Bending Reference
Conduit Bend Radius and Developed Length
The standard one-shot centerline bend radius by EMT size, the NEC Chapter 9, Table 2 value a hand bender is built to, and the developed length of a bend, from the same verified profiles the calculator and 3D renderer use.
Standard Centerline Bend Radius by EMT Size
Standard EMT hand benders are built to the one-shot centerline radius in NEC Chapter 9, Table 2, one per conduit size. That radius is what take-up and mark spacing come from; the field gain adds one conduit diameter on top of the arc savings. An individual shoe can run slightly larger than the tabulated value, so verify with a test bend. The tube outer diameter and wall come from ANSI C80.3 and UL 797.
Centerline bend radius (both NEC Chapter 9, Table 2 columns), take-up, and gain by EMT trade size
Swipe the table sideways to see the rest of its columns. →
| Conduit Size | Centerline Radius (one-shot) | Other Bends (Table 2 column) | Take-Up | Gain (90°) |
|---|---|---|---|---|
| 1/2" EMT | 4" | 4" | 5" | 2.42" |
| 3/4" EMT | 4.5" | 5" | 6" | 2.85" |
| 1" EMT | 5.75" | 6" | 8" | 3.63" |
| 1-1/4" EMT | 7.25" | 8" | 11" † | 4.62" |
† Both take-up tables we hold, Klein and Gardner Bender's, stop at 1", so the 1-1/4" take-up is a field value no manufacturer document we hold confirms. Check it against your own bender before you cut.
Where the Standard Radius Comes From
The standard centerline radius and the NEC value are the same table, which is a common source of confusion:
- Standard centerline radius (this page) is the one-shot / full-shoe bend radius tabulated in NEC Chapter 9, Table 2, 4.5" for 3/4" EMT. It is the radius a hand bender is built to make, and it is what field marks and cut lengths are figured from.
- The same NEC Chapter 9, Table 2 sets the radius floor so a bend never gets tight enough to damage the conductors inside, and it prints two columns: one-shot and full-shoe benders (4.5" for 3/4" EMT) and other bends (5"). For EMT, 358.24(A) points at the one-shot column for any field bend, which is why a standard hand bend and the code minimum line up. The other-bends column, shown beside it in the table above, is the floor named by 348.24(A), 350.24(A), 356.24(A) and 362.24(A) for FMC, LFMC, LFNC and ENT at the same trade size; it is printed here because the table prints it, never as an EMT requirement.
A specific bender shoe can run slightly larger than the tabulated value, so for a precise cut, verify the radius on your own bender with a test bend.
Developed Length of a Bend
The developed length of a single bend is the length of conduit that runs through the curve itself, measured along the centerline:
It scales straight with both the radius and the angle. The table below is the developed length, in inches, for each standard EMT bender radius across common bend angles.
Developed length (inches) by EMT size and bend angle
Swipe the table sideways to see the rest of its columns. →
| Size (Radius) | 10° | 22.5° | 30° | 45° | 60° | 90° |
|---|---|---|---|---|---|---|
| 1/2" (4") | 0.70 | 1.57 | 2.09 | 3.14 | 4.19 | 6.28 |
| 3/4" (4.5") | 0.79 | 1.77 | 2.36 | 3.53 | 4.71 | 7.07 |
| 1" (5.75") | 1.00 | 2.26 | 3.01 | 4.52 | 6.02 | 9.03 |
| 1-1/4" (7.25") | 1.27 | 2.85 | 3.80 | 5.69 | 7.59 | 11.39 |
Worked Exam Problems
Two developed-length problems of the kind apprentice exams set, worked from the formula above. Every answer is computed from the values the problem gives, nothing memorized.
Problem 1. A 15° bend is made on a 25" centerline radius, as a large-radius or factory bend is. How long is its developed length?
Step 1: convert the angle to radians. 15 × π ÷ 180 = 0.2618 radians.
Step 2: multiply by the radius. 25 × 0.2618 = 6.54 inches.
Answer: the developed length is 6.54". The same formula works for any radius, which is why a tight bender radius develops far less length than a wide factory sweep at the same angle.
Problem 2. Write the developed length of a 90° bend as a formula, then work it for a 3/4" EMT bender.
Step 1: the formula. A 90 is a quarter circle, so developed length = radius × (π ÷ 2) = radius × 1.5708.
Step 2: put in the 3/4" radius. 4.5 × 1.5708 = 7.07 inches.
Answer: developed length = radius × π/2, which is 7.07" for 3/4" EMT. The developed-length chart above gives every size: 6.28″ for 1/2", 7.07″ for 3/4", 9.03″ for 1", 11.39″ for 1-1/4".
The code sections this page cites are named in the source receipt.
Frequently Asked Questions
What is the bend radius of 3/4 inch EMT?
The standard one-shot centerline bend radius for 3/4 inch EMT is 4.5 inches, the value tabulated in NEC Chapter 9, Table 2 that a hand bender is built to approximate. That radius is what the take-up and mark spacing come from (the field gain adds one conduit diameter on top of it). By EMT size the standard centerline radius is 4 inches for 1/2 inch, 4.5 inches for 3/4 inch, 5.75 inches for 1 inch, and 7.25 inches for 1-1/4 inch. An individual bender shoe can run slightly larger, so verify against your own bender with a test bend.
How do you calculate the developed length of a bend?
The developed length of a single bend is the length of conduit that travels through the curve: developed length = centerline radius x bend angle in radians, which is the same as (angle / 360) x 2 x pi x radius. For a 15 degree bend at a 25 inch centerline radius, developed length = 25 x (15 x pi / 180) = 6.54 inches. On a standard 3/4 inch EMT bender (4.5 inch radius) a 90 degree bend has a developed length of 7.07 inches.
Where does the standard bend radius come from, and is it the NEC value?
They come from the same place. NEC Chapter 9, Table 2 lists the centerline radius of a one-shot or full-shoe bend by conduit size (4.5 inches for 3/4 inch EMT), which is the radius a hand bender is built to make; the same table sets the radius floor so a bend never damages the conductors inside. So the standard hand-bend radius is the NEC Table 2 one-shot value, and the take-up and cut lengths are figured from it. A specific bender shoe can run slightly larger than the tabulated figure, so verify against your own bender with a test bend.
Does the bend radius change with conduit size?
Yes. A larger conduit uses a larger bender, so the centerline radius grows with size: 4 inches for 1/2 inch EMT, 4.5 inches for 3/4 inch, 5.75 inches for 1 inch, and 7.25 inches for 1-1/4 inch. Because developed length is radius times angle, a bigger radius also means a longer developed length for the same angle, which is why larger conduit saves more material (more gain) on a 90.
What is the developed length of a 90 degree bend?
For a 90 degree bend, developed length = radius x (pi / 2), a quarter of the full circle. On standard EMT benders that is 6.28 inches for 1/2 inch (4 inch radius), 7.07 inches for 3/4 inch (4.5 inch radius), 9.03 inches for 1 inch (5.75 inch radius), and 11.39 inches for 1-1/4 inch (7.25 inch radius). Developed length is the arc through the bend itself; to size a whole piece with 90s you subtract gain from the summed legs instead.
A 15 degree bend is made on a 25 inch centerline radius. How long is its developed length?
The developed length is 6.54 inches. Developed length is the conduit that runs through the curve, and it equals the centerline radius times the bend angle in radians: 25 x (15 x pi / 180) = 6.54 inches. Only the radius and angle the problem gives are used, so the same formula answers any radius, including a large-radius factory bend.
How do you write the developed length of a 90 degree bend as a formula?
Developed length = centerline radius times (pi / 2). A 90 degree bend is a quarter of a full circle, so its arc is the radius times pi/2 (1.5708 radians). On a standard 3/4 inch EMT bender the centerline radius is 4.5 inches, so the developed length is 4.5 x 1.5708 = 7.07 inches. The developed length chart above gives the value for every EMT size.
More Bending References
Conduit Bending Calculator
Calculate marks for every bend family the calculator carries and see each bend as an interactive 3D rendering or flat diagram, from verified bender profiles.
Conduit Gain Chart
The material a 90 saves versus a square corner, and how to size a whole bent piece.
90° Deduction Chart
Take-up, deduct, radius, and gain for 1/2" through 1-1/4" EMT.
Offset Multiplier Chart
Multipliers and shrink per inch for 10° through 60° offset bends.