Appliance Amperage
How Many Amps Does a Sump Pump Use?
The running amps a sump pump draws, the watts-to-amps math behind it, and the branch circuit this page shows it on, with what the code permits.
Will a sump pump Run on Your Circuit?
Sump Pump Circuit
Figures for the Liberty 250 and the circuit shown for a sump pump (NEC 210.8(D), 422.10)
Swipe the table sideways to see the rest of its columns. →
| Volt-amperes (Liberty 250) | 598 VA |
| Voltage | 115V |
| Running amps | 5.2 A |
| Startup surge | Yes (motor) |
| Circuit shown | 15A / 120V dedicated |
Liberty's 250 sump pump (1/3 hp, 115 V) lists 5.2 full-load amps and 8 locked-rotor amps, the current its motor draws for a moment at startup, and it should be on its own dedicated circuit so nothing else can trip the breaker and leave the pit unprotected. Test its GFCI seasonally. GFCI: NEC 2023 210.8(D) requires GFCI protection for the branch circuit or outlet supplying a sump pump (210.8(D)(6) "Sump pumps") rated 150 volts or less to ground and 60 amperes or less, hardwired or plugged in, wherever it is installed; which edition applies is the one your jurisdiction has adopted. The amps here are the current the Liberty 250's maker prints; your own unit's nameplate amps are its current; a continuous load (3 hours or more) may use at most 80% of the breaker, the same rule as rating the breaker at 125% of it (NEC 210.20(A)). The nameplate lists the exact draw and governs over the figure on this page.
Source: Liberty Pumps Pump Specification, 250-Series 1/3 hp Sump/Effluent Pumps (250_P1 R04/2025), Electrical Data, read 2026-11-12.
Adding this on a new circuit? Check whether your panel can handle it (the NEC 220.87 service check), or size the breaker for the load.
Convert Watts to Amps
Watts divided by volts is the current only of a heating element, so for a sump pump the converter below gives a rough figure, not its current. The amps its nameplate prints are its current; where it prints only watts, the maker's documentation or a measured current gives the amps. The power factor field changes the conversion only where you know the unit's power factor. The converter opens on this page's 598 VA, the Liberty 250's printed 5.2 amps times its 115 volts, entered in its watts field: at power factor 1 it gives back the 5.2 amps the maker prints, not a wattage the maker states.
The code sections this page cites are named in the source receipt.
Frequently Asked Questions
How many amps does a sump pump use?
Liberty Pumps' 250-Series electrical data lists the model 250 at HP "1/3", Voltage "115", Full Load Amps "5.2" and Locked Rotor Amps "8"; this page's volt-amperes figure is the full-load amps times 115 volts. That is 5.2 amps at 115 volts, the current its maker prints. Because it is a motor load, it surges to several times that for a moment at startup. For your unit's own draw, read the amperes on its nameplate where it prints them: watts divided by volts is the current only of a heating element. Liberty's 250 sump pump (1/3 hp, 115 V) lists 5.2 full-load amps and 8 locked-rotor amps, the current its motor draws for a moment at startup, and it should be on its own dedicated circuit so nothing else can trip the breaker and leave the pit unprotected. Test its GFCI seasonally. GFCI: NEC 2023 210.8(D) requires GFCI protection for the branch circuit or outlet supplying a sump pump (210.8(D)(6) "Sump pumps") rated 150 volts or less to ground and 60 amperes or less, hardwired or plugged in, wherever it is installed; which edition applies is the one your jurisdiction has adopted.
What size breaker for a sump pump?
This page shows a sump pump on a dedicated 15A / 120V circuit. The code sizes its circuit from the load (a circuit of its own may supply any load within its rating, NEC 210.22); this page shows it on a circuit of its own so nothing else on it can trip the breaker and leave the pit unprotected. A circuit of its own may supply any load within its rating (NEC 210.22), checked against the amperes its nameplate prints; the 5.2 amps is the current the Liberty 250's maker prints.
How do I calculate the amps a sump pump draws?
Read the amperes printed on its nameplate. Watts divided by volts is the current only of a heating element with no motor, fan, pump, compressor or electronics, so for a sump pump the nameplate amps are the figure to use. The figure on this page, 5.2 amps, is the current the Liberty 250's maker prints; your own unit's nameplate prints its own. Add a startup surge of several times that for a fraction of a second on the motor. Your appliance's nameplate governs over the figure on this page.
How many amps does a basement pump use?
Same answer: basement pump is another name for a sump pump. It draws 5.2 amps at 115V, the current the Liberty 250's maker prints,shown here on a dedicated 15A / 120V circuit. Liberty's 250 sump pump (1/3 hp, 115 V) lists 5.2 full-load amps and 8 locked-rotor amps, the current its motor draws for a moment at startup, and it should be on its own dedicated circuit so nothing else can trip the breaker and leave the pit unprotected. Test its GFCI seasonally. GFCI: NEC 2023 210.8(D) requires GFCI protection for the branch circuit or outlet supplying a sump pump (210.8(D)(6) "Sump pumps") rated 150 volts or less to ground and 60 amperes or less, hardwired or plugged in, wherever it is installed; which edition applies is the one your jurisdiction has adopted.
How Many Amps Do Other Appliances Use?
TV
0.9 A at 120V for the Samsung 55-inch Q60R.
Refrigerator
2.6 A at 120V for the GE GNE27JYMFS.
Freezer
5 A at 120V for the Frigidaire FFFC07M4N.
Mini Fridge
1.3 A at 115V for the Danby DCR033B2WM.
Microwave
12.4 A at 120V for the Panasonic NN-SN67KS.
Coffee Maker
8.8 A at 120V for the Hamilton Beach FlexBrew 49968.
Window Air Conditioner
10.3 A at 115V for the Frigidaire FFRE123ZA1.
Space Heater
12.5 A at 120V for the Lasko 758000.
Washing Machine
8 A at 120V for the Frigidaire FFTW1001PW.
Dishwasher
12 A at 120V for the Bosch SHE3AEM6N.
Garbage Disposal
6.3 A at 120V for the InSinkErator Badger 5.
Dehumidifier
8.5 A at 115V for the Frigidaire FFAD5034W1.
Hair Dryer
15.6 A at 120V for the Conair 303 Mid-Size Dryer.
Toaster
8.3 A at 120V for the Hamilton Beach PerfectToast 22408.
Electric Water Heater
18.8 A at 240V for a Rheem Performance tank.
Box Fan
0.94 A at 120V for the Air King 9723.
Air Fryer
12.9 A at 120V for the Ninja AF101.
Vacuum Cleaner
10 A at 120V for the Shark NV360.
PS5
1.8 A at 120V for the PS5 CFI-21 (disc drive attached).
Xbox Series X
1.3 A at 120V for the Xbox Series X.
Gaming PC
5.4 A at 120V for the GeForce RTX 5070 PC.
Watts to Amps Calculator
Convert any wattage to amps at 120V or 240V.
Wire & Breaker for Appliances
The exact wire gauge and breaker for hardwired appliance circuits.