HVAC · Air side
Duct Size Calculator
The round and rectangular duct size, velocity and friction loss for an airflow at a friction rate, by the equal-friction method (ACCA Manual D). Every size is computed from the Darcy-Colebrook duct model, never looked up from a hand-typed grid.
Round Duct Size by CFM (0.08 in. wc/100 ft)
| Airflow (CFM) | Round size | Velocity (fpm) | Friction (in. wc/100 ft) |
|---|---|---|---|
| 50 | 5 in | 367 | 0.058 |
| 75 | 6 in | 382 | 0.050 |
| 100 | 7 in | 374 | 0.039 |
| 150 | 8 in | 430 | 0.043 |
| 200 | 8 in | 573 | 0.072 |
| 300 | 10 in | 550 | 0.051 |
| 400 | 11 in | 606 | 0.054 |
| 600 | 12 in | 764 | 0.074 |
| 800 | 14 in | 748 | 0.059 |
| 1,000 | 15 in | 815 | 0.063 |
| 1,200 | 16 in | 859 | 0.064 |
| 1,600 | 18 in | 905 | 0.061 |
| 2,000 | 20 in | 917 | 0.055 |
Each row is the smallest standard round size whose friction loss stays at or under 0.08 in. wc per 100 ft at that airflow, with the velocity it runs at. Sizes are galvanized steel in standard air. For rectangular duct, match the equivalent diameter with the calculator above.
The equal-friction formula
Friction loss per 100 ft = (12 × f × L / D) × ρ × (V / 1097)², where f is the Colebrook-White friction factor at galvanized absolute roughness ε = 0.0003 ft, D is the diameter in inches, ρ is standard air density 0.075 lb/ft³, and V is velocity in fpm (ASHRAE Fundamentals duct-friction chart). Velocity V = CFM / cross-sectional area. Rectangular to round: De = 1.30 × (a × b)0.625 / (a + b)0.25 (ASHRAE Fundamentals 21.3.1). The sizer steps up standard sizes until the friction loss meets your target.
Duct Size Calculator FAQs
What size duct do I need for 400 CFM?
A 11 in round duct carries 400 CFM at the common 0.08 in. wc per 100 ft friction rate (galvanized, standard air). That is roughly one ton of cooling airflow at 400 CFM per ton. At a looser 0.10 in. wc/100 ft you can drop a size; a rectangular duct with the same equivalent diameter carries the same airflow at the same friction.
What size duct for 800 CFM?
An 14 in round duct carries 800 CFM at 0.08 in. wc per 100 ft. Returns and trunks are often run a size larger to keep velocity and noise down. Use the calculator to see the exact velocity and to read off rectangular equivalents for a tight joist bay.
How do I calculate duct size from CFM?
Duct size comes from the equal-friction method: pick a friction rate (0.08 in. wc per 100 ft is the residential default), then find the smallest standard duct whose friction loss at your CFM stays at or under that rate. Friction loss is (12 f L / D) x density x (velocity/1097) squared, with the friction factor f from the Colebrook-White equation at galvanized roughness 0.0003 ft. This calculator solves it for you and gives the round size, the velocity, and the rectangular equivalent.
What is a good friction rate for residential duct design?
0.08 in. wc per 100 ft is the standard residential design target, and ACCA Manual D Appendix 3 tables are built on it. The usable range is about 0.06 to 0.10 in. wc per 100 ft: lower means larger, quieter ducts, higher means smaller ducts and more noise. Your actual friction rate is available static pressure times 100 divided by total effective length.
What CFM does a 6 inch round duct carry?
A 6 in round duct carries roughly 90 CFM at 0.08 in. wc per 100 ft before it needs to step up to 7 in. Push more air through it and the velocity and friction climb past the residential target, which is where duct noise starts. The chart on this page lists each round size against the airflow it carries.
Is round or rectangular duct better, and how do I convert between them?
Round duct moves air with less friction and material for the same airflow, but rectangular fits flat in joist bays and above ceilings. To convert, match the equivalent diameter: De = 1.30 times (a times b) to the 0.625 power, divided by (a plus b) to the 0.25 power (ASHRAE Fundamentals 21.3.1). The calculator prints the rectangular sizes whose equivalent diameter matches the round size it recommends.
Convert a shape, or jump to a common size
Have a size already and need the other shape? The round-to-rectangular converter matches equivalent diameters both ways. Or open the reference page for a common airflow or duct size:
What size duct for 400 CFM?
400 CFM needs a 11 in round at 0.08 in. wc/100 ft.
What size duct for 600 CFM?
600 CFM needs a 12 in round at 0.08 in. wc/100 ft.
What size duct for 800 CFM?
800 CFM needs a 14 in round at 0.08 in. wc/100 ft.
What size duct for 1000 CFM?
1000 CFM needs a 15 in round at 0.08 in. wc/100 ft.
What size duct for 1200 CFM?
1200 CFM needs a 16 in round at 0.08 in. wc/100 ft.
6 inch duct CFM
A 6 in round carries about 98 CFM at 0.08 in. wc/100 ft.
8 inch duct CFM
A 8 in round carries about 212 CFM at 0.08 in. wc/100 ft.
10 inch duct CFM
A 10 in round carries about 386 CFM at 0.08 in. wc/100 ft.
12 inch duct CFM
A 12 in round carries about 628 CFM at 0.08 in. wc/100 ft.
Related HVAC Tools
CFM Calculator
Airflow from the load: CFM = sensible BTU / (1.08 × ΔT), or 400 CFM per ton. Feeds this sizer.
Static Pressure & Friction Rate
Turn available static pressure and total effective length into the friction rate this tool needs.
BTU / Load Calculator
Size the equipment first, then the airflow, then the duct. The start of the air-side job.