Conduit Bending

Conduit Offset Bend Calculator

An offset steps the conduit over an obstacle with two equal bends. Here is the multiplier and shrink for every common angle, the calculator, and a dedicated page for each angle.

Quick answer: Distance between bends = offset depth × multiplier (30° = 2, 45° = 1.4, 22.5° = 2.6). Then subtract the shrink (30° = 1/4″ per inch of offset). A 6″ offset at 30°: marks 12″ apart, run shrinks 1.5″.

Offset Multiplier & Shrink by Angle

Multiplier and shrink are the bender-chart constants (the multiplier is the rounded 1/sin); the calculator applies both.

Swipe the table sideways to see the rest of its columns. →

AngleMultiplierShrink / inch6″ Offset: Marks
10°6.01/16″36″
22.5°2.63/16″15.6″
30°2.01/4″12″
45°1.43/8″8.4″
60°1.21/2″7.2″ (not bendable in 1-1/4" EMT)

The marks are the same on every EMT size, but whether the bend can be made is not: at the NEC Chapter 9, Table 2 bend radius the two arcs need straight conduit between them. In 1-1/4" EMT a 6" offset at 60° cannot be bent (the two 60° arcs on its 7.25" bend radius would overlap); the smallest offset at 60° in that size is 7" at the bender-chart spacing this calculator lays out (exact 1/sin spacing would need 7-1/4" instead, a spacing this calculator does not lay out at a charted angle). The calculator refuses such a bend and names the smallest depth that works.

Multipliers shown are the bender-chart values (Greenlee, Gardner Bender) and they are what the calculator applies, so its marks match the chart on your bender. The exact 1/sin values they round (5.76, 2.61, 1.41, and so on) are shown beside them on the offset multiplier chart. Keep both bends the same angle.


Pick Your Offset Angle


Offset Calculator

Bend type: 15 families, pick one

Offsets
Saddles
90s and kicks
Racks of conduit
Large radius and corners
The whole stick

Common bends

Klein and Gardner Bender EMT hand bender take-up, with NEC Chapter 9, Table 2 radii by trade size. Greenlee's SITE-RITE hand-bender manual rates the same benders for 1/2" through 1-1/4" EMT and 1/2" through 1" rigid and IMC, and its older IM 1071 manual says 1/2" through 1" rigid: pick the type above (1-1/4" is not carried in IMC or RMC: no held bender document bends it by hand).

Shrink per inch of offset:

10°: 1/16"15°: 0.13222.5°: 3/16"30°: 1/4"45°: 3/8"60°: 1/2"
Offset bend: 4" rise at these marks, 30°4" rise at marks8" travelMark 1Mark 230°
First bend mark0"
Second bend mark8"
Travel8″
Mark Spacing8″
Shrink (total)1″
Multiplier applied2x
Actual rise at these marks4″
Shrink1"
Developed Length
8"
Show the math
  1. MATHTravel = Height × chart multiplier = 4 × 2 = 8"
  2. MATHShrink = Height × Shrink/inch = 4 × 0.2500 = 1"
  3. MATHMark spacing = 8"

Bender charts print a 2.0 multiplier at 30°, which this calculator uses, and exact 1/sin(30°) is the same 2.00, so two bends at that spacing rise exactly the depth you asked for.

Where this number comes fromIntry Verified
Calculated from
Bender-chart offset multiplier (2.0), Greenlee and Gardner Bender. Marks and shrink from the bender-chart constants where a manufacturer prints the angle (offset multiplier, 3-point saddle multiplier and shrink per inch) and from bend geometry elsewhere (offset 1/sin, saddle depth/sin(half-angle), kick travel); take-up from the EMT bender profile for your conduit size, or the deduct you entered (the only take-up carried for IMC and RMC), and gain from that conduit's own radius and outside diameter. See the full receipt ↓
Run with
  • BendOffset
  • Setup4" offset @ 30°
Checked
Every figure an Intry calculator computes comes from a locked source module, not hand-typed. 35,938 automated checks, one suite for the whole site rather than a per-tool count, re-derive the numbers before each deploy from the tables this site holds, read from the bender chart or geometry it was computed from and the NEC Chapter 9 Table 2 radius. This is our own deterministic gate, not a third-party audit.
Final say
Field-verify against the actual bend. Bender take-up varies by tool and shoe.
What Intry Verified means

Intry Verified · Build 525536D · 2026-11-13

Next on this job

This run travels with its receipt: 1/2" EMT, Offset, 2 marks, developed length 8".

  • Conduit fillCarries 1/2" EMT into the fill calculator; add the conductors you are pulling.
  • Wire sizeCarries the receipt only: a bend run knows no load, so enter the amps, voltage and one-way distance there.
  • Box fillCarries the receipt only: a bend run knows no box, so enter the box and its conductors there.

One question

Did this help you on the job?

First bend mark: 0"8" total

Intry Verified. The offset multiplier, shrink, and mark spacing this page shows are computed by the locked conduit-bending geometry engine from the bend angle (1/sin θ), never hand-typed. Those figures are computed by a locked engine straight from the source it cites, not hand-typed, and that computation re-runs inside a deterministic test on every deploy. Source-checked. Locked. This is our own deterministic gate, not a third-party audit. What Intry Verified means

Run this in your AI. Ask Claude or ChatGPT to lay out the marks and shrink for a 6 inch offset at 30 degrees in 3/4 inch EMT and it runs the Intry Conduit Offset Bend Calculator live, handing back the verdict with its cited source instead of a guess. Then keep the reading as one job in the Intry app.

Frequently Asked Questions

How do you calculate a conduit offset?

Two numbers do it. The distance between the two bend marks equals the offset depth times the multiplier for your bend angle, the constant bender charts print (the rounded 1/sin): 30 degrees = 2.0, 45 degrees = 1.4, and 22.5 degrees = 2.6. Then account for shrink, the amount the conduit shortens along its run, which is a fixed amount per inch of offset depth for each angle (30 degrees = 1/4 inch per inch). For example, a 6-inch offset at 30 degrees puts the marks 12 inches apart (6 x 2) and shrinks the run 1.5 inches (6 x 1/4).

What is the multiplier for a conduit offset?

The multiplier converts the offset depth into the distance between your two bend marks. Bender-manufacturer charts print a constant for each standard angle, and that is what this calculator applies: 6.0 at 10 degrees, 2.6 at 22.5 degrees, 2.0 at 30 degrees, 1.4 at 45 degrees, and 1.2 at 60 degrees. Each is 1 divided by the sine of the bend angle, rounded for a tape measure (the exact 1/sin at 60 degrees is 1.15, and at 22.5 degrees 2.61). A larger angle gives a smaller multiplier, so the bends sit closer together but the run shrinks more.

What angle is best for a conduit offset?

30 degrees is an all-around choice because its multiplier is exactly 2, making the math easy, and its shrink is moderate. Use a smaller angle like 10 or 22.5 degrees for a long, gentle offset that pulls wire easily; use 45 degrees for a tight offset around a close obstacle, accepting more shrink and a harder pull. Match the angle to the space and keep both bends the same angle.

What is shrink in a conduit offset?

Shrink is how much shorter the conduit becomes along its straight run once you put the offset in it, because the diagonal travel between the bends uses up length. You subtract it so the fittings still land where you need them. It is a fixed amount per inch of offset depth by angle: 1/16 inch at 10 degrees, 3/16 at 22.5, 1/4 at 30, 3/8 at 45, and 1/2 at 60 degrees. Deeper offsets and steeper angles shrink more.


Related Bending Tools