Conduit Offset Bend

45° Conduit Offset

Everything for a 45 degree offset: the multiplier, the shrink, a worked example, and the calculator, all from the same math your bender uses.

Quick answer: A 45° offset uses the bender-chart multiplier 1.4 (exact 1/sin is 1.41) and shrinks 3/8″ per inch of offset. A 6″ offset → bends 8.4″ apart, run shrinks 2.25″.

The 45° Offset Numbers

Swipe the table sideways to see the rest of its columns. →

Multiplier (bender chart, applied / exact 1/sin)1.4 / 1.41
Shrink per inch of offset3/8″ (0.3750″)
6″ offset: distance between bends8.4″
6″ offset: shrink to subtract2.25″

Distance between bends = offset depth × 1.4. Shrink = offset depth × 3/8″. Both bends are 45 degrees, rotated 180° apart. Bender charts print 1.4 at 45°, which the calculator applies; exact 1/sin is 1.41. The chart value is what the calculator applies, so its marks match the table on your bender (see the offset multiplier chart).


The Geometry of a 45° Bend

A 45 degree offset is two 45 degree bends. On a standard 3/4" EMT bender the centerline radius is 4.5″, so each 45 degree bend has a developed length of 3.53″ of conduit through the curve (developed length = radius × the angle in radians). That is the exact geometry the 3D renderer draws for this bend. For the developed length at every size and angle, see the bend radius and developed length reference.


Calculate Your 45° Offset

The calculator opens on the worked example, a 6″ offset at 45°. Enter your own offset depth for its mark spacing and shrink.

Bend type: 15 families, pick one

Offsets
Saddles
90s and kicks
Racks of conduit
Large radius and corners
The whole stick

Common bends

Klein and Gardner Bender EMT hand bender take-up, with NEC Chapter 9, Table 2 radii by trade size. Greenlee's SITE-RITE hand-bender manual rates the same benders for 1/2" through 1-1/4" EMT and 1/2" through 1" rigid and IMC, and its older IM 1071 manual says 1/2" through 1" rigid: pick the type above (1-1/4" is not carried in IMC or RMC: no held bender document bends it by hand).

Shrink per inch of offset:

10°: 1/16"15°: 0.13222.5°: 3/16"30°: 1/4"45°: 3/8"60°: 1/2"
Offset bend: 5.94" rise at these marks, 45°5.94" rise at marks8.4" travelMark 1Mark 245°
First bend mark0"
Second bend mark8.4"
Travel8.4″
Mark Spacing8.4″
Shrink (total)2.25″
Multiplier applied1.4x
Actual rise at these marks5.94″
Shrink2.25"
Developed Length
8.4"
Show the math
  1. MATHTravel = Height × chart multiplier = 6 × 1.4 = 8.4"
  2. MATHShrink = Height × Shrink/inch = 6 × 0.3750 = 2.25"
  3. MATHMark spacing = 8.4"

Bender charts print a 1.4 multiplier at 45°, which this calculator uses. Exact 1/sin(45°) is 1.41, 1.0% above it; the chart is that value rounded for a tape measure, so two bends at that spacing rise 1.0% less than the depth you asked for, which is the rounding the trade accepts.

Where this number comes fromIntry Verified
Calculated from
Bender-chart offset multiplier (1.4), Greenlee and Gardner Bender. Marks and shrink from the bender-chart constants where a manufacturer prints the angle (offset multiplier, 3-point saddle multiplier and shrink per inch) and from bend geometry elsewhere (offset 1/sin, saddle depth/sin(half-angle), kick travel); take-up from the EMT bender profile for your conduit size, or the deduct you entered (the only take-up carried for IMC and RMC), and gain from that conduit's own radius and outside diameter. See the full receipt ↓
Run with
  • BendOffset
  • Setup6" offset @ 45°
Checked
Every figure an Intry calculator computes comes from a locked source module, not hand-typed. 35,938 automated checks, one suite for the whole site rather than a per-tool count, re-derive the numbers before each deploy from the tables this site holds, read from the bender chart or geometry it was computed from and the NEC Chapter 9 Table 2 radius. This is our own deterministic gate, not a third-party audit.
Final say
Field-verify against the actual bend. Bender take-up varies by tool and shoe.
What Intry Verified means

Intry Verified · Build 525536D · 2026-11-13

Next on this job

This run travels with its receipt: 1/2" EMT, Offset, 2 marks, developed length 8.4".

  • Conduit fillCarries 1/2" EMT into the fill calculator; add the conductors you are pulling.
  • Wire sizeCarries the receipt only: a bend run knows no load, so enter the amps, voltage and one-way distance there.
  • Box fillCarries the receipt only: a bend run knows no box, so enter the box and its conductors there.

One question

Did this help you on the job?

First bend mark: 0"8.4" total

Frequently Asked Questions

What is the multiplier for a 45 degree offset?

The multiplier for a 45 degree offset is 1.4, the constant bender-manufacturer charts print, and it is what this calculator applies. It is the rounded cosecant: exact 1/sin(45 degrees) is 1.41. Multiply your offset depth by the multiplier to get the distance between the two bend marks. For a 6 inch offset that is 6 x 1.4 = 8.4 inches between marks.

How much does a 45 degree offset shrink?

A 45 degree offset shrinks 3/8 inch for every inch of offset depth. So a 6 inch offset shrinks the run about 2.25 inches, and a 4 inch offset shrinks about 1.5 inches. Subtract the shrink from your measurement so the conduit ends and fittings still land where you need them.

How do you bend a 45 degree offset?

Mark the first bend where the offset should start, then measure 8.4 inches (for a 6 inch offset) toward the free end and mark the second bend. Bend both marks to 45 degrees, keeping the bends in the same plane and rotating the conduit 180 degrees between them so the offset lies flat. Check the depth against your target and subtract the 2.25 inch shrink when you cut or measure the run.

When should I use a 45 degree offset?

A 45 degree offset is a tight offset for close obstacles. Its high angle keeps the bends close together (multiplier 1.4) so it fits small spaces, but it shrinks more (3/8 inch per inch) and is a harder wire pull. Use it when you must step over something in a short distance.


Other Offset Angles