Appliance Amperage

How Many Amps Does a Washing Machine Use?

The running amps a washing machine draws, the watts-to-amps math behind it, and the branch circuit it belongs on.

Quick answer: Frigidaire's specification sheet for the FFTW1001PW 3.4 cu. ft. top load washer lists Amps @ 120 Volts "8.0" (8.0 amps), Connected Load (kW Rating) @ 120 Volts "0.4" and Voltage Rating "120V/60Hz/15A": 8 amps at 120V, the current its maker prints. The motor briefly surges higher at startup. It belongs on a dedicated 20A / 120V circuit. Frigidaire's FFTW1001PW sheet lists Minimum Circuit Required (Amps) "15" and notes "For use on adequately wired 120V, dedicated circuit having 2-wire service with a separate ground wire." Where its nameplate prints amps, those govern; watts ÷ volts is the current only of a heating element.

Will a washing machine Run on Your Circuit?


Washing Machine Circuit

Figures for the Frigidaire FFTW1001PW and the circuit shown for a washing machine (NEC 210.11(C)(2), 210.8(A))

Swipe the table sideways to see the rest of its columns. →

Watts (Frigidaire FFTW1001PW)400 W
Voltage120V
Running amps8 A
Startup surgeYes (motor)
Circuit20A / 120V dedicated

Frigidaire lists its FFTW1001PW top load washer at 8.0 amps at 120 volts with a connected load of 0.4 kW (the motor surges higher on spin-up), and the NEC requires the laundry area to have its own dedicated 20A circuit (210.11(C)(2)). A gas or electric dryer is a separate circuit; the washer does not share with it. GFCI: plugged into a receptacle in a dwelling location NEC 2023 210.8(A) lists (210.8(A)(11) "Laundry areas"), a washing machine needs GFCI protection; 210.8(A) reaches 125-volt through 250-volt receptacles supplied by single-phase branch circuits rated 150 volts or less to ground. Which edition applies is the one your jurisdiction has adopted. The amps here are the current the Frigidaire FFTW1001PW's maker prints; your own unit's nameplate amps are its current; a continuous load (3 hours or more) may use at most 80% of the breaker, the same rule as rating the breaker at 125% of it (NEC 210.20(A)). The nameplate lists the exact draw and governs over the figure on this page.

Source: Frigidaire Top Load Washer FFTW1001PW, 3.4 Cu. Ft. D.O.E., specification sheet (FFTW1001P 10/13), read 2026-11-13.

Adding this on a new circuit? Check whether your panel can handle it (the NEC 220.87 service check), or size the breaker for the load.


Convert Watts to Amps

Watts divided by volts is the current only of a heating element, so for a washing machine the converter below gives a rough figure, not its current. The amps its nameplate prints are its current; where it prints only watts, the maker's documentation or a measured current gives the amps. The power factor field changes the conversion only where you know the unit's power factor.

The code sections this page cites are named in the source receipt.


Frequently Asked Questions

How many amps does a washing machine use?

Frigidaire's specification sheet for the FFTW1001PW 3.4 cu. ft. top load washer lists Amps @ 120 Volts "8.0" (8.0 amps), Connected Load (kW Rating) @ 120 Volts "0.4" and Voltage Rating "120V/60Hz/15A". That is 8 amps at 120 volts, the current its maker prints. Because it is a motor load, it surges to several times that for a moment at startup. For your unit's own draw, read the amperes on its nameplate where it prints them: watts divided by volts is the current only of a heating element. Frigidaire lists its FFTW1001PW top load washer at 8.0 amps at 120 volts with a connected load of 0.4 kW (the motor surges higher on spin-up), and the NEC requires the laundry area to have its own dedicated 20A circuit (210.11(C)(2)). A gas or electric dryer is a separate circuit; the washer does not share with it. GFCI: plugged into a receptacle in a dwelling location NEC 2023 210.8(A) lists (210.8(A)(11) "Laundry areas"), a washing machine needs GFCI protection; 210.8(A) reaches 125-volt through 250-volt receptacles supplied by single-phase branch circuits rated 150 volts or less to ground. Which edition applies is the one your jurisdiction has adopted.

What size breaker for a washing machine?

A washing machine belongs on a dedicated 20A / 120V circuit (NEC 210.11(C)(2), 210.8(A)). On a circuit of its own that ends in a single receptacle it may supply any load within the circuit's rating (NEC 210.22); where that circuit ends in a duplex receptacle, which is two receptacles, NEC 210.23(B)(1) holds cord-and-plug equipment not fastened in place to 80 percent of the circuit, 16A on that 20A circuit, and Table 210.21(B)(2) holds a receptacle's load to 16A on a 20A receptacle or 12A on a 15A one. Each is checked against the amperes its nameplate prints; the 8 amps is the current the Frigidaire FFTW1001PW's maker prints. Frigidaire's FFTW1001PW sheet lists Minimum Circuit Required (Amps) "15" and notes "For use on adequately wired 120V, dedicated circuit having 2-wire service with a separate ground wire." Do not put it on a shared circuit with other large loads.

How do I calculate the amps a washing machine draws?

Read the amperes printed on its nameplate. Watts divided by volts is the current only of a heating element with no motor, fan, pump, compressor or electronics, so for a washing machine the nameplate amps are the figure to use. The figure on this page, 8 amps, is the current the Frigidaire FFTW1001PW's maker prints; your own unit's nameplate prints its own. Add a startup surge of several times that for a fraction of a second on the motor. Your appliance's nameplate governs over the figure on this page.

How many amps does a washer use?

Same answer: washer is another name for a washing machine. It draws 8 amps at 120V, the current the Frigidaire FFTW1001PW's maker prints,on a dedicated 20A / 120V circuit. Frigidaire lists its FFTW1001PW top load washer at 8.0 amps at 120 volts with a connected load of 0.4 kW (the motor surges higher on spin-up), and the NEC requires the laundry area to have its own dedicated 20A circuit (210.11(C)(2)). A gas or electric dryer is a separate circuit; the washer does not share with it. GFCI: plugged into a receptacle in a dwelling location NEC 2023 210.8(A) lists (210.8(A)(11) "Laundry areas"), a washing machine needs GFCI protection; 210.8(A) reaches 125-volt through 250-volt receptacles supplied by single-phase branch circuits rated 150 volts or less to ground. Which edition applies is the one your jurisdiction has adopted.


How Many Amps Do Other Appliances Use?