Appliance Amperage
How Many Amps Does a Mini Fridge Use?
The running amps a mini fridge draws, the watts-to-amps math behind it, and the branch circuit it belongs on.
Will a mini fridge Run on Your Circuit?
Mini Fridge Circuit
Figures for the Danby DCR033B2WM and the circuit shown for a mini fridge (NEC 210.23(B))
Swipe the table sideways to see the rest of its columns. →
| Watts (Danby DCR033B2WM) | 110 W |
| Voltage | 115V |
| Running amps | 1.3 A |
| Startup surge | Yes (motor) |
| Circuit | Shared 15A or 20A / 120V |
Danby lists its DCR033B2WM 3.2 cu. ft. compact refrigerator at 1.3 amps and 110 watts on 115 volts, with a small compressor surge at startup, so it shares a normal 15A or 20A circuit. Avoid a long, thin extension cord: the startup surge on undersized cord is what causes trouble, not the running load. GFCI: plugged into a receptacle in a dwelling location NEC 2023 210.8(A) lists (210.8(A)(6) "Kitchens"), a mini fridge needs GFCI protection; 210.8(A) reaches 125-volt through 250-volt receptacles supplied by single-phase branch circuits rated 150 volts or less to ground. Which edition applies is the one your jurisdiction has adopted. The amps here are the current the Danby DCR033B2WM's maker prints; your own unit's nameplate amps are its current; a continuous load (3 hours or more) may use at most 80% of the breaker, the same rule as rating the breaker at 125% of it (NEC 210.20(A)). The nameplate lists the exact draw and governs over the figure on this page.
Source: Danby DCR033B2WM, Diplomat 3.2 cu. ft. Compact Refrigerator in White, specification sheet, read 2026-11-13.
Convert Watts to Amps
Watts divided by volts is the current only of a heating element, so for a mini fridge the converter below gives a rough figure, not its current. The amps its nameplate prints are its current; where it prints only watts, the maker's documentation or a measured current gives the amps. The power factor field changes the conversion only where you know the unit's power factor.
The code sections this page cites are named in the source receipt.
Frequently Asked Questions
How many amps does a mini fridge use?
Danby's specification sheet for the DCR033B2WM Diplomat 3.2 cu. ft. compact refrigerator lists Voltage "115 V", Amperage "1.3 A" and Wattage "110 W". That is 1.3 amps at 115 volts, the current its maker prints. Because it is a motor load, it surges to several times that for a moment at startup. For your unit's own draw, read the amperes on its nameplate where it prints them: watts divided by volts is the current only of a heating element. Danby lists its DCR033B2WM 3.2 cu. ft. compact refrigerator at 1.3 amps and 110 watts on 115 volts, with a small compressor surge at startup, so it shares a normal 15A or 20A circuit. Avoid a long, thin extension cord: the startup surge on undersized cord is what causes trouble, not the running load. GFCI: plugged into a receptacle in a dwelling location NEC 2023 210.8(A) lists (210.8(A)(6) "Kitchens"), a mini fridge needs GFCI protection; 210.8(A) reaches 125-volt through 250-volt receptacles supplied by single-phase branch circuits rated 150 volts or less to ground. Which edition applies is the one your jurisdiction has adopted.
What size breaker for a mini fridge?
A mini fridge does not need its own breaker; at 1.3 amps it rides a shared 15A or 20A / 120V circuit (NEC 210.23(B)). Just avoid running it at the same moment as another heavy load on the same circuit. Keep the total continuous load under 80% of the breaker.
How do I calculate the amps a mini fridge draws?
Read the amperes printed on its nameplate. Watts divided by volts is the current only of a heating element with no motor, fan, pump, compressor or electronics, so for a mini fridge the nameplate amps are the figure to use. The figure on this page, 1.3 amps, is the current the Danby DCR033B2WM's maker prints; your own unit's nameplate prints its own. Add a startup surge of several times that for a fraction of a second on the motor. Your appliance's nameplate governs over the figure on this page.
How many amps does a compact refrigerator use?
Same answer: compact refrigerator is another name for a mini fridge. It draws 1.3 amps at 115V, the current the Danby DCR033B2WM's maker prints,on a shared 15A or 20A / 120V circuit. Danby lists its DCR033B2WM 3.2 cu. ft. compact refrigerator at 1.3 amps and 110 watts on 115 volts, with a small compressor surge at startup, so it shares a normal 15A or 20A circuit. Avoid a long, thin extension cord: the startup surge on undersized cord is what causes trouble, not the running load. GFCI: plugged into a receptacle in a dwelling location NEC 2023 210.8(A) lists (210.8(A)(6) "Kitchens"), a mini fridge needs GFCI protection; 210.8(A) reaches 125-volt through 250-volt receptacles supplied by single-phase branch circuits rated 150 volts or less to ground. Which edition applies is the one your jurisdiction has adopted.
How Many Amps Do Other Appliances Use?
TV
0.9 A at 120V for the Samsung 55-inch Q60R.
Refrigerator
2.6 A at 120V for the GE GNE27JYMFS.
Freezer
5 A at 120V for the Frigidaire FFFC07M4N.
Microwave
12.4 A at 120V for the Panasonic NN-SN67KS.
Coffee Maker
8.8 A at 120V for the Hamilton Beach FlexBrew 49968.
Window Air Conditioner
10.3 A at 115V for the Frigidaire FFRE123ZA1.
Space Heater
12.5 A at 120V for the Lasko 758000.
Washing Machine
8 A at 120V for the Frigidaire FFTW1001PW.
Dishwasher
12 A at 120V for the Bosch SHE3AEM6N.
Garbage Disposal
6.3 A at 120V for the InSinkErator Badger 5.
Dehumidifier
8.5 A at 115V for the Frigidaire FFAD5034W1.
Sump Pump
5.2 A at 115V for the Liberty 250.
Hair Dryer
15.6 A at 120V for the Conair 303 Mid-Size Dryer.
Toaster
8.3 A at 120V for the Hamilton Beach PerfectToast 22408.
Electric Water Heater
18.8 A at 240V for a Rheem Performance tank.
Box Fan
0.94 A at 120V for the Air King 9723.
Air Fryer
12.9 A at 120V for the Ninja AF101.
Vacuum Cleaner
10 A at 120V for the Shark NV360.
PS5
1.8 A at 120V for the PS5 CFI-21 (disc drive attached).
Xbox Series X
1.3 A at 120V for the Xbox Series X.
Gaming PC
5.4 A at 120V for the GeForce RTX 5070 PC.
Watts to Amps Calculator
Convert any wattage to amps at 120V or 240V.