HVAC · Air side
CFM Calculator
The airflow a system needs, from nominal tonnage (400 CFM per ton) or from the sensible load (CFM = sensible BTU / (1.08 × ΔT)). The result feeds the duct size calculator.
400 CFM/ton is the nominal comfort rule; 350 for hot, humid climates (more dehumidification), 450 for dry climates (more sensible cooling). Confirm against OEM blower data (ACCA).
Show the math
CFM = tons × CFM/ton = 3 × 400 = 1,200
Where this number comes fromIntry Verified
- Calculated from
- Sensible-heat equation (1.08 x CFM x dT) or 400 CFM per ton (ACCA). Computed from the standard-air 1.08 sensible-heat constant (60 x 0.075 x 0.24; a secondary, HVAC School, states its basis) or the ACCA 400 CFM-per-ton rule, at standard air. See the full receipt ↓
- Run with
- Basis3 ton x 400 CFM/ton
- Required airflow1,200 CFM
- Checked
- Every figure an Intry calculator computes comes from a locked source module, not hand-typed. 31163 automated checks, one suite for the whole site rather than a per-tool count, re-derive the numbers before each deploy from the tables this site transcribed from the ASHRAE and ACCA airflow standards it was computed from. This is our own deterministic gate, not a third-party audit.
- Final say
- The OEM blower table for the actual coil, or a full ACCA Manual J/D design, has final say.
Intry Verified · Build 2731D30 · 2026-10-15
The airflow formulas
From tonnage: CFM = tons × CFM-per-ton, with 400 CFM per ton nominal (ACCA; band 350 to 450). From sensible load: CFM = sensible BTU / (1.08 × ΔT). The 1.08 = 60 min/h × 0.075 lb/ft³ × 0.24 BTU/lb°F is the standard-air sensible-heat constant, so both assume air at 70°F and sea level. Latent load uses a separate constant and is not included here.
CFM Calculator FAQs
How many CFM for a 3 ton unit?
A 3-ton system needs about 1200 CFM at the nominal 400 CFM per ton (3 x 400). Hot, humid climates run closer to 350 CFM/ton (1050 CFM) for more dehumidification; dry climates run up to 450 CFM/ton (1350 CFM) for more sensible cooling. Confirm against the OEM blower table for the actual coil.
How many CFM for a 2 ton unit?
A 2-ton system needs about 800 CFM at 400 CFM per ton. The 350-450 CFM/ton band puts it between 700 and 900 CFM depending on climate and how the system is set up for latent versus sensible load.
How do I calculate CFM from BTU?
For the SENSIBLE portion of the load, CFM = sensible BTU / (1.08 x deltaT), where deltaT is the supply-to-room temperature difference. For 24,000 BTU sensible at a 20F deltaT that is 1111 CFM. The 1.08 constant is 60 min/h x 0.075 lb/ft3 standard-air density x 0.24 BTU/lb-F specific heat, so it assumes standard air at 70F and sea level.
What is the 1.08 constant in the CFM formula?
1.08 is 60 x 0.075 x 0.24: 60 minutes per hour, times the density of standard air (0.075 lb/ft3 at 70F, sea level), times the specific heat of air (0.24 BTU/lb-F). It converts a sensible BTU/hr load and a temperature difference into the airflow in CFM. At altitude or high supply temperatures the air is thinner, so the real constant is lower and the required CFM is higher.
Is 400 CFM per ton always right?
No. 400 CFM per ton is a nominal comfort starting point, not a law. ACCA gives a 350 to 450 CFM per ton band: 350 for hot, humid climates that need more moisture removal, 450 for dry climates that want more sensible cooling. The OEM blower performance table for the specific air handler is the authority; this calculator sizes the airflow, then feed it into the duct size calculator.
Next in the air-side job
Duct Size Calculator
Turn this CFM into a round or rectangular duct size by the equal-friction method.
Static Pressure & Friction Rate
Get the friction rate the duct sizer needs from your available static pressure and TEL.
BTU / Load Calculator
Size the cooling load first, then the airflow, then the duct.