Conduit Offset Bend
22.5° Conduit Offset
Everything for a 22.5 degree offset: the multiplier, the shrink, a worked example, and the calculator, all from the same math your bender uses.
The 22.5° Offset Numbers
Swipe the table sideways to see the rest of its columns. →
| Multiplier (bender chart, applied / exact 1/sin) | 2.6 / 2.61 |
| Shrink per inch of offset | 3/16″ (0.1875″) |
| 6″ offset: distance between bends | 15.6″ |
| 6″ offset: shrink to subtract | 1.13″ |
Distance between bends = offset depth × 2.6. Shrink = offset depth × 3/16″. Both bends are 22.5 degrees, rotated 180° apart. Bender charts print 2.6 at 22.5°, which the calculator applies; exact 1/sin is 2.61. The chart value is what the calculator applies, so its marks match the table on your bender (see the offset multiplier chart).
The Geometry of a 22.5° Bend
A 22.5 degree offset is two 22.5 degree bends. On a standard 3/4" EMT bender the centerline radius is 4.5″, so each 22.5 degree bend has a developed length of 1.77″ of conduit through the curve (developed length = radius × the angle in radians). That is the exact geometry the 3D renderer draws for this bend. For the developed length at every size and angle, see the bend radius and developed length reference.
Calculate Your 22.5° Offset
The calculator opens on the worked example, a 6″ offset at 22.5°. Enter your own offset depth for its mark spacing and shrink.
Bend type: 15 families, pick one
Common bends
Klein and Gardner Bender EMT hand bender take-up, with NEC Chapter 9, Table 2 radii by trade size. Greenlee's SITE-RITE hand-bender manual rates the same benders for 1/2" through 1-1/4" EMT and 1/2" through 1" rigid and IMC, and its older IM 1071 manual says 1/2" through 1" rigid: pick the type above (1-1/4" is not carried in IMC or RMC: no held bender document bends it by hand).
Shrink per inch of offset:
Show the math
- MATHTravel = Height × chart multiplier = 6 × 2.6 = 15.6"
- MATHShrink = Height × Shrink/inch = 6 × 0.1875 = 1.13"
- MATHMark spacing = 15.6"
Bender charts print a 2.6 multiplier at 22.5°, which this calculator uses. Exact 1/sin(22.5°) is 2.61, 0.5% above it; the chart is that value rounded for a tape measure, so two bends at that spacing rise 0.5% less than the depth you asked for, which is the rounding the trade accepts.
Where this number comes fromIntry Verified
- Calculated from
- Bender-chart offset multiplier (2.6), Greenlee and Gardner Bender. Marks and shrink from the bender-chart constants where a manufacturer prints the angle (offset multiplier, 3-point saddle multiplier and shrink per inch) and from bend geometry elsewhere (offset 1/sin, saddle depth/sin(half-angle), kick travel); take-up from the EMT bender profile for your conduit size, or the deduct you entered (the only take-up carried for IMC and RMC), and gain from that conduit's own radius and outside diameter. See the full receipt ↓
- Run with
- BendOffset
- Setup6" offset @ 22.5°
- Checked
- Every figure an Intry calculator computes comes from a locked source module, not hand-typed. 35,938 automated checks, one suite for the whole site rather than a per-tool count, re-derive the numbers before each deploy from the tables this site holds, read from the bender chart or geometry it was computed from and the NEC Chapter 9 Table 2 radius. This is our own deterministic gate, not a third-party audit.
- Final say
- Field-verify against the actual bend. Bender take-up varies by tool and shoe.
Intry Verified · Build 525536D · 2026-11-13
Next on this job
This run travels with its receipt: 1/2" EMT, Offset, 2 marks, developed length 15.6".
- Conduit fillCarries 1/2" EMT into the fill calculator; add the conductors you are pulling.
- Wire sizeCarries the receipt only: a bend run knows no load, so enter the amps, voltage and one-way distance there.
- Box fillCarries the receipt only: a bend run knows no box, so enter the box and its conductors there.
One question
Did this help you on the job?
Check your working
Each problem is worked with the bender-chart multiplier and shrink the calculator above applies. Work a problem on paper first, then open its working to check yours. We chose these problems' numbers; your own numbers go in the calculator.
4" offset @ 22.5°, 1/2" EMT
Show the math
- MATHTravel = Height × chart multiplier = 4 × 2.6 = 10.4"
- MATHShrink = Height × Shrink/inch = 4 × 0.1875 = 0.75"
- MATHMark spacing = 10.4"
Bender charts print a 2.6 multiplier at 22.5°, which this calculator uses. Exact 1/sin(22.5°) is 2.61, 0.5% above it; the chart is that value rounded for a tape measure, so two bends at that spacing rise 0.5% less than the depth you asked for, which is the rounding the trade accepts.
10" offset @ 22.5°, 3/4" EMT
Show the math
- MATHTravel = Height × chart multiplier = 10 × 2.6 = 26"
- MATHShrink = Height × Shrink/inch = 10 × 0.1875 = 1.88"
- MATHMark spacing = 26"
Bender charts print a 2.6 multiplier at 22.5°, which this calculator uses. Exact 1/sin(22.5°) is 2.61, 0.5% above it; the chart is that value rounded for a tape measure, so two bends at that spacing rise 0.5% less than the depth you asked for, which is the rounding the trade accepts.
12" offset @ 22.5°, 1" EMT
Show the math
- MATHTravel = Height × chart multiplier = 12 × 2.6 = 31.2"
- MATHShrink = Height × Shrink/inch = 12 × 0.1875 = 2.25"
- MATHMark spacing = 31.2"
Bender charts print a 2.6 multiplier at 22.5°, which this calculator uses. Exact 1/sin(22.5°) is 2.61, 0.5% above it; the chart is that value rounded for a tape measure, so two bends at that spacing rise 0.5% less than the depth you asked for, which is the rounding the trade accepts.
Frequently Asked Questions
What is the multiplier for a 22.5 degree offset?
The multiplier for a 22.5 degree offset is 2.6, the constant bender-manufacturer charts print, and it is what this calculator applies. It is the rounded cosecant: exact 1/sin(22.5 degrees) is 2.61. Multiply your offset depth by the multiplier to get the distance between the two bend marks. For a 6 inch offset that is 6 x 2.6 = 15.6 inches between marks.
How much does a 22.5 degree offset shrink?
A 22.5 degree offset shrinks 3/16 inch for every inch of offset depth. So a 6 inch offset shrinks the run about 1.13 inches, and a 4 inch offset shrinks about 0.75 inches. Subtract the shrink from your measurement so the conduit ends and fittings still land where you need them.
How do you bend a 22.5 degree offset?
Mark the first bend where the offset should start, then measure 15.6 inches (for a 6 inch offset) toward the free end and mark the second bend. Bend both marks to 22.5 degrees, keeping the bends in the same plane and rotating the conduit 180 degrees between them so the offset lies flat. Check the depth against your target and subtract the 1.13 inch shrink when you cut or measure the run.
When should I use a 22.5 degree offset?
A 22.5 degree offset is a gentle, long offset. Its low angle pulls wire easily and looks clean, and it shrinks little (3/16 inch per inch), but the bends sit far apart (multiplier 2.6), so it needs room. Use it for shallow steps over conduit or where you want the easiest wire pull.