and enter them below to get the exact draw at 120V or 240V. The rating plate governs over any typical value. GE Profile prints no wattage for this line, so the calculator below opens on a 1,500 W example, not this unit: enter your rating plate's watts.

Solve for

Current
12.5 A
Show the math

Amps = Watts / (Volts) = 1500 / (120) = 12.5 A

Power factor (PF) applies to AC motor and reactive loads: real power W = V x A x PF. For resistive loads (heaters, incandescent, most 120V appliances) PF is 1.0. This calculator converts single-phase; for reference, three-phase uses W = V x A x PF x 1.732.