Appliance Amperage

How Many Amps Does a Freezer Use?

The running amps a freezer draws, the watts-to-amps math behind it, and the branch circuit this page shows it on, with what the code permits.

Quick answer: Frigidaire's specification sheet for the FFFC07M4N 7 cu. ft. chest freezer lists Voltage Rating "120V/60Hz/5A", Connected Load (kW rating) @ 120 Volts ".6", Amps @ 120 Volts "5" and Minimum Circuit Required (Amps) "15": 5 amps at 120V, the current its maker prints. The motor briefly surges higher at startup. This page shows it on a dedicated 20A / 120V circuit. Frigidaire's freezer sheets (the FFFC07M4N chest, FFFH21F6Q upright and FGCH25M8L chest) each list Minimum Circuit Required (Amps) "15" and note "An electrical supply with grounded three-prong receptacle is required." The code sizes its circuit from the load: a circuit of its own that ends in a single receptacle may supply any load within its rating (NEC 210.22), and where it ends in a duplex receptacle NEC 210.23(B)(1) holds a freezer not fastened in place to 80 percent of the circuit, each checked against the amperes its nameplate prints. Where its nameplate prints amps, those govern; watts ÷ volts is the current only of a heating element.

Will a freezer Run on Your Circuit?


Freezer Amps by Size

Watts, volts and amps for each row as its document prints them; a row whose document prints no amps shows its watts over its volts

Swipe the table sideways to see the rest of its columns. →

FreezerWattsVoltsAmps
Frigidaire FFFC07M4N, 7.2 cu ft chest (120 V)600 W120V5 A
Frigidaire FFFH21F6Q, 20.5 cu ft upright (115 V)600 W115V5 A
Frigidaire FGCH25M8L, 24.6 cu ft chest (115 V)600 W115V5 A

Each row's figures as its document prints them, not code data; your appliance's nameplate governs. Motor loads also draw a brief startup surge above their running current.

Freezer Circuit

Figures for the Frigidaire FFFC07M4N and the circuit shown for a freezer (NEC 210.8(A), 422.10)

Swipe the table sideways to see the rest of its columns. →

Watts (Frigidaire FFFC07M4N)600 W
Voltage120V
Running amps5 A
Startup surgeYes (motor)
Circuit shown20A / 120V dedicated

Frigidaire lists a connected load of .6 kW and 5 amps for its 7.2 cu ft FFFC07M4N chest freezer at 120 volts, and the same .6 kW and 5 amps at 115 volts for its 20.5 cu ft FFFH21F6Q upright and 24.6 cu ft FGCH25M8L chest, each with a 15 A minimum circuit; the compressor adds a brief surge at startup. A freezer in a garage or basement on a GFCI should have a quality one to avoid nuisance trips. GFCI: plugged into a receptacle in a dwelling location NEC 2023 210.8(A) lists (210.8(A)(2) "Garages and also accessory buildings that have a floor located at or below grade level not intended as habitable rooms and limited to storage areas, work areas, and areas of similar use", 210.8(A)(5) "Basements"), a freezer needs GFCI protection; 210.8(A) reaches 125-volt through 250-volt receptacles supplied by single-phase branch circuits rated 150 volts or less to ground. Which edition applies is the one your jurisdiction has adopted. The amps here are the current the Frigidaire FFFC07M4N's maker prints; your own unit's nameplate amps are its current; a continuous load (3 hours or more) may use at most 80% of the breaker, the same rule as rating the breaker at 125% of it (NEC 210.20(A)). The nameplate lists the exact draw and governs over the figure on this page.

Source: Frigidaire Freezer FFFC07M4NW, 7 Cu. Ft. Chest, specification sheet (08/13), read 2026-11-12.

Adding this on a new circuit? Check whether your panel can handle it (the NEC 220.87 service check), or size the breaker for the load.


Convert Watts to Amps

Watts divided by volts is the current only of a heating element, so for a freezer the converter below gives a rough figure, not its current. The amps its nameplate prints are its current; where it prints only watts, the maker's documentation or a measured current gives the amps. The power factor field changes the conversion only where you know the unit's power factor.

The code sections this page cites are named in the source receipt.


Frequently Asked Questions

How many amps does a freezer use?

Frigidaire's specification sheet for the FFFC07M4N 7 cu. ft. chest freezer lists Voltage Rating "120V/60Hz/5A", Connected Load (kW rating) @ 120 Volts ".6", Amps @ 120 Volts "5" and Minimum Circuit Required (Amps) "15". That is 5 amps at 120 volts, the current its maker prints. Because it is a motor load, it surges to several times that for a moment at startup. For your unit's own draw, read the amperes on its nameplate where it prints them: watts divided by volts is the current only of a heating element. Frigidaire lists a connected load of .6 kW and 5 amps for its 7.2 cu ft FFFC07M4N chest freezer at 120 volts, and the same .6 kW and 5 amps at 115 volts for its 20.5 cu ft FFFH21F6Q upright and 24.6 cu ft FGCH25M8L chest, each with a 15 A minimum circuit; the compressor adds a brief surge at startup. A freezer in a garage or basement on a GFCI should have a quality one to avoid nuisance trips. GFCI: plugged into a receptacle in a dwelling location NEC 2023 210.8(A) lists (210.8(A)(2) "Garages and also accessory buildings that have a floor located at or below grade level not intended as habitable rooms and limited to storage areas, work areas, and areas of similar use", 210.8(A)(5) "Basements"), a freezer needs GFCI protection; 210.8(A) reaches 125-volt through 250-volt receptacles supplied by single-phase branch circuits rated 150 volts or less to ground. Which edition applies is the one your jurisdiction has adopted.

What size breaker for a freezer?

This page shows a freezer on a dedicated 20A / 120V circuit. Frigidaire's freezer sheets (the FFFC07M4N chest, FFFH21F6Q upright and FGCH25M8L chest) each list Minimum Circuit Required (Amps) "15" and note "An electrical supply with grounded three-prong receptacle is required." The code sizes its circuit from the load: a circuit of its own that ends in a single receptacle may supply any load within its rating (NEC 210.22), and where it ends in a duplex receptacle NEC 210.23(B)(1) holds a freezer not fastened in place to 80 percent of the circuit, each checked against the amperes its nameplate prints. On a circuit of its own that ends in a single receptacle it may supply any load within the circuit's rating (NEC 210.22); where that circuit ends in a duplex receptacle, which is two receptacles, NEC 210.23(B)(1) holds cord-and-plug equipment not fastened in place to 80 percent of the circuit, 16A on that 20A circuit, and Table 210.21(B)(2) holds a receptacle's load to 16A on a 20A receptacle or 12A on a 15A one. Each is checked against the amperes its nameplate prints; the 5 amps is the current the Frigidaire FFFC07M4N's maker prints.

How do I calculate the amps a freezer draws?

Read the amperes printed on its nameplate. Watts divided by volts is the current only of a heating element with no motor, fan, pump, compressor or electronics, so for a freezer the nameplate amps are the figure to use. The figure on this page, 5 amps, is the current the Frigidaire FFFC07M4N's maker prints; your own unit's nameplate prints its own. Add a startup surge of several times that for a fraction of a second on the motor. Your appliance's nameplate governs over the figure on this page.

Does the size of a freezer change the amps?

Yes. By the figures each row's document prints, Frigidaire FFFC07M4N, 7.2 cu ft chest (120 V) at 600 W is 5 amps at 120 V, and Frigidaire FGCH25M8L, 24.6 cu ft chest (115 V) at 600 W is 5 amps at 115 V. See the table above. The rating on the nameplate is the number to size the circuit to.

How many amps does a chest freezer use?

Same answer: chest freezer is another name for a freezer. It draws 5 amps at 120V, the current the Frigidaire FFFC07M4N's maker prints,shown here on a dedicated 20A / 120V circuit. Frigidaire lists a connected load of .6 kW and 5 amps for its 7.2 cu ft FFFC07M4N chest freezer at 120 volts, and the same .6 kW and 5 amps at 115 volts for its 20.5 cu ft FFFH21F6Q upright and 24.6 cu ft FGCH25M8L chest, each with a 15 A minimum circuit; the compressor adds a brief surge at startup. A freezer in a garage or basement on a GFCI should have a quality one to avoid nuisance trips. GFCI: plugged into a receptacle in a dwelling location NEC 2023 210.8(A) lists (210.8(A)(2) "Garages and also accessory buildings that have a floor located at or below grade level not intended as habitable rooms and limited to storage areas, work areas, and areas of similar use", 210.8(A)(5) "Basements"), a freezer needs GFCI protection; 210.8(A) reaches 125-volt through 250-volt receptacles supplied by single-phase branch circuits rated 150 volts or less to ground. Which edition applies is the one your jurisdiction has adopted.


How Many Amps Do Other Appliances Use?