Heat Pump Water Heater Circuit

A.O. Smith Voltex Hybrid (HPTU, prior generation): Breaker & Wire Size

The circuit the A.O. Smith Voltex Hybrid (HPTU, prior generation) needs, read from the manufacturer's own spec sheet, with the conductor and ground derived for the stated breaker.

Quick answer: the A.O. Smith Voltex Hybrid (HPTU, prior generation) takes a 30A breaker on a dedicated 240V circuit with #10 copper conductors and a #10 copper equipment ground. Its 4,500W element draws 18.75A at 240V; sized at 125% per NEC 422.13, 23.44A.

Circuit Spec

Circuit specification for the A.O. Smith Voltex Hybrid (HPTU, prior generation) (240V dedicated)

Swipe the table sideways to see the rest of its columns. →

Voltage208/240V (240V dedicated)
Circuitdedicated 240V circuit
Nameplate element wattage4,500 W
Nameplate amps18.75 A
Design amps at 125% (NEC 422.13)23.44 A
Manufacturer-required breaker30 A
Conductor for that breaker#10 Cu
Equipment ground#10 Cu
Load-sized circuit (code minimum)25A on #10 Cu

The breaker is the manufacturer-stated value; the conductor and ground derive from that breaker. Under NEC 422.11(A) the overcurrent device must not exceed the rating marked on the appliance, so the nameplate on your unit always governs.

Models & Capacities

Representative models in this line: HPTU-50N, HPTU-66N, HPTU-80N. Capacities: 50, 66, 80 gallons. The circuit spec above applies across the line as published by A.O. Smith; confirm against the rating plate on the specific unit.

A Dedicated Circuit, Wired Like a Standard Tank

A.O. Smith states a dedicated 30A / 240V circuit for this line, on #10 copper with a #10 ground. It uses the same 4,500W backup element as a standard 4,500W / 240V electric resistance tank, which draws 18.75A (23.44A at the 125% sizing of NEC 422.13) on the same 30A / #10 circuit (25A is the NEC code minimum), so it wires identically to the tank it typically replaces.

Source

Circuit data read from the manufacturer: A.O. Smith Voltex Hybrid (HPTU, prior generation) specification, accessed 2026-07-11.

The prior-generation A.O. Smith Voltex (HPTU) uses dual 4,500W elements (4,500W of connected load) and is 208/240V dual-voltage, as the A.O. Smith service handbook prints it; it requires a 30-amp breaker, so it takes the standard 30A / 240V circuit on 10 AWG copper. Note: some listings claim the HPTU-66N is a '120V, 29A' unit; the A.O. Smith documents show 208/240V and a 30A breaker, so that figure is incorrect.

The documents behind these figures, and the code sections this page cites, are named in the source receipt.


Frequently Asked Questions

What size breaker does the A.O. Smith Voltex Hybrid (HPTU, prior generation) need?

A.O. Smith specifies a 30A breaker on a dedicated 240V circuit for this line (models HPTU-50N, HPTU-66N, HPTU-80N). Under NEC 422.11(A) the overcurrent device must not exceed the rating marked on the appliance, so the nameplate governs. The conductor for a 30A breaker is #10 copper with a #10 copper equipment ground.

How many amps does the A.O. Smith Voltex Hybrid (HPTU, prior generation) draw?

With its 4,500W element on, it draws 18.75A at 240V (amps = watts / volts). NEC 422.13 requires the breaker and conductors for a fixed storage water heater 120 gallons or less to be rated at not less than 125% of it: 23.44A design. In heat-pump mode the draw is far lower; the circuit is sized for the element.

Does the A.O. Smith Voltex Hybrid (HPTU, prior generation) need a dedicated circuit?

Yes. A.O. Smith states a dedicated 30A / 240V circuit for this line. For comparison, a standard 4,500W resistance tank draws 18.75A at 240V, 23.44A at the 125% sizing of NEC 422.13.

What wire size for the A.O. Smith Voltex Hybrid (HPTU, prior generation)?

#10 copper conductors for the manufacturer-required 30A breaker, with a #10 copper equipment ground sized to the breaker per NEC Table 250.122. Sized from the load alone: 4,500W / 240V = 18.75A, x1.25 = 23.44A (NEC 422.13), which lands on a 25A code-minimum breaker with #10 copper. The manufacturer's marked maximum governs the installed breaker (NEC 422.11(A)).


Compute Your Unit's Exact Amps

Read the watts off the rating plate and enter them below to get the exact draw at 120V or 240V. The rating plate governs over any typical value.

Solve for

Current
18.75 A
Show the math

Amps = Watts / (Volts) = 4500 / (240) = 18.75 A

Power factor (PF) applies to AC motor and reactive loads: real power W = V x A x PF. For resistive loads (heaters, incandescent, most 120V appliances) PF is 1.0. This calculator converts single-phase; for reference, three-phase uses W = V x A x PF x 1.732.

Common conversions


Other Heat Pump Water Heater Circuits

Related Tools