Heat Pump Water Heater Circuit

Rheem ProTerra Plug-in Heat Pump (Dedicated Circuit): Breaker & Wire Size

The circuit the Rheem ProTerra Plug-in Heat Pump (Dedicated Circuit) needs, read from the manufacturer's own spec sheet, with the conductor and ground derived for the stated breaker.

Quick answer: the Rheem ProTerra Plug-in Heat Pump (Dedicated Circuit) takes a 15A breaker on a dedicated 120V circuit with #14 copper conductors and a #14 copper equipment ground. Needs a dedicated circuit: The manufacturer requires a dedicated circuit for this unit (NEC 110.3(B)), whatever its draw against NEC 210.23(B)(2)'s 7.5 A shared-circuit ceiling (15 A x 50% = 7.5 A).

Circuit Spec

Circuit specification for the Rheem ProTerra Plug-in Heat Pump (Dedicated Circuit) (120V plug-in)

Swipe the table sideways to see the rest of its columns. →

Voltage120V (120V plug-in)
Circuitdedicated 120V circuit
Nameplate element wattageNot printed by the manufacturer
Nameplate ampsNot derived (no printed wattage)
Manufacturer-required breaker15 A
Conductor for that breaker#14 Cu
Equipment ground#14 Cu

The breaker is the manufacturer-stated value; the conductor and ground derive from that breaker. Under NEC 422.11(A) the overcurrent device must not exceed the rating marked on the appliance, so the nameplate on your unit always governs.

Models & Capacities

Representative models in this line: PROPH40 T0 RH120, PROPH50 T0 RH120. Capacities: 40, 50 gallons. The circuit spec above applies across the line as published by Rheem; confirm against the rating plate on the specific unit.

Can It Share a Circuit?

Needs a dedicated circuit. The manufacturer requires a dedicated circuit for this unit (NEC 110.3(B)), whatever its draw against NEC 210.23(B)(2)'s 7.5 A shared-circuit ceiling (15 A x 50% = 7.5 A).

NEC 210.23(B)(2) caps the total rating of equipment fastened in place at 50% of a 15A or 20A multi-outlet circuit: 7.5A on a 15A circuit, the code's ceiling. This tool keeps a margin under it, 6A on a 15A circuit, by counting the heater at the 125% NEC 422.13 sets for its breaker and conductors. A listed unit may be cord-and-plug connected under NEC 422.16(A). This shared-circuit question applies only to the 120V plug-in class.

It needs its own dedicated circuit. Can your panel take it?

The Rheem ProTerra Plug-in Heat Pump (Dedicated Circuit) cannot share a general-purpose circuit, so this is a new dedicated circuit on the panel. Before you add it, check that the service has the room and spare capacity for another load.

Source

Circuit data read from the manufacturer: Rheem ProTerra Plug-in Heat Pump (Dedicated Circuit) specification, accessed 2026-07-11.

Rheem's 120V plug-in DEDICATED model plugs into a standard 120V outlet (NEMA 5-15P) but the manufacturer requires that outlet to be on its OWN 15A circuit. It has no large resistance backup element, which is how a 120V unit works at all; recovery is slower than a 240V hybrid. GFCI: plugged into a receptacle in a dwelling location NEC 2023 210.8(A) lists (210.8(A)(2) "Garages and also accessory buildings that have a floor located at or below grade level not intended as habitable rooms and limited to storage areas, work areas, and areas of similar use", 210.8(A)(5) "Basements"), a 120V plug-in heat pump water heater needs GFCI protection; 210.8(A) reaches 125-volt through 250-volt receptacles supplied by single-phase branch circuits rated 150 volts or less to ground. Which edition applies is the one your jurisdiction has adopted.

The documents behind these figures, and the code sections this page cites, are named in the source receipt.


Frequently Asked Questions

What size breaker does the Rheem ProTerra Plug-in Heat Pump (Dedicated Circuit) need?

Rheem specifies a 15A breaker on a dedicated 120V circuit for this line (models PROPH40 T0 RH120, PROPH50 T0 RH120). Under NEC 422.11(A) the overcurrent device must not exceed the rating marked on the appliance, so the nameplate governs. The conductor for a 15A breaker is #14 copper with a #14 copper equipment ground. GFCI: plugged into a receptacle in a dwelling location NEC 2023 210.8(A) lists (210.8(A)(2) "Garages and also accessory buildings that have a floor located at or below grade level not intended as habitable rooms and limited to storage areas, work areas, and areas of similar use", 210.8(A)(5) "Basements"), a 120V plug-in heat pump water heater needs GFCI protection; 210.8(A) reaches 125-volt through 250-volt receptacles supplied by single-phase branch circuits rated 150 volts or less to ground. Which edition applies is the one your jurisdiction has adopted.

How many amps does the Rheem ProTerra Plug-in Heat Pump (Dedicated Circuit) draw?

Rheem does not print a wattage for this line, so no amp figure is derived here. The manufacturer-stated 15A breaker governs the circuit (NEC 422.11(A)); read the rating plate on the unit for its exact draw.

Can the Rheem ProTerra Plug-in Heat Pump (Dedicated Circuit) share a circuit?

Needs a dedicated circuit. The manufacturer requires a dedicated circuit for this unit (NEC 110.3(B)), whatever its draw against NEC 210.23(B)(2)'s 7.5 A shared-circuit ceiling (15 A x 50% = 7.5 A). The rule: NEC 210.23(B)(2) (the total rating of equipment fastened in place, 50% of the circuit); this tool's margin also counts the heater at the 125% NEC 422.13 sets for its breaker and conductors. A listed unit may be cord-and-plug connected under NEC 422.16(A).

What wire size for the Rheem ProTerra Plug-in Heat Pump (Dedicated Circuit)?

#14 copper conductors for the manufacturer-required 15A breaker, with a #14 copper equipment ground sized to the breaker per NEC Table 250.122.


Compute Your Unit's Exact Amps

Read the watts off the rating plate and enter them below to get the exact draw at 120V or 240V. The rating plate governs over any typical value. Rheem prints no wattage for this line, so the calculator below opens on a 1,500 W example, not this unit: enter your rating plate's watts.

Solve for

Current
12.5 A
Show the math

Amps = Watts / (Volts) = 1500 / (120) = 12.5 A

Power factor (PF) applies to AC motor and reactive loads: real power W = V x A x PF. For resistive loads (heaters, incandescent, most 120V appliances) PF is 1.0. This calculator converts single-phase; for reference, three-phase uses W = V x A x PF x 1.732.

Common conversions


Other Heat Pump Water Heater Circuits

Related Tools